ECB violations
Bmcc Fiterman Hall, Manhattan • Block 00127 • Lot 0001
59 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Apr 11, 2024 | 37027257X | ACTIVE | CLASS - 2 | FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 9B REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WA... | $1,250 | $0 | Jun 13, 2024 |
| Apr 26, 2018 | 38262541J | ACTIVE | CLASS - 2 | 50M7 BRAKE MAINTENANCE TAG MISSING. | $0 | $0 | Jul 5, 2018 |
| Apr 26, 2018 | 38262540H | ACTIVE | CLASS - 2 | 59M, 5E1. 59M7- BRAKE MAINTENANCE TAG MISSING; 5B1- CAR DOOR RUBBING ADJUST. | $0 | $0 | Jul 5, 2018 |
| Sep 13, 2011 | 34922137N | RESOLVE | CLASS - 2 | FAILURE TO SAFEGUARD ALL PERSONS & PROPERTY AFFECTED BY CONST.OPERATIONS.@ TIME OFINSPEC.OBSERVED WELDING OPERATIONS ... | $1,200 | $0 | Nov 3, 2011 |
| Jul 12, 2011 | 34918286P | RESOLVE | CLASS - 1 | RESPONSIBILITY FOR SAFETY PARTIAL STOP WORK ORDER ISSUED PURSUANT TO 27-208.2 AND POSTED AT PREMISES AN INCIDENT OCCU... | $0 | $0 | Nov 3, 2011 |
| Jul 12, 2011 | 34918287R | RESOLVE | CLASS - 1 | AN INCIDENT OCCURRED AT ABOVE JOBSITE A BOOM TRUCK MATERIAL FOR IT POSITION PUSHED A SECTION OF 2X3 STUDS OFF THE TRU... | $2,400 | $0 | Nov 3, 2011 |
| Jun 6, 2011 | 34803473K | ACTIVE | CLASS - 1 | FAILURE TO SAFEGUARD ALL PERSONS AND PROPERTY AFFECTED BY CONSTRUCTIONOPERATIONS. AT TIME OF INSPECTION LADDER LEADIN... | $2,400 | $0 | Jan 12, 2012 |
| Mar 22, 2011 | 34900510P | RESOLVE | CLASS - 2 | USE OF SUPPORTED SCAFFOLD W/O A SCAFFOLD USER CERTIFICATE.AS NOTED:@ TIME OF INSPECTION @ ABOVE ACTIVE CONSTRUCTION S... | $800 | $0 | May 12, 2011 |
| Nov 22, 2010 | 34875320M | RESOLVE | CLASS - 1 | USE OF SUPPORTED SCAFFOLD W/O A SCAFFOLD. USER CERTIFICATE. NOTED: AT TIME OF INSPECTION OBSERVED WELDER ON 8TH FLR W... | $1,600 | $0 | May 12, 2011 |
| Nov 22, 2010 | 34875321Y | RESOLVE | CLASS - 2 | SEC. 3301.7. DESIGN DRAWING REQUIRED BY THE PROVISION OF CHAPTER 33 OFNYC BLDG CODE. NOTED: NO DESIGN DWGS FOR PROTEC... | $0 | $0 | Jan 13, 2011 |
| Aug 10, 2010 | 34860215Z | RESOLVE | CLASS - 2 | FAILURE TO SAFEGUARD ALL PERSONS & PROPERTY AFFECTED BY CONSTRUCTION OPERATIONS. @ THE TIME OF MY INSPECTION BLDG STE... | $1,200 | $0 | Sep 30, 2010 |
| Aug 10, 2010 | 34860216K | RESOLVE | CLASS - 1 | 3301.1.2 NO FIRE WATCH PERSONS. @ THE TIME OF MY INSPECTION I OBSERVED WELDING IN PROGRESS W/ NO FIRE WATCH PERSON IN... | $1,600 | $0 | Sep 30, 2010 |
| Aug 10, 2010 | 34860218Y | RESOLVE | CLASS - 1 | SEC. 28-407.1 NO WELDERS LICENSE. AT THE TIME OF MY INSPECTION,APPROX 30 WORKER ON SITE BLDG STEEL STRUCTURE UPTO MAI... | $1,600 | $0 | Sep 30, 2010 |
| Aug 10, 2010 | 34860217M | RESOLVE | CLASS - 2 | SEC. 3303.7.2 NO FIRE EXITING USHER. AT THE TIME OF MY INSPECTION APPROX 30 WORKER ON SITE BLDG STRUCTURE UPTO MAIN F... | $0 | $0 | Sep 30, 2010 |
| Jun 7, 2010 | 34844769K | RESOLVE | CLASS - 2 | SEC. 3310.3. FAILURE TO COMPLY W/SSP. SITE SAFETY PLAN DOES NOT INDICATE 3 TRAILERS AND 1 CONTAINER ON SITE. REMEDY: ... | $400 | $0 | Jul 29, 2010 |
| Oct 20, 2009 | 34809383Y | RESOLVE | CLASS - 2 | WORK W/O PERMIT: EXPIRED PERMIT. AS NOTED: AT TIME OF INSPECTION AT ABOVE ACTIVE DEMO SITE BLDG DOWN TO 5TH FLR & DEM... | $400 | $0 | Dec 17, 2009 |
| Oct 20, 2009 | 34809384X | RESOLVE | CLASS - 2 | WORK W/O PERMIT: EXPIRED PERMIT. AS NOTED: AT TIME OF INSPECTION AT ABOVE ACTIVE DEMO SITE BLDG DOWN TO 5TH FLR & DEM... | $400 | $0 | Apr 15, 2010 |
| Sep 16, 2009 | 34805794K | RESOLVE | CLASS - 2 | FAIL TO PROVIDE APPROVED/ACCEPTED PLANS AT JOBSITE AT TIME OF INSPECTION. AS NOTED: THERE IS NO APPROVED SIDEWALK SHE... | $0 | $0 | Nov 5, 2009 |
| Sep 16, 2009 | 34805795M | RESOLVE | CLASS - 2 | SEC 3301.11 MISC VIOL: FAIL TO MAINTAIN EXITS DURING CONST OR DEMO AS REQUIRED. AS NOTED: DEMO WORK IN PROGRESS (BLDG... | $0 | $0 | Nov 5, 2009 |
| Sep 9, 2009 | 34805779M | RESOLVE | CLASS - 2 | SEC. BC 3314.4.3 FAILURE TO MAINTAIN INSPECTION LOG FOR SUPPORTED SCAFFOLD AS REQUIRED. AS NOTED: AT TIME OF INSPECTI... | $0 | $0 | Feb 18, 2010 |
| Aug 19, 2009 | 34800017N | RESOLVE | CLASS - 2 | SEC. BC 3301.2 OPENING & HOLES NOT COVERED. AS NOTED: AT TIME INSPECTION AT ABOVE ACTIVE DEMO SITE BUILDING DOWN TO 1... | $0 | $0 | Oct 8, 2009 |
| Aug 19, 2009 | 34800016L | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH NYC FIRE CODE. AS NOTED: AT TIME OF INSPECTION AT ABOVE ACTIVE DEMO SITE BUILDING DOWN TO 14TH... | $0 | $0 | Oct 8, 2009 |
| Aug 6, 2009 | 34800000R | RESOLVE | CLASS - 1 | FAILURE TO CARRY OUT DEMOLITION OPERATIONS AS REQUIRED BY SECTION. NOTE: AT TIME OF INSPECTION AT ABOVE ACTIVE DEMO S... | $400 | $0 | Jan 11, 2011 |
| Aug 3, 2009 | 34790170N | RESOLVE | CLASS - 2 | FAILURE TO SAFEGUARD ALL PERSONS & PROPERTY AFFECTED BY CONSTRUCTION OPERATIONS. AS NOTED: AT TIME OF INSPECTION ON A... | $1,200 | $0 | Apr 12, 2010 |
| Aug 3, 2009 | 34788611R | RESOLVE | CLASS - 1 | SEC 3303.8 MISC VIOL: STANDPIPE SYSTEMS DURING CONST, ALTERATION OR DEMO. NOTED: STANDPIPE IS NOT IN READINESS, HYPOS... | $1,600 | $0 | Apr 12, 2010 |
| Aug 3, 2009 | 34790169X | RESOLVE | CLASS - 1 | FAILURE TO SAFEGUARD ALL PERSONS & PROPERTY AFFECTED BY CONSTRUCTION OPERATIONS. AS NOTED: AT TIME OF INSPECTION ON A... | $2,400 | $0 | Apr 12, 2010 |
| Jul 29, 2009 | 34799606X | RESOLVE | CLASS - 2 | SEC. 3314.4.6. UNQUALIFIED PERSON USING A SUPPORTED SCAFFOLD. AS NOTED: AT TIME OF INSPECTION AT ABOVE ACTIVE DEMO SI... | $400 | $0 | Apr 12, 2010 |
| Jul 8, 2009 | 34790315P | RESOLVE | CLASS - 2 | SEC. BC 3313.1 STORAGE & USE OF ALL VOLATILE FLAMMABLE & COMBUSTIBLE MIXTURES COMPRESSED GASES. NOTE: AT TIME OF INSP... | $800 | $0 | Apr 12, 2010 |
| Jun 17, 2009 | 34783593J | RESOLVE | CLASS - 2 | SEC. BC3314.8 & 27-1009(A) FAILURE TO PROVIDE REQUIRED GUARD RAILS & TOE BOARDS FOR SCAFFOLD PLATFORM. AS NOTED: AT T... | $400 | $0 | Dec 17, 2009 |
| Jun 17, 2009 | 34783592H | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN ADEQUATE HOUSEKEEPING PER SECTION REQUIREMENT. AS NOTED: AT TIME OF INSPECTION AT ABOVE DEMO SITE... | $2,400 | $0 | Dec 22, 2009 |
| Jun 17, 2009 | 34783590Y | RESOLVE | CLASS - 2 | SEC. BC 3303.12 & 27-1014 FAILURE TO PROVIDE REQUIRED TEMPORARY OR PERMANENT ELEVATOR IN READINESS IN BUILDING UNDER ... | $400 | $0 | Dec 22, 2009 |
| Jun 17, 2009 | 34783591X | RESOLVE | CLASS - 2 | SEC. BC3301.2 & 27-1009(A) OPENING/HOLES NOT COVERED AS NOTED: AT TIME OF INSPECTION AT ABOVE DEMO SITE I OBSERVED HO... | $400 | $0 | Dec 22, 2009 |
| Apr 17, 2009 | 34764944Z | RESOLVE | CLASS - 2 | SEC BC3314.4.2 FAILURE TO MAINTAIN NETTING ON SUPPORTED SCAFFOLD. NOTED: SUPPORTED SCAFFOLD AT ALL EXPOSURES UNDER PE... | $0 | $0 | Jun 11, 2009 |
| Apr 17, 2009 | 34764943R | RESOLVE | CLASS - 2 | WORK DOES NOT CONFORM TO APPROVED CONSTRUCTION DOCUMENTS OR AMENDMENTS. NOTED: SIDEWALK SHED ALL EXPOSURES UNDER PERM... | $250 | $0 | Jun 11, 2009 |
| Nov 21, 2008 | 36000970P | RESOLVE | CLASS - 2 | FAILURE TO SUBMIT AN ACCEPTABLE 6TH ROUND TECHNICAL REPORT IN COMPLIANCE WITH CODE PROVISIONS: PERIODIC INSPECTION OF... | $0 | $0 | Dec 18, 2008 |
| Sep 25, 2008 | 36000201K | RESOLVE | CLASS - 1 | FAILURE TO FILE AFFIDAVITS AND OR COMPLY W/ OTHER REQUIREMENTS SET FORTH FOR PHOTOLUMINESCENT EXIT PATH MARKING. REME... | $0 | $0 | Dec 18, 2008 |
| Aug 22, 2007 | 34579576J | RESOLVE | Hazardous | FAILURE TO PROPERLY STORE COMBUSTIBLE MATERIAL OR OTHER MATERIAL AND EQUIPMENT WHILE SCAFFOLDING BEING ERECTED UNDER ... | $900 | $0 | Oct 11, 2007 |
| Dec 12, 2003 | 34462579X | RESOLVE | Non-Hazardous | FAILURE TO SUBMIT A FIFTH ROUND TEHCNICAL REPORT PERIODIC INSPECTION OR EXTERIOR WALLS AND APPURTENANCES AS REQUIRED ... | $2,500 | $0 | Jul 15, 2004 |
| Jun 22, 2000 | 38098990N | RESOLVE | Non-Hazardous | 73##. 73- FILE FOR REMOVAL. | $2,500 | $0 | Aug 10, 2000 |
| Jun 22, 2000 | 38098991P | RESOLVE | Non-Hazardous | 73##. 73# RETURN TO SERVICE. | $2,500 | $0 | Aug 10, 2000 |
| Apr 29, 1997 | 38059448L | RESOLVE | Non-Hazardous | 37 R 50 L 39 L 37-REMOVE OBJECT STUCK IN VSR RELAY 50-REMOVE NOISE FROM SECONDARY SHEIVE. 39- REMOVE NOIS FROM GOVERN... | $0 | $0 | Jun 19, 1997 |
| Apr 29, 1997 | 38059449N | RESOLVE | Non-Hazardous | 46 L 37 R 39 I 28 L 46 CHANGE HOIST ROPES #28 REPLACE GUIDE ROLLERS 37-REMOVE OBJECT STUCK IN RELAYS USR & GP. 39-REM... | $0 | $0 | Jun 19, 1997 |
| Apr 29, 1997 | 38059441Z | RESOLVE | Non-Hazardous | 37 D 37 R 37-PROPERLY MOUNT RESISTORS & CAPACITORS TO CONTROLLER 37-REMOVE OBJECT STACK IN GP RELOUS | $0 | $0 | Jun 19, 1997 |
| Apr 29, 1997 | 38059442K | RESOLVE | Non-Hazardous | 37 D 37 R 37-PROPERLY SECURE RESISTORS BEHIND CONTROLLER 37-REMOVE OBJECT STUCK IN GP RELAY. | $0 | $0 | Jun 19, 1997 |
| Apr 29, 1997 | 38059443M | RESOLVE | Non-Hazardous | 46 L 37 O 37 R 46-CHANGE HOIST CABLES. 37-MOUNT RESISTORES PROPERLY TOCONTROLLER 37-REMOVE OBJECT STUCK IN DTS USD RE... | $0 | $0 | Jun 19, 1997 |
| Apr 29, 1997 | 38059450K | RESOLVE | Non-Hazardous | CEASE USE OF ELEVATOR BASEMENT DOOR UNSECURED (HATCH) | $0 | $0 | Jun 19, 1997 |
| Apr 29, 1997 | 38059444Y | RESOLVE | Non-Hazardous | 37 R 37 D REMOVE OBJECT STUCK IN RELAYS GP-NI BGS IB CONTROLLER AND DISPATCHER 37-MOUNT RESISTORS TO CONTROLLER | $0 | $0 | Jun 19, 1997 |
| Apr 29, 1997 | 38059445X | RESOLVE | Non-Hazardous | 57 Y 57-REMOVE OIL FROM PIT | $0 | $0 | Jun 19, 1997 |
| Apr 29, 1997 | 38059447J | RESOLVE | Non-Hazardous | 46 L 37 R 46 CHANGE HOIST CABLES. 37-REMOVE OBJECT STUCK IN RELAY | $0 | $0 | Jun 19, 1997 |
| Nov 7, 1996 | 34146115N | RESOLVE | Non-Hazardous | INSTALLATION OF A/C UNITS WITHOUT FIRST OBTAINING AN EQUIPMENT USE PERMIT OR AN EQUIPMENT WORK WITHOUT. IN THAT AN EQ... | $0 | $0 | Jan 2, 1997 |