ECB violations
125-127 Bowery, Manhattan • Block 00304 • Lot 0016
59 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| May 30, 2026 | 39190504R | ACTIVE | CLASS - 1 | I OBSERVED EXTENSIONS CORD BEEN USE AS PERMANENT WIRING TO POWER SINGLE ROOMS, APPLIANCES AND LIGHT FIXTURES IN COMME... | $1,600 | $1,600 | Aug 6, 2026 |
| May 23, 2026 | 39190505Z | ACTIVE | CLASS - 1 | I OBSERVED UNSAFE UNSUITABLE ELECTRICAL CONDITIONS THROUGHOUT GROUND, 3RD AND 5TH FLOORS, OPEN BOXES, WIRE HANGING AN... | $1,600 | $1,600 | Aug 6, 2026 |
| May 18, 2026 | 39189053Z | ACTIVE | CLASS - 1 | OBSERVED CUBICAL BEING INSTALLED AT 3RD FLOOR AND DEMOLISHED AT 5TH FLOOR. NO WORK ALLOWED TO CONSTRUCT OR DEMOLISH L... | $2,500 | $2,500 | Feb 5, 2027 |
| May 6, 2026 | 39187523P | ACTIVE | CLASS - 1 | OBSERVED IN F & R TRADING STORE IN THE BASEMENT OPEN ENDED GAS LINE AND A FUTURE ON GAS LINE. ALSO A SPRINKLER HEAD N... | $2,500 | $2,500 | Feb 16, 2027 |
| May 6, 2026 | 39187526K | ACTIVE | CLASS - 1 | OBSERVED IN THE BASEMENT BOILER ROOM BEING USED AS A STORAGE ROOM. ALSO, STORAGE AROUND GAS METER LOCATED IN CHINESE ... | $2,500 | $2,500 | Feb 16, 2027 |
| May 6, 2026 | 39187525Z | ACTIVE | CLASS - 1 | OBSERVED ON THE FOURTH FLOOR SPRINKLER HEAD INSTALLED BACKWARDS. IN THE BATHROOM SINKS DOESN'T CLOSE. ON THE FIFTH FL... | $2,500 | $2,500 | Feb 16, 2027 |
| May 6, 2026 | 39187492L | ACTIVE | CLASS - 1 | ELECTRICAL WORK WITHOUT A PERMIT. OBSERVED ON THE 2ND 3RD 4TH FLS INSTALLATION OF A/C SPILT UNIT DUCTLESS SYSTEM AND ... | $2,500 | $2,500 | Feb 9, 2027 |
| May 6, 2026 | 39187493N | ACTIVE | CLASS - 1 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT, APPARATUS, MATERIALS, DEVICES, APPLIANCES OR WIRING IN USE. OBSERV... | $1,600 | $1,600 | Feb 9, 2027 |
| May 6, 2026 | 39187494P | ACTIVE | CLASS - 1 | FAILURE TO GROUND ELECTRICAL SYSTEMS. OBSERVED IN THE BASEMENT THAT THE MAIN BUILDING WATER GROUND CLAMP IS DEUTERATE... | $4,800 | $4,800 | Feb 9, 2027 |
| May 6, 2026 | 39187495R | ACTIVE | CLASS - 1 | FAILURE TO PROVIDE/MAINTAIN SUFFICIENT ACCESS/WORK SPACE ABOUT ELECTRICAL EQUIPMENT. OBSERVED IN THE BASEMENT THAT TH... | $1,600 | $1,600 | Feb 9, 2027 |
| May 6, 2026 | 39187511H | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.ATOI I WAS GRANTED ACCESS TO SUBJECT LOCATION WHERE I OBSERVED ... | $2,500 | $2,500 | Feb 25, 2027 |
| May 6, 2026 | 39187524R | ACTIVE | CLASS - 1 | OBSERVED THROUGH OUT THE BUILDING SPRINKLER HEADS OBSTRUCTED WHICH IS CONTRARY TO CODE SECTION BC 903.3.3, REPAIR AND... | $2,500 | $2,500 | Feb 16, 2027 |
| Apr 14, 2026 | 39184515L | ACTIVE | CLASS - 2 | OBSERVED DEBRIS STORED AT INTERIOR OF 4TH FLOOR, BATHROOM CEILING REMOVED AT 3RD & 4TH FLOOR EXPOSING THE WOODEN FLOO... | $1,250 | $1,250 | Feb 25, 2027 |
| Apr 14, 2026 | 39186914H | ACTIVE | CLASS - 2 | OBSERVED APPROX. 85% OF THE EXISTING CUBICLES USED AS SLEEPING QUARTERS WAS REMOVED FROM THE 4TH & 5TH FLOOR WITHOUT ... | $1,250 | $1,250 | Feb 25, 2027 |
| Apr 14, 2026 | 39184486L | ACTIVE | CLASS - 2 | OBSERVED APPROX. 85% OF THE CUBICLES AT 4TH & 5TH FLOOR WAS COMPLETELY REMOVED CONTRARY TO C OF O # 35211. FLOOR IS O... | $1,250 | $1,250 | Feb 25, 2027 |
| Apr 14, 2026 | 39184514J | ACTIVE | CLASS - 1 | OBSERVED THE DROP LADDER LANDING AREA TO THE EXTERIOR FIRE ESCAPE ON BOWERY ST SIDE OF THE BUILDING IS OBSTRUCTED BY ... | $2,500 | $2,500 | Feb 25, 2027 |
| Sep 11, 2025 | 39160034Y | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER; OBSERVED CEILINGS ON 2ND, 3RD, AND 4TH FLOORS REMOVED IN COMMO... | $25,000 | $25,000 | Jan 8, 2026 |
| Aug 4, 2025 | 39155953Z | ACTIVE | CLASS - 1 | ATOI OBSERVED CEILINGS ON SECOND, THIRD AND FOURTH FLOOR REMOVED IN COMMON BATHROOMS. COMPROMISED CEILING JOISTS SUPP... | $2,530 | $2,530 | Aug 17, 2026 |
| Mar 17, 2021 | 39037757Y | RESOLVE | CLASS - 2 | BOILER FLUE IS UNSUPPORTED; CORRECT VIOLATION AND SUBMIT THE CERTIFICATE OF CORRECTION | $0 | $0 | May 6, 2021 |
| Mar 17, 2021 | 39037756M | RESOLVE | CLASS - 2 | CAST IRON CIRCULATOR INSTALLED ON DOMESTIC HW BOILER/ BOILER FLUE TO CHIMNEY IS UNSUPPORTED; CORRECT VIOLATION AND SU... | $312 | $0 | May 6, 2021 |
| Mar 27, 2020 | 39020505R | RESOLVE | CLASS - 2 | FOUND AO SMITH HW420 HOT WATER BOILER FTM MISSING SPILL SWITCH, CLEANED BOILER ROOM | $625 | $0 | Apr 22, 2021 |
| Mar 27, 2020 | 39020506Z | RESOLVE | CLASS - 2 | FOUND WEILMCLAIN LGB-10 FTM NO STORAGE IN BOILER ROOM, CHIMNEY BASE NOT SEALED | $625 | $0 | Apr 22, 2021 |
| May 10, 2013 | 35014718Y | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN A CODE-COMPLIANT MANNER. DEFECTS NOTED:AT TIME OF INSPECTION WATER IS COMING THROUGH RUBB... | $1,000 | $0 | Jun 27, 2013 |
| Dec 6, 2011 | 34925103Z | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN A CODE COMPLIANT MANNER.NOTED AT EXP.#1,FIRE ESCAPE AT 2ND FLR STORY AWNING IS ILLEGALLY ... | $1,000 | $0 | Feb 23, 2012 |
| Aug 18, 2010 | 34852223Z | RESOLVE | CLASS - 1 | FAIL MAINTAIN BLDG COMPLIANT MANNER:LACK EMERGENCY POWER TO EXIT SIGNSPER BC 10115.3;27-384(E). NOTED: THRU OUT 2ND, ... | $4,800 | $0 | Jul 21, 2011 |
| Aug 18, 2010 | 34852222R | RESOLVE | CLASS - 1 | FAIL TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER: USE PROB DOOR/HARDWAREAS PER BC 1008.1.8;27-371(J). NOTED: AT THE 2ND... | $1,000 | $0 | Jul 21, 2011 |
| Jun 16, 2005 | 34477347Z | RESOLVE | Non-Hazardous | WORK WITHOUT A PERMIT WORK NOTED INSTALLED NEW STORE FRONT SHEETROCK PARTITIONS METAL PAN STAIR FROM BASEMENT TO FIRS... | $250 | $0 | Aug 4, 2005 |
| May 25, 2005 | 34471004J | RESOLVE | Hazardous | EXIT PASSAGEWAY-TOTAL OBSTRUCTION:OPEN SECTION AT TOP OF AWNING SIGN WHERE FIRE-ESCAPE DISCHARGE LADDER PASS THROUGHT... | $2,500 | $0 | Jan 26, 2006 |
| Sep 29, 2003 | 34414517Y | RESOLVE | Non-Hazardous | OCCUPANCY CONTRARY TO THAT ALLOWED BY CERTIFICATE OF OCCUPANCY#85211 USE CHANGED FROM STORES TO A MINI-MALL WITHOUT A... | $800 | $0 | Nov 13, 2003 |
| May 14, 2003 | 34392846K | RESOLVE | Non-Hazardous | FAILURE TO PROVIDE A SYSTEM OF AUTOMATIC SPRUNLERS WHERE REQUIRED LOCATION RESTAURANT BASEMENT NO SPRUNKLER SYSTEM IN... | $2,500 | $0 | Jul 3, 2003 |
| Apr 8, 2003 | 34383954N | RESOLVE | Non-Hazardous | PREMISES DOES NOT COMPLY WITH LL58/87 IN THAT PUBLIC RESTROOMS. DO NOT MEET THE MINIMUM REQUIREMENTS FOR CLEARANCE, T... | $2,500 | $0 | Aug 21, 2003 |
| Dec 17, 2002 | 34378277Z | RESOLVE | Non-Hazardous | (1) HAVING INSTALLED A SIGN W/O A PERMIT REMEDY : REMOVE ILLEGAL WORK | $400 | $0 | May 1, 2003 |
| Dec 17, 2002 | 34378278K | RESOLVE | Non-Hazardous | (1) HAVING INSTALLED AN AWNING W/O A PERMIT REMEDY : REMOVE ILLEGAL WORK ! | $400 | $0 | May 1, 2003 |
| Dec 17, 2002 | 34377977P | RESOLVE | Non-Hazardous | HAVING INSTALLED AN AWNING WITHOUT A PERMIT TWO. REMEDY: REMOVE ILLEGAL WORK. | $0 | $0 | Mar 13, 2003 |
| Dec 17, 2002 | 34377978R | RESOLVE | Non-Hazardous | 1 HAVINE AN ILLUMINATED AWNING SINGN 2, HAVING AWNING SIGNAGE WITH A SURFACE AREA EXCEEDING 12 SQ FT. 3, HAVING AWNIN... | $0 | $0 | Mar 13, 2003 |
| Dec 17, 2002 | 34377920Y | RESOLVE | Non-Hazardous | HAVING A PROJECTING SIGN LESS THAN 10 FT ABOVE THE CURB LINE. REMEDY: REMOVE ILLEGAL WORK. | $0 | $0 | Mar 13, 2003 |
| Dec 17, 2002 | 34377924L | RESOLVE | Non-Hazardous | HAVING MORE THAN 3 ILLUMINATED SIGNAS IN ONE WINDOW IN C6-1 DISTRICT. REMEDY: REMOVE ILLEGAL SIGNAGE. | $0 | $0 | Mar 13, 2003 |
| Dec 17, 2002 | 34378276R | RESOLVE | Non-Hazardous | HAVING SIGNAGE DOUBLE FACED PROJECTING MORE THAN 18 IN ACROS THE STREET LINE. (2ND FLOOR) REMEDY: REMOVE ILLEGAL SIGN... | $800 | $0 | Sep 18, 2003 |
| Dec 17, 2002 | 34378100N | RESOLVE | Non-Hazardous | HAVING AN ILLUMINATED SIGN WITHOUT A CURRENT PRMIT. (2ND FLOOR) REMEDY: REMOVE ILLEGAL WORK. | $0 | $0 | Sep 18, 2003 |
| Dec 17, 2002 | 34377921X | RESOLVE | Non-Hazardous | AHVING A SIGN ATTACHED TO A FIRE ESCAPE REMEDY: REMOVE ILLEGAL WORK. | $0 | $0 | Mar 13, 2003 |
| Dec 17, 2002 | 34377922H | RESOLVE | Non-Hazardous | HAVING FLASHING SIGNAGE IN A WINDOW IN C6-1 DISTRICT. REMEDY: REMOVE ILLEGAL SIGNAGE. | $0 | $0 | Mar 13, 2003 |
| Dec 17, 2002 | 34377925N | RESOLVE | Non-Hazardous | HAVING SIGNAGE (DOUBLE OR MULTIFACED) PROJECTING MORE THAN 18 IN ACROSS THE STREET LINE. REMEDY: REMOVE ILLEGAL SIGNAGE. | $0 | $0 | Mar 13, 2003 |
| Dec 17, 2002 | 34378279M | RESOLVE | Non-Hazardous | (1) HAVING ILLUMINATED AWNING SIGANGE REMEDY : REMOVE ILLEGAL SIGNAGE | $400 | $0 | May 1, 2003 |
| Dec 17, 2002 | 34377976N | RESOLVE | Non-Hazardous | 1 HAVING AN ILLUMINATED AWNING SIGN 2, HAVING AWNING SIGNAGE WITH A SURFACE AREA EXCEEDING 12 SQ FT. 3, HAVING AWNING... | $800 | $0 | Mar 13, 2003 |
| Dec 17, 2002 | 34377918P | RESOLVE | Non-Hazardous | HAVING INSTALLED FOUR SIGNS WITHOUT A PERMIT. REMEDY; REMOVE ILLEGAL WORK. | $800 | $0 | Mar 13, 2003 |
| Dec 17, 2002 | 34377919R | RESOLVE | Non-Hazardous | HAVING THREE ILLUMINATED SIGNS WITHOUT A CURRENT PERMIT. REMEDY; REMOVE ILLEGAL WORK. | $400 | $0 | Mar 13, 2003 |
| Dec 17, 2002 | 34377923J | RESOLVE | Non-Hazardous | HAVING AN ILLUMINATED SIGN LARGER THAN 8 SQ FT IN A WINDOW IN C6-1 DISTRICT. REMEDY: REMOVE ILLEGAL SIGNAGE. | $800 | $0 | Mar 13, 2003 |
| Dec 16, 2002 | 34372666P | RESOLVE | Non-Hazardous | OCCUPANCY CONTRARY TO THAT ALLOWED BY C OF O BUILDING DEPARTMENT RECORDS NOTED: UNDER PERMIT #102119529 3/5/99 1, SIN... | $0 | $0 | Apr 10, 2003 |
| Dec 16, 2002 | 34372665N | RESOLVE | Non-Hazardous | WORK WITHOUT A PERMIT NOTED THE INTEIOR OR STORE HAS BEEN SUB DIVIED INTO 6 STORES WITH INSTALLATION OF 6 INTERIOR RO... | $0 | $0 | Jan 30, 2003 |
| Dec 13, 2002 | 34378099P | RESOLVE | Non-Hazardous | HAVING INSTALLED A SIGN WITHOUT A PERMIT. (2ND FLOOR). REMEDY: REMOVE ILLEGAL WORK. | $800 | $0 | Sep 18, 2003 |