ECB violations
Exchange Plaza, Manhattan • Block 00020 • Lot 0016
84 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Apr 25, 2025 | 39146029Z | ACTIVE | CLASS - 1 | CLASS 1:FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERV... | $1,250 | $0 | Jul 3, 2025 |
| Apr 25, 2025 | 39146030X | ACTIVE | CLASS - 1 | CLASS 1:FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERV... | $1,250 | $0 | Jul 3, 2025 |
| Feb 19, 2025 | 39139380K | ACTIVE | CLASS - 1 | UPON INSPECTION OF ESCALATORS THERE ISNO SERVICE TO DEVICES AS PER CODE 1 RCNY 11-02 RETURN TO SERVICE. | $625 | $0 | May 21, 2026 |
| Feb 19, 2025 | 39139379N | ACTIVE | CLASS - 1 | UPON INSPECTION OF ESCALATORS THERE ISNO SERVICE TO DEVICES AS PER CODE 1 RCNY 11-02 RETURN TO SERVICE. | $625 | $0 | May 21, 2026 |
| Sep 9, 2024 | 39124364Z | ACTIVE | CLASS - 2 | CLASS 2 RESTORE TO SERVICE. ENTIRE DEVICE IS SHUT DOWN. NEED TO REPAIR. | $310 | $0 | Nov 14, 2024 |
| Jul 22, 2024 | 39119572R | ACTIVE | CLASS - 2 | RESTORE TO SERVICE | $310 | $0 | Sep 26, 2024 |
| Jul 22, 2024 | 39119573Z | ACTIVE | CLASS - 2 | RESTORE TO SERVICE | $625 | $0 | Jul 22, 2025 |
| Jul 22, 2024 | 39119662K | ACTIVE | CLASS - 2 | AS PER DCP AGENCY RECORDS, THERE IS A PAIR OF ESCALATORS LISTED IN THE AMENITIES LIST FOR THE 24 HOUR ACCESS POPS. AT... | $5,000 | $0 | Mar 13, 2025 |
| Jun 17, 2024 | 37028723Z | RESOLVE | CLASS - 2 | A.C.27-929.1,FAILURE TO COMPLETE INSTALLATION OF FULL SYSTEM OF AUTOMATIC SPRINKLERS & FILE FINAL SPRINKLER REPORT PR... | $6,250 | $0 | Mar 27, 2025 |
| Sep 25, 2023 | 39095726R | RESOLVE | CLASS - 1 | CLASS 1, 97/X/17 ESCALATOR IS NOT WORKING INOPERATIVE REPAIR. | $0 | $0 | Sep 11, 2025 |
| Feb 28, 2023 | 37025309J | RESOLVE | CLASS - 2 | 27-929.1 FAILURE TO COMPLETE THE INSTALLATION OF A FULL SYSTEM OF AUTOMATIC SPRINKLERS AND FILE SPRINKLER REPORT PREP... | $6,250 | $0 | Jun 22, 2023 |
| May 13, 2022 | 35654523J | RESOLVE | CLASS - 2 | TEMP CONST EQUIPMENT ONSITE EXPIRED PERMIT.NOTE:ATOI OF 31STY OCCUPIEDBLDG I OBSERVED SIDEWALKSHED INSTALLED ON PREMI... | $0 | $0 | Aug 11, 2022 |
| Nov 1, 2021 | 37022689R | RESOLVE | CLASS - 2 | 27-929.1 FAILURE TO COMPLETE INSTALLATION OF FULL SYSTEM OF AUTOMATIC SPRINKLERS AND FILE FINAL SPRINKLER REPORT PREP... | $3,125 | $0 | Jul 21, 2022 |
| Jun 1, 2021 | 37021684N | RESOLVE | CLASS - 2 | FAILURE TO SUBMIT ACCEPTABLE REQUIRED CYCLE 8B REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALL ... | $3,125 | $0 | Mar 10, 2022 |
| May 8, 2021 | 35559675N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN EXTERIOR FACADE&APPURTENANCES @W ELEVATION,EXP3 OBSERVED BROKEN GLASS PANEL2MEZZANINE TOP LEVEL.M... | $1,250 | $0 | Jul 29, 2021 |
| Oct 17, 2020 | 35499520R | RESOLVE | CLASS - 2 | PROVISION OF LAW:BC3307.1.PEDESTRIAN PROTECTION DOES NOT MEET CODE SPECIFICATION.NOTE:AT TIME OF INSPECTON OF A 31 ST... | $1,250 | $0 | May 13, 2021 |
| Jul 13, 2020 | 37019688H | RESOLVE | CLASS - 2 | SEC. AC 27-929.1 FAILURE TO COMPLETE THE INSTALLATION OF A FULL SYSTEMOF AUTOMATIC SPRIKLERS & FILE A FINAL SPRINKLER... | $3,125 | $0 | Mar 18, 2021 |
| Apr 10, 2020 | 35496025X | RESOLVE | CLASS - 2 | VIOLATION OF DISCRETIONARY ZONING CONDITIONS ON PRIVATELY OWNED PUBLCI SPACE NOTED ATTHE TIME OF INSPECTION OBSERVED ... | $5,000 | $0 | Sep 3, 2020 |
| Nov 15, 2019 | 37015970N | RESOLVE | CLASS - 2 | 27-929.1 A.C. 27-929.1,FAILURE TO COMPLETE THE INSTALLATION OF A FULL SYSTEM OF AUTOMATIC SPRINKLERS AND FILE A FINAL... | $1,250 | $0 | Jun 18, 2020 |
| Oct 18, 2019 | 35461721J | RESOLVE | CLASS - 2 | FAILURE TO HAVE APPROVED DRAWINGS ON SITE. NOTED:AT TIME OF INSPECTIONI OBSERVED SUSPENDED SCAFFOLD/DAVIT SYSTEM IN U... | $0 | $0 | Jan 2, 2020 |
| Oct 18, 2019 | 35461711X | RESOLVE | CLASS - 2 | WORK DOES NOT CONFORM TO APPROVED CONSTRUCTION DOCUMENTATION.NOTED:AT THE TIME OF INSPECTION,I OBSERVED SWS IN PLACE ... | $0 | $0 | Dec 26, 2019 |
| Oct 18, 2019 | 35461712H | RESOLVE | CLASS - 2 | PEDESTRIAN PROTECTION DOES NOT MEET CODE SPECIFICATIONS VERTICALS NEAREST CURB CUT NOT PROTECTED.NOTED:AT TIME OF INS... | $2,400 | $0 | Dec 26, 2019 |
| Oct 18, 2019 | 35461713J | RESOLVE | CLASS - 2 | PEDESTRIAN PROTECTIONS DOES NOT MEET CODE SPECIFICATIONS(SHED NOT TIGHT TO FACADE)NOTED:AT THE TIME OF THE INSPECTION... | $2,400 | $0 | Dec 26, 2019 |
| Oct 18, 2019 | 35461714L | RESOLVE | CLASS - 1 | BC33012-SAFETY MEAUSURES AND STANDARDS.FAILURE TO INSTITUTE AND MAINTAIN ALL SAFETY MEASURES REQUIRED BY THIS CHAPTER... | $2,500 | $0 | Dec 26, 2019 |
| Oct 18, 2019 | 35461716P | RESOLVE | CLASS - 1 | BC330113-MANUFACTOR SPECIFICATION.NOTED:AT THE TIME OF THE INSPECTION OF AN ACTIVE JOB SITE FOR WHICH A SITE SAFETY M... | $2,500 | $0 | Dec 26, 2019 |
| Oct 18, 2019 | 35461719K | RESOLVE | CLASS - 2 | FAILURE TO NOTIFY THE DEPT PRIOR TO INSTALLATION OF SUSPENDED SCAFFOLD. NOTED:AT TIME OF INSPECTION I OBSERVED WORKER... | $0 | $0 | Jan 2, 2020 |
| Oct 18, 2019 | 35461720H | RESOLVE | CLASS - 1 | BC-3314.4.2 SUPERVISION OF SUSPENDED SCAFFOLD IN USE. NOTED:AT TIME OFINSPECTION I OBSERVED SUSPENDED SCAFFOLD IN USE... | $0 | $0 | Jan 2, 2020 |
| Oct 18, 2019 | 35461717R | RESOLVE | CLASS - 2 | DOCUMENTS TO BE KEPT ON SITE.NOTED:AT TIME OF THE INSPECTION OF AN ACTIVE JOB SITE FOR WHICH A SITE SAFETY MANAGER IS... | $0 | $0 | Dec 26, 2019 |
| Oct 10, 2019 | 35461715N | RESOLVE | CLASS - 1 | BC3301123-PRE-SHIFT SAFETY MEETINGS RECORDS.NOTED:AT TIME OF INSPECTION,I OBSERVED AT AN ACTIVE FOR WHICH A SITE SAFE... | $2,500 | $0 | Dec 26, 2019 |
| Oct 15, 2018 | 37013200H | RESOLVE | CLASS - 2 | FAILURE TO SUBMIT A REQUIRED CYCLE 8B REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALL AND APPUR... | $1,250 | $0 | Mar 21, 2019 |
| Mar 1, 2018 | 35268660K | RESOLVE | CLASS - 2 | FAILURE TO HAVE NEW OR ALTERED PLUMBING SYSTEM TESTED. AT TIME OF SPOTCHECK INSPECTION FOR WASTE,SEWER,WATER & VENT R... | $0 | $0 | Apr 19, 2018 |
| Oct 20, 2017 | 35296676N | RESOLVE | CLASS - 2 | VIOLATION OF DISCRETIONARY ZONING CONDITIONS ON PRIVATELY OWNED PUBLICSPACE. NOTED: AT TIME OF INSPECTION ESCALATORS ... | $4,000 | $0 | Mar 29, 2018 |
| Jun 20, 2017 | 37002616H | RESOLVE | CLASS - 2 | FAILURE TO FILE ANNUAL CERT. THAT COOLING TOWER 1000002088 HAS BEEN INSPECTED, TESTED, & DESINFECTED, & THAT A MAINTE... | $1,000 | $0 | Dec 14, 2017 |
| Jun 20, 2017 | 37002617J | RESOLVE | CLASS - 2 | FAILURE TO FILE ANNUAL CERT. THAT COOLING TOWER 1000002093 HAS BEEN INSPECTED, TESTED, & DESINFECTED, & THAT A MAINTE... | $2,000 | $0 | Dec 14, 2017 |
| Mar 20, 2017 | 38253368K | RESOLVE | CLASS - 1 | 97X17 UPON INSPECTION THE DEVICE WAS FOUND TO BE OUT OF SERVICE.RETURN UNIT TO SERVICE OR FILE FOR A DISMANTLE. | $1,000 | $0 | May 4, 2017 |
| Mar 20, 2017 | 38253369M | RESOLVE | CLASS - 1 | 97X17-UPON INSPECTION THE DEVICE WAS FOUND TO BE OUT OF SERVICE RETURNUNIT TO SERVICE OR FILE FOR A DISMANTLE. | $1,000 | $0 | May 4, 2017 |
| Dec 22, 2008 | 38199649M | RESOLVE | CLASS - 2 | 44H0967B0198BB0571X1039P16. 44H REGROOVE TARTATION SHEAVE. 67B ADJUST PHONE VOL IN CAR. 39P PROVIDE DROP KEY HOLE FOR... | $0 | $0 | Feb 12, 2009 |
| Nov 9, 2008 | 38192147K | RESOLVE | CLASS - 2 | 91X10.9.100B01.100H11.88I11.59B01.91 ORGINAL STOP BUTTONS ON UNIT INOPERATIVE RESTORE TO WORKING ORDER OR REMOVE 100 ... | $0 | $0 | Dec 18, 2008 |
| Nov 3, 2008 | 38192696N | RESOLVE | CLASS - 2 | 91X10.100H11.100X10.91X10 REPAIR OR REMOVE LOWER STOP SW'S TOP & BOTTOM OF UNIT 100H11 TOP HANDRAIL BRUSHES WORN REPL... | $0 | $0 | Dec 18, 2008 |
| Sep 26, 2008 | 38191875Y | RESOLVE | CLASS - 2 | 02X10.01X10.100M11.100L11.100X10.02X10.ONE SIDE OF DUAL EMERGENCY SW. ALARM NOT WORKING REPAIR ALARM 01X10 ONE OF DUA... | $500 | $0 | Nov 13, 2008 |
| Jul 24, 2008 | 34699025J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: NO FIRE STOPPING - FLOORS 29-32 ELECTRICAL ROOM. REMEDY: PROVIDE/M... | $2,500 | $0 | Sep 11, 2008 |
| Feb 8, 2008 | 38181560K | RESOLVE | Non-Hazardous | 84X10.83B10. 84X FIRE SERVICE INOPERATIVE REPAIR 83B CADDY CORNER FROM CAR STATION WHEN LEANED ON WALL DEVICE WILL NO... | $350 | $0 | Jun 12, 2008 |
| Feb 8, 2008 | 38181559N | RESOLVE | Non-Hazardous | 51B14.85M05.28Q03.07B10.33M07.65B07.51B14-CT/W TO PISTON LESS THAN 6" EXISTING 85M-5YR MISSING ON GOV'S 07B-SAFETY ED... | $350 | $0 | Aug 14, 2008 |
| Mar 23, 2007 | 38165683K | RESOLVE | Non-Hazardous | CEASE USE ITEMS.77M11,80R01,82L10,79D10,70X10.77M-COMB PLATE TEETH MISSING ON BOTTOM LEFT SIDE-REPLACE.80R-EXCESSIVE ... | $500 | $0 | May 17, 2007 |
| Jul 12, 2006 | 38159548R | RESOLVE | Non-Hazardous | 86,O,15 | $0 | $0 | Aug 31, 2006 |
| Jul 12, 2006 | 38159549Z | RESOLVE | Non-Hazardous | 86,O,15 | $0 | $0 | Aug 31, 2006 |
| Apr 20, 2006 | 38157797Z | RESOLVE | Non-Hazardous | 64X10/78L01/83O02. 78L-TO PROPER TENSION. 83O-PERFORM A FULL CLEAN DOWN INSIDE ENTIRE EQUIPMENT. | $180 | $0 | Jun 8, 2006 |
| May 4, 2005 | 38150830J | RESOLVE | Non-Hazardous | 78X10/82B#/76B01/84B07/84J10 (C/U)78/X-BOTTOM COMB PALTE SWV.82/B EMG STOP SW RELOCATE AS PER CODE 84/J BOTTOM PANELS | $500 | $0 | Jun 24, 2005 |
| May 4, 2005 | 38150831L | RESOLVE | Non-Hazardous | 85B#/76B01/84B07 82/B- RELOCATE EMG STOP BUTTON AS PER CODE 76/B STEP TO SKIRT OVER 3/16" 84/B-PROVIDE ANTI SLIDE DEV... | $350 | $0 | Jun 24, 2005 |
| Dec 26, 2003 | 38144226M | RESOLVE | Non-Hazardous | 74B14,66O02,38O02,73O02,03I10,28L06. #73-O-02 CLEAN COMP & SWTICH #03-I-10 CAR ENTRANCE DAMAGED- REPAIR #28-L-06 COVE... | $350 | $0 | Feb 12, 2004 |