ECB violations
Confucius Plaza, Manhattan • Block 00289 • Lot 0001
92 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Aug 6, 2026 | 39199609Y | ACTIVE | CLASS - 1 | AT THE TIME OF INSPECTION, OBSERVED A LARGE FLOOR OPENING AT THE ALTERATION WORK AREA WITH EXPOSED REINFORCING STEEL ... | $10,000 | $10,000 | Oct 15, 2026 |
| Jul 30, 2025 | 35721029L | ACTIVE | CLASS - 2 | RE-ISSUE #35684728K. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: ILLUMINATION FOR EXITS, EXIT DISCHARGES A... | $3,125 | $0 | Sep 5, 2025 |
| Aug 29, 2024 | 35684729M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED INTERIOR FPSC DOORS NOT CLOSING/WORKING PROPERLY AT 3RD F... | $625 | $0 | Nov 7, 2024 |
| Aug 29, 2024 | 35684728K | ACTIVE | CLASS - 2 | REISSUE#35674857H FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER:ILLUMINATION FOR EXITS,EXIT DISCHARGES AND PU... | $1,562 | $0 | Nov 7, 2024 |
| Apr 6, 2023 | 35674857H | ACTIVE | CLASS - 2 | REISSUE#35657708J FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATE EXITS EXIT DISCHARGES AND PUBLIC ... | $625 | $0 | Aug 24, 2023 |
| May 5, 2022 | 35657706X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER:USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8; 27-371(... | $625 | $0 | Aug 25, 2022 |
| May 5, 2022 | 35657707H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER:NOTED:OBSERVED ROFING MATERIAL HAS BECOME POROUS ALLOWING WATER... | $625 | $0 | Aug 25, 2022 |
| May 5, 2022 | 35657708J | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER:ILLUMINATION FOR EXITS EXIT DISCHARGES & PUBLIC CORRIDORS PER B... | $625 | $0 | Aug 25, 2022 |
| Apr 28, 2021 | 35554040R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTE: AT ROOF LEVELROOF LEAKS IN VARIOUS AREAS CAUSING DAMAGE TO C... | $625 | $0 | Sep 2, 2021 |
| Apr 26, 2021 | 39040041X | ACTIVE | CLASS - 2 | FRESH AIR FAN DEFECTIVE/AIR PROVING SWITCH DEFECTIVE/LOOSE FLUE CONNECTION TO BOILER/SAFETY DISCHARGE PIPE INCORRECT/... | $625 | $0 | Aug 26, 2021 |
| Apr 26, 2021 | 39040073K | ACTIVE | CLASS - 2 | WATER FEED TANK BACKFLOW NOT PIPED DOWN/MOTORIZED WATER VALVE RT SIDE LEAKING/VAC SYSTEM PUMP LEAKING; CORRECT VIOLAT... | $625 | $0 | May 12, 2021 |
| Apr 26, 2021 | 39040072Z | ACTIVE | CLASS - 2 | MANHOLE LEAKING/SKIMMER PIPE LEAKING/OLD WATER STORAGE TANK MANHOLE CORRODED; CORRECT VIOLATION AND SUBMIT THE CERTIF... | $625 | $0 | May 10, 2021 |
| Nov 6, 2020 | 35539664J | RESOLVE | CLASS - 1 | BC 3307.6.5.11 FAILURE TO NOTIFY THE DEPARTMENT PRIOR TO REMOVING SIDEWALK SHED.AT THE TIME OF AN INSPECTION OF AN AC... | $1,250 | $0 | Jun 3, 2021 |
| May 26, 2020 | 35495322H | RESOLVE | CLASS - 2 | REISSUE#35415409H FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCE. NOTE AT EXP#4 REAR OF BLDG AT EXIT 10 & 7 ABOVE BOT... | $3,125 | $0 | Sep 10, 2020 |
| May 26, 2020 | 35495323J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER USE OF PROHIBITED DOOR & OR HARDWARE PER BC 1008.1.8;27-371(J). NOT... | $625 | $0 | Sep 10, 2020 |
| May 26, 2020 | 35495321X | RESOLVE | CLASS - 2 | REISSUE#35415410P FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER ILLUMINATION FOR EXITS,EXIT DISCHARGES & PUBLIC C... | $1,562 | $0 | Sep 10, 2020 |
| Dec 20, 2019 | 35462940Y | RESOLVE | CLASS - 1 | 3314.3.3=FAILURE TO COMPLY WITH DEISGN DRAWINGS NOTED AT TIME OF INSEPCTION OF AN ATCIE JOBSIET AT A 44 STORY BUIDLIN... | $625 | $0 | Nov 12, 2020 |
| Apr 15, 2019 | 35415409H | RESOLVE | CLASS - 2 | REISSUE#35322505P DATE OF ISSUE 3/9/18 FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. AT REAR OF BUILDING EXI... | $0 | $0 | Jun 27, 2019 |
| Apr 15, 2019 | 35415410P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER ILLUMINATION FOREXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER ... | $0 | $0 | Jun 27, 2019 |
| Nov 27, 2018 | 35380652K | RESOLVE | CLASS - 1 | UNSAFE STORAGE OF MATERIALS DURING CONSTRUCTION. 8 STORY NEW BUILDING UNDER CONSTRUCTION @ BULKHEAD LEVEL ACTIVE JOBS... | $0 | $0 | Dec 19, 2019 |
| Nov 27, 2018 | 35380650R | RESOLVE | CLASS - 1 | BC3309.1 FAILURE TO PROTECT ADJOINING PROPERTIES DURING CONSTRUCTION OPERATIONS IN PURSUANT TO 3309.10-NO ROOF PROTEC... | $0 | $0 | Dec 19, 2019 |
| Mar 9, 2018 | 35322505P | RESOLVE | CLASS - 2 | REISSUE #35200926H FAILURE TO MAINTAIN BUILDING WALLS OR APPURTENANCEAT REAR OF BUILDING EXIT 7 AND EXIT 10 BRICKWORK... | $0 | $0 | Aug 30, 2018 |
| Mar 9, 2018 | 35322506R | RESOLVE | CLASS - 2 | 28-301.1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT 1ST FL REAR VESTIBULE STORAGE OF (3) GAS POWERED S... | $0 | $0 | Sep 13, 2018 |
| Mar 9, 2018 | 35322507Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT CELLAR ELECTRICAL ROOM BEING USED FOR STORAGE OF CONSTRUCTI... | $0 | $0 | Sep 13, 2018 |
| Mar 9, 2018 | 35322508K | RESOLVE | CLASS - 2 | EXIT DOORS NOT SELF-CLOSING EXIT DOORS NOT SELF-CLOSING AT 1ST FLOOR EXIT (B). REM: REPAIR/REPLACE DOOR. | $0 | $0 | Sep 13, 2018 |
| Jul 15, 2016 | 35200925X | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF CLOSING. NOTED: VARIOUS EXIT DOOR THROUGHOUT THE SCHOOL ARE NOT SELF CLOSING INCLUDING BUT NOT LIM... | $0 | $0 | Sep 15, 2016 |
| Jul 15, 2016 | 35200926H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG WALL(S) OR APPURTENANCES. NOTED: @ EXIT 7, FACADE HORIZONTAL BRICKWALL AROUND THE EXIT HAS M... | $0 | $0 | Sep 15, 2016 |
| Jul 15, 2016 | 35200927J | RESOLVE | CLASS - 2 | WORK W/OUT A PERMIT. WORK NOTED: @ CELLAR ERECTED FULL HEIGHT PARTITIONS OF COMBUSTIBLE WOODEN MATERIAL CREATING A RO... | $0 | $0 | Sep 15, 2016 |
| Jul 15, 2016 | 35200929N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN A CODE COMPLIANT MANNER: LACK OF EMERGENCYLIGHTING FOR EXITS, EXIT DISCHARGES & PUBLIC CO... | $0 | $0 | Sep 15, 2016 |
| Jul 15, 2016 | 35195549H | RESOLVE | CLASS - 2 | ALTERED/CHANGED BLDG OCCUPIED W/OUT A VALID C OF O AS PER 28-11 8.3.1-28-118.5.2. TCO# 100641442-T-9 EXPIRED ON 5/5/2... | $0 | $0 | Sep 15, 2016 |
| Jul 15, 2016 | 35200928L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: MULTIPLE EXIT DOOR THROUGHOUT ENTIRE SCHOOL HAVE PROBLEM WH... | $0 | $0 | Sep 15, 2016 |
| Apr 25, 2016 | 35148298K | RESOLVE | CLASS - 2 | ALTERED/CHANGED BLDG OCCUPIED W/O A VALID CERT OF OCCUPANCY 28-118.3.128-118.3.2.TCO#100061442-T-9 EXPIRED 5/5/04.REM... | $500 | $0 | Aug 25, 2016 |
| Mar 21, 2014 | 35093396Z | RESOLVE | CLASS - 2 | RE-ISSUE # 34987587H. LOOSE,MISSING MORTAR JOINTS. AT EXTERIOR WALLS OF GYM & ADJACENT TO STAIR C -VISIBLE FROM INTER... | $0 | $0 | Jun 5, 2014 |
| Mar 21, 2014 | 35093397K | RESOLVE | CLASS - 2 | PARTIAL OBSTRUCTION WITH COMBUSTIBLES. AT 2ND FLOOR CORRIDOR ADJACENT TO ROOM 201, FILLED WOOD BOOK SHELVES,TABLE,STA... | $0 | $0 | Jun 5, 2014 |
| Mar 21, 2014 | 35093398M | RESOLVE | CLASS - 2 | UNAUTHORIZE STORAGE. AT ELECTRIC METER SERVICE ROOM, STORAGE OF VARIOUS EQUIPMENT & SUPPLIES. REMEDY: REMOVE ALL ITEM... | $0 | $0 | Jun 5, 2014 |
| Mar 21, 2014 | 35093399Y | RESOLVE | CLASS - 2 | OCCUPANCY CONTRARY TO C OF O # 78332. 11 CARS PARKED IN ACTIVE SCHOOL YARD. C OF O DOES NOT INDICATE OPEN OFF STREET ... | $0 | $0 | Jun 5, 2014 |
| Jan 11, 2013 | 34987586X | RESOLVE | CLASS - 2 | SEC. 27.766. REISSUE: 34950109Y, 34902345J. NO F.A.I. IN GAS METER ROOM IN CELLAR. REMEDY: PROVIDE FAI | $0 | $0 | Apr 4, 2013 |
| Jan 11, 2013 | 34987587H | RESOLVE | CLASS - 2 | EXTERIOR FACADE MISSION/LOOSE MORTAR JOINTS AT REAR NEAR GYM EXIT DOOR. REMEDY: MAKE SAFE. | $0 | $0 | Apr 4, 2013 |
| Mar 12, 2012 | 34950109Y | RESOLVE | CLASS - 2 | 27-766. REISSUE # 34902345J. NO FRESH AIR VENT INSIDE GAS METER ROOM IN CELLAR. REMEDY: PROVIDE F.A.I. | $0 | $0 | May 17, 2012 |
| Mar 12, 2012 | 34933712Y | RESOLVE | CLASS - 3 | REISSUE # 34902347N. DEFECTIVE DOORS EXIT 3 VESTIBULE DOORS & STAIR C 2ND FLOOR, DOORS NOT CLOSING PROPERLY. REMEDY: ... | $0 | $0 | May 17, 2012 |
| Feb 25, 2011 | 34902342Y | RESOLVE | CLASS - 2 | SEC. 1509.8;27-333/334 MISSING PROTECTIVE GUARDRAILS RE: 34872059Y,34793117H,34645875M. AT 3RD FL GYM ROOF APPROX 1 F... | $0 | $0 | May 5, 2011 |
| Feb 25, 2011 | 34902344H | RESOLVE | CLASS - 3 | DEFECTIVE EXTERIOR LIGHTING MOUNTS. AT ROOF,PARAPET MOUNTED AREA LIGHTS HAVE LOOSE MOUNTING PLATES AT VARIOUS LOCATIO... | $0 | $0 | May 5, 2011 |
| Feb 25, 2011 | 34902346L | RESOLVE | CLASS - 2 | PARTIAL CORRIDOR OBSTRUCTION. AT 2ND FL NEAR ROOM 214,THE CORRIDOR HAS PARTIAL OBSTRUCTION NOTED: BOOKCASES,TABLE,10 ... | $0 | $0 | May 5, 2011 |
| Feb 25, 2011 | 34902345J | RESOLVE | CLASS - 2 | SEC. 27-766 NO VENT FOR GAS METER ROOM. AT CELLAR/BSMT GAS METER ROOM #C18 HAS NO FRESH AIR VENT. REMEDY: PROVIDE VEN... | $0 | $0 | May 5, 2011 |
| Feb 25, 2011 | 34902347N | RESOLVE | CLASS - 2 | DEFECTIVE DOORS. FIRE PROOF SELF CLOSING DOORS ARE RACKED & NOT CLOSING PROPERLY AT - GYM,RIGHT EXIT DOOR - 2ND FLOOR... | $0 | $0 | May 5, 2011 |
| Aug 17, 2010 | 34872059Y | RESOLVE | CLASS - 2 | REISSUE # 34645875M, 34793117H MISSING PROTECTIVE GUARDS OVER GYM. REMEDY: INSTALL PROTECTIVE GUARDS. | $0 | $0 | Sep 16, 2010 |
| Aug 17, 2010 | 34872060L | RESOLVE | CLASS - 2 | REISSUE 34793118J; MISSING HANDRAIL AT REAR PLAYYARD (MIDDLE RAIL).REMEDY; INSTALL HANDRAIL. | $0 | $0 | Sep 16, 2010 |
| Aug 17, 2010 | 34872062P | RESOLVE | CLASS - 2 | DEFECTIVE LIGHTING AT REAR OF BLDG ALL 3 FLRS. SECTION OF LIGHTS/EXIT SIGNS NOT WORKING. REMEDY: REPAIR FORTHWITH. | $0 | $0 | Sep 16, 2010 |
| Aug 17, 2010 | 34872061N | RESOLVE | CLASS - 1 | EXIT PASSAGWAY AT CELLAR OBSTRUCATED W ITH FURNITURE, TABLES, CHAIRS, OTHER COMBUSTILE DEBRIS. REMEDY:REMOVE OBSTRUCT... | $0 | $0 | Sep 16, 2010 |
| Jul 14, 2009 | 34793117H | RESOLVE | CLASS - 2 | SEC. BC 1509.8 RE #34645875M MISSING PROTECTION GUARDS OVER GYM ROOF 3 STORY BUILDING. REMEDY: INSTALL GUARD. | $0 | $0 | Nov 19, 2009 |