ECB violations
47 Pine Street, Manhattan • Block 00040 • Lot 0016
57 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Jul 9, 2026 | 39195519M | ACTIVE | CLASS - 2 | CLASS 2: CITY ID NUMBER INSIDE THE CAR WAS MISSING AS PER NYC BUILDING CODE 3001.6, WHICH REQUIRES THE CITY-ASSIGNED ... | $625 | $625 | Sep 17, 2026 |
| Jul 9, 2026 | 39195517Z | ACTIVE | CLASS - 2 | CLASS 2 RTS: ELEVATOR DEVICE IN A MULTI-ELEVATOR BUILDING WAS FOUND OUT OF SERVICE DURING INSPECTION. FAILURE TO MAIN... | $625 | $625 | Sep 17, 2026 |
| Jul 9, 2026 | 39195518K | ACTIVE | CLASS - 2 | CLASS 2 RTS: ELEVATOR DEVICE IN A MULTI-ELEVATOR BUILDING WAS FOUND OUT OF SERVICE DURING INSPECTION. FAILURE TO MAIN... | $625 | $625 | Sep 17, 2026 |
| Jul 9, 2026 | 39195516R | ACTIVE | CLASS - 1 | CLASS 1 RTS: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-9... | $1,250 | $1,250 | Sep 17, 2026 |
| Jul 2, 2026 | 39194670K | ACTIVE | CLASS - 1 | 97/X/17 CLASS 1, RESTORE TO SERVICE FOR PROPER INSPECTION BY DOB. | $1,250 | $1,250 | Sep 10, 2026 |
| May 27, 2026 | 39190068J | ACTIVE | CLASS - 1 | CLASS 1 RTS: WHEELCHAIR LIFT REMAINS OUT OF SERVICE AND HAS NOT BEEN RESTORED TO OPERATION, CONSTITUTING A CONTINUED ... | $1,280 | $1,280 | Aug 6, 2026 |
| Dec 16, 2025 | 39170534J | RESOLVE | CLASS - 2 | CLASS 2 ITEM: DEVICE IS UNDER MODERNIZATION . PROVIDE A UPDATED WORK PERMIT. | $625 | $625 | Aug 14, 2026 |
| Aug 14, 2025 | 39157191K | RESOLVE | CLASS - 2 | CLASS 2: RESTORE TO SERVICE | $312 | $312 | May 14, 2026 |
| Aug 11, 2025 | 39156692Y | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED EXPOSED ELECTRICAL WITHOUT COVER., REPAIR AND/REPLACE | $2,500 | $2,500 | Jan 28, 2027 |
| Aug 11, 2025 | 39156691M | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $2,500 | $2,500 | May 28, 2026 |
| Jun 30, 2025 | 39152293Z | ACTIVE | CLASS - 1 | CLASS 1. RETURN TO SERVICE. : FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PE... | $625 | $0 | Sep 4, 2025 |
| Jun 30, 2025 | 39152292R | ACTIVE | CLASS - 1 | CLASS 1. RETURN TO SERVICE. : FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PE... | $625 | $0 | Sep 4, 2025 |
| Jul 31, 2024 | 39120466L | RESOLVE | CLASS - 2 | I OBSERVED ON THE ROOF, THE 5TH ROOF, AND IN THE SUBCELLAR BOILER ROOM, THE FAILURE TO PROVIDE/ INSTALL GFCI PROTECTI... | $1,200 | $0 | Oct 10, 2024 |
| Jul 31, 2024 | 39120414J | RESOLVE | CLASS - 2 | OBSERVED EXCESSIVE STORAGE IN THE GAS METER ROOM LOCATED IN THE SUB CELLAR. AS PER E3 OF THE FGC GAS METER ROOMS, WHE... | $0 | $0 | Oct 10, 2024 |
| Jul 31, 2024 | 39120450R | RESOLVE | CLASS - 2 | WALLS ERECTED/INSTALLED OBSTRUCTING/BLOCKING PATHWAYS AND EMERGENCY EXITS LOCATED #1 FLOOR PREP AND SERVICE AREA INCL... | $0 | $0 | Oct 10, 2024 |
| Jul 31, 2024 | 39120451Z | RESOLVE | CLASS - 2 | EMERGENCY LIGHTING IS MISSING THROUGHOUT BUILDING., REPAIR AND/OR REPLACE LIGHTING | $0 | $0 | Oct 10, 2024 |
| Jul 31, 2024 | 39120415L | RESOLVE | CLASS - 2 | OBSERVED IN THE SUB CELLAR ACTIVE WATER LEAK ON VALVE ON STEAK PIPING, ALSO STORAGE TANK THAT IS HOUSED IN THE SUB CE... | $625 | $0 | Oct 10, 2024 |
| Jul 31, 2024 | 39120465J | RESOLVE | CLASS - 1 | I OBSERVED THE INSTALLATION OF TRANSFORMERS, RACEWAYS AND WIRING FOR THE INSTALLATION OF NEW ELEVATORS. NO PERMIT ON ... | $1,600 | $0 | Mar 28, 2025 |
| Jul 31, 2024 | 39120413H | RESOLVE | CLASS - 2 | OBSERVED ON THE 2ND FLOOR OFFICE AND THE 3RD FLOOR HALLWAY CONCEALED SPRINKLER HEAD IS BEING OBSTRUCTED BY CEILING. A... | $0 | $0 | Oct 10, 2024 |
| Jul 31, 2024 | 39120448H | RESOLVE | CLASS - 2 | IMPROPER STORAGE UNDERNEATH METAL STAIRCASE LOCATED AT CELLAR LEVEL., REPAIR AND/OR REPLACE | $0 | $0 | Oct 10, 2024 |
| Jul 31, 2024 | 39120461M | RESOLVE | CLASS - 1 | I OBSERVED ON THE ROOF THE GENERATOR IN THE BEGINNING STAGES OF CORROSION AS PER EC 110.11 ALL ELECTRICAL EQUIPMENT S... | $1,600 | $0 | Mar 13, 2025 |
| Jul 31, 2024 | 39120462Y | RESOLVE | CLASS - 2 | I OBSERVED ON THE ROOF MULTIPLE DISCONNECT SWITCHES WITH NO EQUIPMENT GROUND CONDUCTOR INSTALLED AS REQUIRED WHEN THE... | $800 | $0 | Mar 13, 2025 |
| Jul 31, 2024 | 39120463X | RESOLVE | CLASS - 2 | I OBSERVED IN THE BOILER ROOM AND THE GARBAGE AREA OUTSIDE OF THE MAIN ELECTRICAL ROOM THE SHUT OFF SWITCH FOR THE EL... | $800 | $0 | Mar 13, 2025 |
| Jul 31, 2024 | 39120464H | RESOLVE | CLASS - 1 | I OBSERVED ON ALL FLOORS THE FAILURE TO INSTALL TAMPER RESISTANT/PROOF OUTLETS IN THE HALLS AS REQUIRED IN LL 39/2015... | $1,250 | $0 | Mar 13, 2025 |
| Jul 31, 2024 | 39120447X | RESOLVE | CLASS - 2 | ELECTRICAL & GAS METER MENCHANICAL ROOM DOOR DOES NOT SELF-CLOSE LOCATED AT CELLAR LEVEL AND THROUGHOUT BUILDING., RE... | $0 | $0 | Oct 10, 2024 |
| Jul 31, 2024 | 39120449J | RESOLVE | CLASS - 2 | OPEN HOLES, HOLE PENETRATION, AND REMOVED FIRE-STOPPING FOUND THROUGHOUT BUILDING AND MECHANICAL ROOMS., PROVIDE/MAIN... | $625 | $0 | Oct 10, 2024 |
| Jul 30, 2024 | 39120223R | RESOLVE | CLASS - 1 | DOOR ZONE RESTRICTOR INOPERATIVE. THIS IS A SAFETY FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY: TO RESTORE SERVICE... | $1,250 | $0 | Nov 14, 2024 |
| Jan 26, 2024 | 39104499H | RESOLVE | CLASS - 1 | CLASS 1 C/U DOOR ZONE RESTRICTOR BYPASSED. PROVIDE TO REPAIR OR REPLACE. PROVIDE A UPDATED MAINTENACE LOG. | $1,250 | $0 | Apr 4, 2024 |
| Jan 26, 2024 | 39104497Y | RESOLVE | CLASS - 1 | CLASS 1 C/U DOOR ZONE RESTRICTOR BYPASSED. PROVIDE TO REPAIR. | $1,250 | $0 | Apr 4, 2024 |
| Jan 26, 2024 | 39104498X | RESOLVE | CLASS - 1 | RETURN TO SERVICE | $1,250 | $0 | Apr 4, 2024 |
| Jan 26, 2024 | 39104496M | RESOLVE | CLASS - 2 | DEVICE IS OUT OF SERVICE. PROVIDE TO RETURN TO SERVICE. | $625 | $0 | Apr 4, 2024 |
| May 8, 2023 | 39085716Y | RESOLVE | CLASS - 1 | CLASS 1: UPON INSPECTION FOUND DEVICE TO BE OUT OF SERVICE. RESTORE TO SERVICE REPAIR IMMAEDIATELY AS PER 1RCNY 11-02. | $0 | $0 | Jul 13, 2023 |
| May 8, 2023 | 39085717X | RESOLVE | CLASS - 1 | CLASS 1: UPON INSPECTION FOUND DEVICE TO BE OUT OF SERVICE. RESTORE TO SERVICE REPAIR IMMAEDIATELY AS PER 1RCNY 11-02. | $0 | $0 | Jul 13, 2023 |
| Mar 2, 2023 | 35670849J | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE ADEQUATE SAFETY MEASURES SUCH AS SHED,NETTING ETC.WHERE REQUIRED TO PROTECT PUBLIC AND PROPERTY FR... | $10,000 | $0 | Jun 22, 2023 |
| Oct 19, 2022 | 37022927N | RESOLVE | CLASS - 2 | FAILURE TO SUBMIT ACCEPTABLE REQ CYCLE8B REPORT OF CRITICAL EXAM DOC CONDITION OF EXTERIOR WALL&APPURTENANCES REQ BY ... | $3,125 | $0 | Mar 16, 2023 |
| Aug 10, 2022 | 39067759P | RESOLVE | CLASS - 1 | 97,X,10 RESTORE TO SERVICE CLASS 1. REPLACE RESISTERS AND CALL DOB FOR PROPER INSPECTION. | $625 | $0 | Nov 17, 2022 |
| May 23, 2022 | 39062643K | RESOLVE | CLASS - 1 | 5/X/10 CAR CEASE USE CLASS 1 CAR DOOR RESTRICTOR IS NOT WORKING PLUNGER STUCK IN UP DIRECTION REPAIR | $1,250 | $0 | Feb 23, 2023 |
| May 11, 2022 | 39061902L | RESOLVE | CLASS - 1 | 97/X/17 CLASS 1 RESTORE TO SERVICE FOR PROPER INSPECTION BY DOB. | $625 | $0 | Dec 8, 2022 |
| Jun 1, 2021 | 37021682J | RESOLVE | CLASS - 2 | FAILURE TO SUBMIT ACCEPTABLE REQUIRED CYCLE 8B REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALL ... | $1,250 | $0 | Jun 9, 2022 |
| Dec 15, 2020 | 35524977Z | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35475597Z ISSUED ON 10/08/20 & TO FILE A CERT OF CORREC... | $1,250 | $0 | Jun 3, 2021 |
| Oct 8, 2020 | 35475597Z | RESOLVE | CLASS - 1 | FAIURE TO MAINTAIN AT ROOF LEVEL ACCUMULATED OF UNSECURRED CONSTRUCTION DEBRIS FROM WATER TOWER SITTING ON ROOF.REM:R... | $3,125 | -$3,125 | Dec 24, 2020 |
| Jul 1, 2014 | 36019420K | RESOLVE | CLASS - 2 | FAILURE TO FILE AN ACCEPTABLE CYCLE 7 TECHNICAL REPORT IN COMPLIANCE WITH CODE PROVISIONS: PERIODIC INSPECTION OF EXT... | $400 | $0 | Jan 22, 2015 |
| Aug 12, 2013 | 38221243K | RESOLVE | CLASS - 2 | 41B10-PROPERLY SECURE SECONDARY MACHINE ROOM DOOR. | $0 | $0 | Sep 26, 2013 |
| Jun 11, 2013 | 34749603P | RESOLVE | CLASS - 1 | DESIGNATED SITE SAFETY MANAGER. NOTE: AT THE TIME OF MY INSPECTION ON CONSTRUCTION SITE,LOG BOOK INDICATES THAT THE D... | $1,600 | $0 | Aug 1, 2013 |
| Jun 11, 2013 | 34749602N | RESOLVE | CLASS - 1 | FAILURE TO COMPLY RULES PROMULGATED BY THE COMMISSIONER - SITE SAFETY RULES. NOTE: AT THE TIME OF MY INSPECTION ON CO... | $2,500 | $0 | Aug 1, 2013 |
| Oct 15, 2012 | 34986892J | RESOLVE | CLASS - 2 | PARTIAL SWO (NORTH AND WEST ELEVATION) ISSUED PURSUANT TO 28-207.2 ANDPOSTED AT PREMISES. NO ROOF PROTECTION INSTALLE... | $250 | $0 | Nov 29, 2012 |
| Oct 13, 2009 | 38206486J | RESOLVE | CLASS - 2 | 70O02,39O02,39Q03,17H11,39M07,68M07. 17H11-WHERE AS NEEDED. 39M07-ANTISPIN DEVICE. | $250 | $0 | Dec 3, 2009 |
| Dec 20, 2004 | 38150318K | RESOLVE | Non-Hazardous | 02L10/10H11/17H11/83E10 02-EMERGENCY PHONE IN CAR INOPERATIVE 10-CAR DOOR GIBS WORN, REPLACE 17-HOISTWAY DOOR GIBS WO... | $0 | $0 | Feb 3, 2005 |
| Nov 13, 2003 | 38142756K | RESOLVE | Non-Hazardous | 41R09. 41-R-09- REMOVE GREEN JUMPER FROM CONTROLLED. | $0 | $0 | Jan 8, 2004 |
| Dec 4, 1998 | 38082576L | RESOLVE | Non-Hazardous | 73B,PROVIDE MEANS TO PROPERLY DISMANTLE SIDE WALK ELEVATOR AND SECURE TO STREET OPENING. | $0 | $0 | Mar 4, 1999 |