ECB violations
331 Greenwich Street, Manhattan • Block 00143 • Lot 0019
25 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Dec 2, 2022 | 39074948J | RESOLVE | CLASS - 1 | UNLAWFUL ACTS. FAILURE TO COMPLY WITH COMMISSIONER'S ORDER. I OBSERVED THAT A VIOLATION WAS ISSUED ON 04/15/2021 ECB ... | $6,250 | $0 | Mar 16, 2023 |
| Apr 15, 2021 | 39039484R | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLAINT MANNER I OBSERVED ON GROUND FLOOR ENTIRE 2, 3, 4 FLOORS SPRINKLER HEAD... | $1,250 | $0 | Nov 18, 2021 |
| Apr 15, 2021 | 39039485Z | RESOLVE | CLASS - 1 | WORK WITHOUT A PERMIT I OBSERVED AT TIME OF CERTIFICATE OF CORRECTION INSPECTION VIOLATION NUMBER 39001101R WAS ISSUE... | $0 | $0 | Nov 18, 2021 |
| Jul 17, 2019 | 35423881L | RESOLVE | CLASS - 1 | AN UNLAWFUL ACT FAILURE TO COMPLY WITH AN ORDER OF TEH COMMISSIONER FAILURE TO CORRECT AND CERTIFY SUMMONS#S 35359902... | $1,250 | $0 | Jan 16, 2020 |
| May 23, 2019 | 35359901X | RESOLVE | CLASS - 1 | UNLAWFUL ACTS FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER.IN MARCH 18 2019 A ELECTRICAL VIOLATION WAS ISSUE T... | $0 | $0 | Aug 22, 2019 |
| May 23, 2019 | 35359902H | RESOLVE | CLASS - 1 | UNLAWFUL ACTS. FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER. IN FEBRUARY 22, 2019, THREE ELECTRICAL VIOLATIONS... | $1,250 | $0 | Jan 16, 2020 |
| Apr 4, 2019 | 35359057J | RESOLVE | CLASS - 1 | UNLAWFUL ACT.FAILURE TO COMPLY W/AN ORDER OF THE COMMISSIONER.RECORDS INDICATE NO APPLICATION FILED TO CORRECT,CERTIF... | $1,250 | $0 | Nov 21, 2019 |
| Feb 28, 2019 | 35358962P | RESOLVE | CLASS - 1 | FAILURE TO PROTECT CONDUCTORS AGAINST OVERCURENT PER EC.LOAD CALCULATION NOT PROVIDED FOR HEATERS IN APTS 2,3 & 4.REM... | $0 | $0 | Aug 8, 2019 |
| Feb 22, 2019 | 35358961N | RESOLVE | CLASS - 1 | ELECTRICAL WORK WITHOUT A PERMIT. OBSERVED AT 10:00AM 1 ELECTRIC WATER HEATER INSTALLED IN APARTMENT 2, IN LOFT.NO EL... | $0 | $0 | Nov 21, 2019 |
| Feb 22, 2019 | 35358960L | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE ADEQUATE CIRCUIT OVER CURRENT PROTECTION DEVICE PERTABLE. LOAD CALCULATION NOT PROVIDED FOR FEEDER... | $1,200 | $0 | Nov 21, 2019 |
| Feb 20, 2019 | 39001400R | RESOLVE | CLASS - 1 | ON 02-20-19 @ APPROX 9:15 AM I OBSERVED IN APTS 2,3 AND 4 GAS, WATER AND SANITARY PIPING INSTALLED WITHOUT ANY GAS AN... | $1,250 | $0 | Nov 21, 2019 |
| Feb 20, 2019 | 39001399Z | RESOLVE | CLASS - 1 | ON 02-20-19 @ APPROX 9:15 AM I OBSERVED IN APTS 2,3 AND 4 GAS, WATER AND SANITARY PIPING INSTALLED WITHOUT ANY ACTIVE... | $0 | $0 | Nov 21, 2019 |
| Feb 20, 2019 | 39001398R | RESOLVE | CLASS - 1 | ON 02-20-19 @ APPROX 9:15 AM I OBSERVED GAS PIPING INSTALLED ON 1ST FLOOR PUBIC HALLWAY, PLASTIC TUBING INSTALLED FOR... | $625 | $0 | Nov 21, 2019 |
| Jan 9, 2019 | 39001103K | RESOLVE | CLASS - 1 | ON 01-09-18 @ APPROX 9:15 AM I OBSERVED A SPRINKLER SYSTEM INSTALLED THROUGHOUT ENTIRE 2, 3,4TH FLOOR APTS WITHOUT AN... | $0 | $0 | Nov 21, 2019 |
| Jan 9, 2019 | 39001102Z | RESOLVE | CLASS - 1 | ON 01-09-18 @ APPROX 9:15 AM I OBSERVED FROM THE 2ND-4TH FLOOR MULTIPLE LOCATIONS OF PAINTED SPRINKLER HEADS AND NOT ... | $625 | $0 | Nov 21, 2019 |
| Jan 9, 2019 | 39001101R | RESOLVE | CLASS - 1 | ON 01-09-18 @ APPROX 9:15 AM I OBSERVED A SPRINKLER SYSTEM INSTALLED THROUGHOUT ENTIRE 2, 3,4TH FLOOR APTS WITHOUT AN... | $1,250 | $0 | Nov 21, 2019 |
| Jan 9, 2019 | 39001104M | RESOLVE | CLASS - 1 | ON 01-09-18 @ APPROX 9:15 AM I OBSERVED IN APTS 2,3 AND 4 GAS, WATER AND SANITARY PIPING INSTALLED WITHOUT ANY ACTIVE... | $1,250 | $0 | Nov 21, 2019 |
| Jan 9, 2019 | 39001105Y | RESOLVE | CLASS - 1 | ON 01-09-18 @ APPROX 9:15 AM I OBSERVED GAS PIPING INSTALLED ON 1ST FLOOR PUBIC HALLWAY, PLASTIC TUBING INSTALLED FOR... | $625 | $0 | Nov 21, 2019 |
| Jan 9, 2019 | 39001106X | RESOLVE | CLASS - 1 | ON 01-09-18 @ APPROX 9:15 AM I OBSERVED IN APTS 2,3 AND 4 GAS, WATER AND SANITARY PIPING INSTALLED WITHOUT ANY GAS AN... | $1,250 | $0 | Nov 21, 2019 |
| Jan 4, 2019 | 32098033N | RESOLVE | CLASS - 1 | B154,36,50,50A,50B. AS PER B154 28-201.1 CEASE USE BAXI LUNA GAS FIRED BOILER ON 4TH FLOOR DUE TO FLEX GAS PIPING TO ... | $625 | $0 | Nov 21, 2019 |
| Jan 4, 2019 | 32098032L | RESOLVE | CLASS - 1 | B101 FOUND A BAX1 LUNA BOILER MODEL #1.310F1 INSTALLED W/O PERMIT ON 4TH FLOOR OBTAIN PROPER PERMIT. | $1,250 | $0 | Nov 21, 2019 |
| Jun 12, 2009 | 34752987K | RESOLVE | CLASS - 2 | ALTERED BUILDING OCCUPIED W/O A VALID C OF O. NOTED: AS PER DEPT OF BUILDING RECORDS NO C/O ISSUED FOR JOB #100309658... | $0 | $0 | Jul 30, 2009 |
| May 5, 2009 | 32066125Y | RESOLVE | CLASS - 2 | 36.50A.3A.50B 50A INSTALL SUPPORT ON FLUE PIPE 50B INTERLOCK FRESH AIR FAN W/ BOILER OPERATION | $500 | $0 | Jun 25, 2009 |
| Jan 19, 1999 | 34194986P | RESOLVE | Non-Hazardous | WORK WITHOUT PERMIT NOTED NEW PARTITION WALLS THROUGHT MADE OF METAL STUD & SHEETROCK NEW SHEETROCK CEILING THROUGHOU... | $0 | $0 | Mar 11, 1999 |
| May 23, 1997 | 32014837H | RESOLVE | Non-Hazardous | 16, 49 | $0 | $0 | Aug 18, 1997 |