ECB violations
243 Canal Street, Manhattan • Block 00208 • Lot 0020
26 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Sep 26, 2007 | 32052320M | RESOLVE | Non-Hazardous | 18B/. | $0 | $0 | Nov 15, 2007 |
| Sep 26, 2007 | 32052322X | RESOLVE | Non-Hazardous | 50A/50B/.50A-CORRODED BOIELR CASSING ALLOWING SPILLAGE OF COMBUSTION PRODUCTS.50B-COMBUSTION SPILLAGE AROUND UPPER & ... | $400 | $0 | Nov 15, 2007 |
| Sep 26, 2007 | 32052319P | RESOLVE | Non-Hazardous | 38/.38-INTRODUCE FRESH AIR DIRECTLY INTO BOILER ROOM BY MEANS OF DUCT. | $2,500 | $0 | Nov 15, 2007 |
| Sep 26, 2007 | 32052321Y | RESOLVE | Non-Hazardous | 18B/50A/.50A-CLEAN LINT OFF BOILER. | $2,500 | $0 | Feb 28, 2008 |
| Jun 9, 2006 | 32050113K | RESOLVE | Non-Hazardous | 50A,50B,50C.FUCTON V.T. BCR,15HP,NB69460,GAS,1994.50A-SECONDARY LOW WATER MANUAL RESET SWITCH ASSEMBLY DISCONNECTED.R... | $0 | $0 | Jul 27, 2006 |
| Jun 9, 2006 | 32050117H | RESOLVE | Non-Hazardous | 6A,36.FUCTON V.T. BOILER,15HP,NB64369,GAS 1992. 6A-SAFETY VALVE LEAKING. REPLACE DEFECTIVE SAFETY VALVE ON THE REFERE... | $2,500 | $0 | May 31, 2007 |
| Aug 4, 2004 | 32045394J | RESOLVE | Non-Hazardous | 11A/BQ9 36/38 50A/18 16/50B 50C 1982 FULTON NATL BD 42192 50A. ENCLOSEBOILER IN A ROOM TO PREVENT INJURY. 50B PIPE DO... | $650 | $0 | Oct 7, 2004 |
| Aug 3, 2004 | 32045389P | RESOLVE | Non-Hazardous | 50A/50B 50C/50D 50E 1988 FULTON N.B. 54299 50A. ENCLOSE BOILER IN A ROOM WITH A FIRE RATING OF 2 HRS 50B. REMOVE CARD... | $180 | $0 | Oct 7, 2004 |
| Aug 3, 2004 | 32045390M | RESOLVE | Non-Hazardous | BQ9/36 38/50A 50B/11A 1994 FULTON NATL. BD 69460 50A ENCLOSE BOILER IN A ROOM WITH A 2 HR FIRE RATING 50B PIPE DOWN T... | $850 | $0 | Oct 7, 2004 |
| Aug 3, 2004 | 32045391Y | RESOLVE | Hazardous | BQ9/36 38/40 16/51 50A/50B 50C 1977 FULTON NATL BB #33515 51 BOILER SEALED - HOLE AROUND FIRE BOX BY LEFT HANDHOLE. 1... | $0 | $0 | Oct 7, 2004 |
| Oct 22, 2003 | 38142433X | RESOLVE | Non-Hazardous | 31H10/34Q7/55Y13/2B10/52B11 31-H-10 REPAIR WORN GUIDE 34-Q-7 PROVIDE MISSING ELECTRICAL COVERS 55-Y-13 SEAL OIL LEAK ... | $180 | $0 | Dec 11, 2003 |
| Nov 19, 2002 | 38134073L | RESOLVE | Non-Hazardous | 81B05. 5 YEAR TAG EXPIRED. | $0 | $0 | Jan 9, 2003 |
| Oct 1, 1997 | 38064631X | RESOLVE | Non-Hazardous | 75R46R50O52H74M 75-PERFORM 5 YEAR TEST ADN TAG (50) CLEAN OIL FROM MACHINE (52) REPLACE BRAKE LINING (74) PROVIDE CAP... | $0 | $0 | Feb 26, 1998 |
| Oct 1, 1997 | 38064630Y | RESOLVE | Non-Hazardous | 75R46R74M 75-PERFORM 5 YEAR TEST AND TAG (74) CAPACITY PLATE. | $0 | $0 | Feb 26, 1998 |
| Sep 17, 1997 | 38064182J | RESOLVE | Non-Hazardous | 28H,48H,49H,50Y,75U, | $0 | $0 | Nov 6, 1997 |
| Sep 17, 1997 | 38064181H | RESOLVE | Non-Hazardous | 50Y,74A,75U, 74-THE RIGHT CITY I.D TAG | $0 | $0 | Nov 6, 1997 |
| Mar 15, 1995 | 38047647X | RESOLVE | Non-Hazardous | 74I,15C,46H,73O,33#. 74 CEASE USE AT 1P1860 UNTIL THE BY PASI KEY SWI-TCH IS REMOVED. 15 TERMINAL FLOORS. 33 SECURE G... | $0 | $0 | Jun 1, 1995 |
| Mar 5, 1995 | 38047648H | RESOLVE | Non-Hazardous | 5L,6L,5L,6L,49H,52L,15L,15L,73O. 5+6 CEASE USE OF 1206 UNTIL THE CAR GATES+CONTACTS ARE WORKING PROPERLY. 15-C-9-TERM... | $0 | $0 | Jun 1, 1995 |
| Apr 6, 1993 | 38033487Z | RESOLVE | Non-Hazardous | 05L 28L 73O 15L 48U 49U 11M 2L 15L 34L 30L 35M 15 CEASE USE UNTIL INTERLOCKS ARE WORKING P¢ROPERLY 2 BELLS 30 HOISTWA... | $0 | $0 | Jun 10, 1993 |
| Apr 6, 1993 | 38033488K | RESOLVE | Non-Hazardous | 2L 11M 15L 21L 31M 18M 30L 35M 28L 34I 2 BELLS 1 GUARDS 31 COVERS 18 COVERS SECURE 30 HOISTWAY WALLS 35 CO NAME | $0 | $0 | Jun 10, 1993 |
| Apr 30, 1992 | 34073064H | RESOLVE | Unknown | FAILURE TO PROVIDE DURABLE FLOOR NUMBERING SIGNS (3") THROUGHOUT. FAILURE TO PROVIDE DURABLE-STAIR IDENTIFICATION SIG... | $0 | $0 | Jun 11, 1992 |
| Oct 15, 1991 | 38018401N | RESOLVE | Non-Hazardous | 35P,15C,18L,18L,15L,74M,74AR,19L. 74 PROVIDE GRADING IN THE OVERHEAD. 74A REMOVE COMPLETELY THE BY PASS KFG SWITCH - ... | $150 | $0 | Mar 19, 1992 |
| Oct 10, 1991 | 38018650Y | RESOLVE | Non-Hazardous | 5L,5L,6L,6L,33P,35P,47L,10L,74L,57O,74AR,18L,18L. 74REPAIR ANNUNCIATOR74A REMOVE COMPLETELY THE BY PASS KFG SWITCH IT... | $150 | $0 | Mar 19, 1992 |
| Aug 1, 1988 | 32000757K | RESOLVE | Hazardous | BOILER NOT REGISTERED. | $35 | $0 | Sep 22, 1988 |
| Aug 1, 1988 | 32000755R | RESOLVE | Non-Hazardous | — | $0 | $0 | Sep 22, 1988 |
| Aug 1, 1988 | 32000756Z | RESOLVE | Unknown | — | $125 | $0 | Oct 6, 1988 |