ECB violations
41-45 Pine Street, Manhattan • Block 00043 • Lot 0001
41 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Sep 16, 2024 | 39532433X | RESOLVE | CLASS - 2 | AT THE TIME OF INSPECTION OF A 24 STORIES ALTERATION JOBSITE, I OBSERVED NO RED LIGHT WAS PROVIDED FOR FDNY STANDPIPE... | $2,500 | $0 | Jan 2, 2025 |
| Jan 16, 2024 | 37026682M | RESOLVE | CLASS - 2 | FAILURE TO FILE ACCEPTABLE AMENDED CYCLE 9C REPORT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRIBED IN INITIAL FA... | $625 | $0 | May 2, 2024 |
| Sep 26, 2023 | 39522083X | RESOLVE | CLASS - 1 | AT A 16 STORY BUILDING SIDEWALK SHED COMPANY WAS ERECTING A SIDEWALK SHED WHERE TWO WORKERS GOT INJURED FROM IMPROPER... | $0 | $0 | Jan 4, 2024 |
| Aug 4, 2023 | 39520201Z | RESOLVE | CLASS - 1 | AT A INCIDENT OF A 16 STORY BUILDING WHERE SIDEWALK SHED CREW FAILURE TO PROPERLY HANDLE MATERIAL AND EQUIPMENT APPRO... | $0 | $0 | Jun 25, 2026 |
| Jul 28, 2023 | 39519925X | RESOLVE | CLASS - 2 | AT THE TIME OF INSPECTION I OBSERVED SIDEWALK SHED INSTALLED, AT EXPOSURE #1 AND 4 WITH APPROXIMATELY 2 VERTICAL MEMB... | $0 | $0 | Oct 5, 2023 |
| Jul 28, 2023 | 39519924Y | RESOLVE | CLASS - 2 | AT THE TIME OF INSPECTION WHILE RESPONDING TO A COMPLIANT, I OBSERVED THE SIDEWALK SHED INSTALLED FOR PEDESTRIAN PROT... | $2,400 | $0 | Oct 5, 2023 |
| Jun 12, 2023 | 39517717M | RESOLVE | CLASS - 2 | PERMITHOLDER FAILED TO CODES ?3307.6.3 NOT MAINTAIN 18 INCHES OF CURB LINE CLEARANCE TO AVOID EXISTING OBSTRUCTIONS. ... | $2,400 | $0 | Jul 11, 2024 |
| Feb 27, 2023 | 39513621J | RESOLVE | CLASS - 2 | AT TIME OF INSPECTION OBSERVED SIDEWALK SHED IN PLACE WITH ACTIVE PERMIT AT EXPOSURE #3 & #4. UPON REVIEWING SIDEWALK... | $2,400 | $0 | Jul 6, 2023 |
| Dec 22, 2022 | 39076187N | RESOLVE | CLASS - 2 | FAILURE TO SAFEGUARD ALL PERSONS AND PROPERTY AFFECTED BY CONSTRUCTION OPERATIONS. OBSERVED SIDEWALK SHED ERECTED UND... | $5,030 | $0 | Jan 17, 2024 |
| Nov 15, 2019 | 37015999R | RESOLVE | CLASS - 2 | AC 27-929.1, FAILURE TO COMPLETE THE INSTALLATION OF A FULL SYSTEM OF AUTOMATIC SPRINKLERS & FILE SPRINKLER REPORT PR... | $625 | $0 | Jun 11, 2020 |
| Sep 6, 2018 | 35308414Z | RESOLVE | CLASS - 2 | FAILURE TO CONDUCT/FILE FINAL INSPECTION FOR COMPLETED WORK WITHIN ONE YEAR OF PERMIT EXPIRATION. ALT II JOB #1205230... | $0 | $0 | Feb 21, 2019 |
| Apr 17, 2018 | 35323686H | RESOLVE | CLASS - 1 | FAILURE TO DESIGNATE OR HAVE SSM OR (2)SSP ON/PRESENCE AT THE SITE. NOTE: AT TIME OF INSPECTION WOR IN PROGRESS. ON T... | $0 | $0 | Aug 16, 2018 |
| Mar 7, 2018 | 37009282Z | RESOLVE | CLASS - 2 | FAILURE TO SUBMIT ACCEPTABLE 7TH ROUND REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALLS AND APP... | $3,125 | $0 | Jul 26, 2018 |
| Jan 4, 2017 | 35200331Z | RESOLVE | CLASS - 2 | WORK DOES NOT CONFORM TO APPROVED CONSTRUCTION DOCUMENTS &/OR AMENDED PLANS. NOTE: AT TIME OF INSPECTION I OBSERVED O... | $500 | $0 | May 11, 2017 |
| Jul 11, 2016 | 38242741X | RESOLVE | CLASS - 2 | 34B9. REMOVE EXISTING LADDER & DEFLECTIVE SHEAVE BEAMS (TOP OF HOISTWAY). | $500 | $0 | Dec 1, 2016 |
| Nov 2, 2015 | 36023523P | RESOLVE | CLASS - 2 | FAILURE TO FILE AN ACCEPTABLE TECHNICAL REPORT IN COMPLIANCE W/CODE.PROVISION:36026669L.PERIODIC INSP OF EXTERIOR WAL... | $2,000 | $0 | Sep 22, 2016 |
| Dec 12, 2014 | 36026669L | RESOLVE | CLASS - 2 | FAILURE TO FILE AN ACCEPTABLE CYCLE 7 TECHNICAL REPORT IN COMPLIANCE WITH CODE PROVISIONS: PERIODIC INSPECTION OF EXT... | $800 | $0 | May 14, 2015 |
| Nov 10, 2014 | 35039542K | RESOLVE | CLASS - 1 | ELECTRICIAL WORK W/OUT A PERMIT.THE ENTIRE 9 FLR:SUB FEEDERS SUB PANELS,BRANCH CIRCUIT WIRING RECEPTACLES OUTLETS,SWI... | $1,600 | $0 | Mar 12, 2015 |
| Sep 18, 2014 | 35110092L | RESOLVE | CLASS - 1 | "FAILURE TO HAVE SSM OR COORDINATOR PRESENT"@ TIME OF INSP NO SSM OR DOCUMENTAION(CCD-1)PRESENT.FIVE WORKER ON PIPE S... | $0 | $0 | Nov 6, 2014 |
| Aug 6, 2014 | 35099581H | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE APPROVED PLANS AT JOB SITE AT TIME OF INSPECTION. NOTED: AT TIME OF INSPECTION APPROVED PLANS FOR ... | $0 | $0 | Sep 25, 2014 |
| Aug 6, 2014 | 35099580X | RESOLVE | CLASS - 2 | SEC. 3310.3 FAILURE TO HAVE SITE SAFETY PLAN AS REQUIRED. NOTED: AT TIME OF INSPECTION SITE SAFETY PLAN COULD NOT BE ... | $0 | $0 | Sep 25, 2014 |
| Aug 6, 2014 | 35099579Z | RESOLVE | CLASS - 2 | WORK DOES NOT CONTRARY TO APPROVED CONSTRUCTION DOCUMENTS. NOTED: WORKDOES NOT WALL MOUNTED ANCHORE PLATES USE FOR LI... | $250 | $0 | Sep 25, 2014 |
| Aug 6, 2014 | 35099578R | RESOLVE | CLASS - 2 | PWSO (OUTRIGGER BEAMS) ISSUED PURSUANT TO 28-207.2 POSTED. FAILED TO NOTIFY DEPT/OBTAIN PERMIT PRIOR TO USE/INST OFF ... | $400 | $0 | Sep 25, 2014 |
| May 8, 2012 | 38219847Z | RESOLVE | CLASS - 2 | 97X10- REPAIR/RETURN TO SERVICE SO A COMPLETE INSPECTION CAN BE PERFORMED. | $0 | $0 | Jun 28, 2012 |
| Jan 27, 2010 | 36011576K | RESOLVE | CLASS - 2 | FAILURE TO FILE AN ARCHITECT / ENGINEER REPORT CERTIFYING EXIT / DIRECTIONAL SIGNS ARE CONNECTED TO EMERGENCY POWER S... | $4,000 | $0 | Jul 22, 2010 |
| Mar 4, 2009 | 38200013M | RESOLVE | CLASS - 3 | 52B11.#E10.UNDERSIZED HOIST ROPES # E TACK ON TRACTION SHEAVE MAKING NOISE REPAIR | $200 | $0 | Apr 23, 2009 |
| Mar 4, 2009 | 38200014Y | RESOLVE | CLASS - 3 | 52B11 UNDERSIDE HOIST ROPES (REPLACE) | $200 | $0 | Apr 23, 2009 |
| Mar 4, 2009 | 38200012K | RESOLVE | CLASS - 3 | 42M07.52B11.40R13.#E10 42M PROVIDE AN EMERGENCY TERMINAL STOPPING DEVICE AS PER ANSI A17IA 1988 RULE 209.2B 52B REPLA... | $100 | $0 | Apr 23, 2009 |
| Feb 11, 2009 | 38201326H | RESOLVE | CLASS - 2 | 97X17 97X17 C.U.CALL DOB BEFORE BACK TO SERVICE FOR A COMPLETE INSPECTION CAN BE MADE AN ACCIDENT OCCURED ON 11-13-09... | $0 | $0 | Jun 18, 2009 |
| Feb 10, 2009 | 38201325X | RESOLVE | CLASS - 3 | 97R#-FAILURE TO REPORT AN ACCIDENT THAT OCCURRED ON NOVEMBER 13TH, 208, THAT RESULTED AN INJURY. 3010.1 OF THE BUILDI... | $0 | $0 | Jun 18, 2009 |
| Aug 19, 2008 | 38190070M | RESOLVE | CLASS - 2 | 1X10.60X10.59B01.71X REPAIR LIGHT IN PIT 60X REPAIR LIGHT IN SECONDARY59B ADJUST BRAKE PIN OPEN ENDS OF BRAKE PIN | $500 | $0 | Jan 21, 2010 |
| Jun 10, 2008 | 38183490N | RESOLVE | Non-Hazardous | 58B0766B1066O02. 58/B PROVIDE PROPER BRAKE SWITCH PIN W/ COTTER PINS. 66/B PIT LIGHTING. | $180 | $0 | Jul 31, 2008 |
| Jun 10, 2008 | 38183491P | RESOLVE | Non-Hazardous | 83X10. 83X RETURN TO SERVICE SO A PROPER INSPECTION CAN BE PERFORMED. | $180 | $0 | Jul 31, 2008 |
| Aug 30, 2005 | 34491199R | RESOLVE | Non-Hazardous | NOTED:FAILURE TO POST PERMIT HOLDER SIGN AS REQUIRED BY ADMIN CODE REMEDY:POST SIGN AS REQUIRED | $0 | $0 | Nov 10, 2005 |
| Jun 26, 1997 | 34142984R | RESOLVE | Non-Hazardous | FAILURE TO OBTAIN A CERTIFICATE OF ELECTRICAL INSPECTION FROM THE BAREAU OF ELECTRICAL CONTROL FOR THE INSTALLATION O... | $600 | $0 | Aug 14, 1997 |
| Aug 17, 1995 | 34122940R | RESOLVE | Unknown | FAILURE TO PROVIDE ADVOCATE EMERGENCY POWER EXIT LIGHT IN EXIT STARCA-SES(A+B)REPLACE BULBS AND/OR BATTERIES,IE,FLRS ... | $0 | $0 | Oct 5, 1995 |
| Oct 15, 1992 | 38028158L | RESOLVE | Non-Hazardous | 77X, | $0 | $0 | Dec 3, 1992 |
| Oct 15, 1992 | 38028159N | RESOLVE | Non-Hazardous | 46K, | $0 | $0 | Dec 3, 1992 |
| Oct 15, 1992 | 38028160K | RESOLVE | Non-Hazardous | 74$, 74. PROVIDE PROPER CLEARANCE BETWEEN THE CWT AND THE BUFFER. | $0 | $0 | Dec 3, 1992 |
| Aug 27, 1991 | 38015658P | RESOLVE | Non-Hazardous | 07X,07 REPAIR DOOR EDGE TO REOPEN DOOR | $0 | $0 | Oct 10, 1991 |
| Aug 26, 1991 | 38015657N | RESOLVE | Non-Hazardous | 46H | $0 | $0 | Oct 10, 1991 |