ECB violations
282-284 East 3 Street, Manhattan • Block 00372 • Lot 0014
49 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Dec 23, 2025 | 39171288H | ACTIVE | CLASS - 2 | OBSERVED OBSTRUCTED SPRINKLER HEADS THROUGHOUT THE BUILDING, MISSING INSULATION ON BATHROOM TRAPS, LACK OF FIRESTOPPI... | $1,250 | $0 | Dec 24, 2025 |
| Dec 23, 2025 | 39171289J | ACTIVE | CLASS - 2 | OBSERVED IN BASEMENT DAMAGED SPRINKLER HEAD; THE DOOR OPENS INTO SPRINKLER LINE, AND THE DRAIN LINE IS IN THE DEDICAT... | $1,250 | $0 | Feb 6, 2026 |
| Dec 23, 2025 | 39171291Z | ACTIVE | CLASS - 2 | FOUND A O SMITH (MODEL#HW 670) GAS FIRED BOILER NOT REGISTERED CORRECT VIOLATING CONDITION SUBMIT CERTIFICATE OF CORR... | $1,250 | $0 | Dec 24, 2025 |
| Dec 23, 2025 | 39171251Y | ACTIVE | CLASS - 2 | FOUND WEIL MCLAIN(MODEL# 588 DUAL FUEL BOILER NOT REGISTERED CORRECT VIOLATING CONDITION SUBMIT CERTIFICATE OF CORREC... | $1,250 | $0 | Dec 24, 2025 |
| Dec 23, 2025 | 39171248N | ACTIVE | CLASS - 2 | FOUND WEIL MCLAIN(MODEL# 588) DUAL FUEL BOILER NOT REGISTERED, CORRECT VIOLATING CONDITION SUBMIT CERTIFICATE OF CORR... | $1,250 | $0 | Dec 24, 2025 |
| Apr 4, 2024 | 39110753P | RESOLVE | CLASS - 3 | OBSERVED ON THE 6TH FLOOR AC ROOM LEAK ON THE CAP OF THE WATER LINE, ALSO ON THE ROOF LEVEL STAIRCASE STANDPIPE NOT P... | $500 | $0 | Jun 5, 2024 |
| Mar 27, 2024 | 39110081L | RESOLVE | CLASS - 1 | ONLY ELEVATOR IN THE BUILDING OUT OF SERVICE. RESTORED TO SERVICE IMMEDIATELY AND CONTACT NYCDOB. AT EIE@BUILDINGS.NY... | $3,125 | $0 | May 29, 2024 |
| Nov 15, 2023 | 39099372R | RESOLVE | CLASS - 1 | CLASS 1: UPON INSPECTION FOUND DEVICE TO BE OUT OF SERVICE. THIS PRESENTS A HAZZARDOUS CONDITION TO RESIDENTS & STAFF... | $3,125 | $0 | Nov 28, 2023 |
| Sep 8, 2023 | 39094526H | RESOLVE | CLASS - 1 | R T S . ELEVATOR IN BUILDING OUT OF SERVICE , UPON INSPECTION , DEVICE IS FOUND TO BE OUT OF SERVICE, RESTORE TO SERV... | $1,250 | $0 | Oct 20, 2023 |
| May 26, 2023 | 38274589R | RESOLVE | CLASS - 1 | 97X17 THE ONLY ELEVATOR IN BUILDING OUT OF SERVICE.UPON INSPECTION THEDEVICE IS FOUND TO DUE OUT OF SERVICE CREATING ... | $1,250 | $0 | Aug 17, 2023 |
| Jan 26, 2023 | 39078494M | RESOLVE | CLASS - 1 | ELEVATOR OUT OF SERVICE. REPAIR AND CALL THE DOB ELEVATOR DIVISION FOR A PROPER INSPECTION. 97-X-17 | $1,250 | $0 | Apr 6, 2023 |
| Dec 9, 2022 | 39075413H | ACTIVE | CLASS - 2 | AS PER ONE NATURAL GAS BURNING, HOT WATER BOILER MODEL 588 SERIES 1, BOILER NO. 100473-01. BOILER NOT REGISTERED AS P... | $625 | $0 | Jan 11, 2023 |
| Dec 9, 2022 | 39075411Y | ACTIVE | CLASS - 2 | AS PER ONE NATURAL GAS BURNING, AO SMITH DOMESTIC HOT WATER BOILER. MODEL NO. HW-670 200, SERIAL NO. 1937M000013; BOI... | $625 | $0 | Jan 11, 2023 |
| Dec 9, 2022 | 39075412X | ACTIVE | CLASS - 2 | AS PER ONE, NATURAL GAS BURNING, WEIL MCLAIN, HOT WATER BOILER, MODEL 588 SERIES 1, BOILER NO. 100473-02; BOILER NOT ... | $625 | $0 | Jan 11, 2023 |
| Dec 5, 2022 | 39075113X | ACTIVE | CLASS - 2 | OBSERVED: AT SECOND FLOOR, TERRACE, CONCRETE TILES ARE SPLIT /CRACKED AND DETERIORATED., REPAIR AND/OR REPLACE | $625 | $0 | Dec 8, 2022 |
| Dec 5, 2022 | 39075114H | ACTIVE | CLASS - 2 | OBSERVED: FROM FIRST FLOOR TO 6TH FLOOR, MECHANICAL ROOM, GAS METER/GENERATOR RMS, EXPOSED STEEL STRUCTURE (COLUMNS, ... | $1,250 | $0 | Dec 8, 2022 |
| Nov 23, 2021 | 39051619R | ACTIVE | CLASS - 2 | NOTED: OBSERVED PIPES AND ELECTRICAL CONDUITS PENETRATING THROUGH EACH FLOOR AND CEILING WITHIN ALL AC ROOMS WITH NO ... | $3,125 | $0 | Dec 13, 2021 |
| Sep 30, 2021 | 39048522N | RESOLVE | CLASS - 1 | COUNTERWEIGHT ROLLER BROKEN OFF RIGHT SIDE (CU). EMERGENCY STOP SWITCH WORKS BUT NO BUZZER. ALARM BELL NO BUZZER. CAR... | $1,250 | $0 | Oct 15, 2021 |
| Sep 15, 2021 | 39047504P | RESOLVE | CLASS - 2 | SECTIONS ON MIDDLE LEFT SIDE OF BOILER ARE CORRODED. CORRECT VIOLATING CONDITION AND SUBMIT A CERTIFICATE OF CORRECTION. | $625 | $0 | Oct 15, 2021 |
| Feb 12, 2020 | 39017429R | RESOLVE | CLASS - 2 | WEIL MCLAIN 588 BOILER #2 MISSING COMBUSTION AIR FAN PROVING SWITCH. CORRECT VIOLATING CONDITIONS AND SUBMIT CERTIFIC... | $625 | $0 | Feb 21, 2020 |
| Feb 12, 2020 | 39017430Y | RESOLVE | CLASS - 2 | AO SMITH BOILER MISSING COMBUSTION AIR FAN PROVING SWITCH. CORRECT VIOLATING CONDITIONS AND SUBMIT CERTIFICATE OF COR... | $625 | $0 | Feb 21, 2020 |
| Feb 12, 2020 | 39017428P | RESOLVE | CLASS - 2 | WEIL MCLAIN 588 BOILER #1 MISSING PROVING SWITCH FOR COMBUSTION AIR FAN. CORRECT VIOLATING CONDITIONS AND SUBMIT CERT... | $625 | $0 | Feb 21, 2020 |
| Dec 16, 2019 | 35416632P | RESOLVE | CLASS - 1 | 28-104.8.4 INADEQUATE TENANT PROTECTION PLAN. NOTED:AT TIME OF INSPECTION READING THE TPP SECTION 3:DOES NOT SAY THE ... | $6,250 | $6,250 | Feb 20, 2020 |
| May 8, 2019 | 38269564Y | RESOLVE | CLASS - 2 | 70O02,29M07,40B07,40P16. 70O02-PIT AREA DIRYT; 29M07-DOOR OPERATOR COVER MISSING AND WIRES ARE EXPOSED; 40B07 LADDER ... | $0 | $0 | Aug 22, 2019 |
| Apr 11, 2019 | 38269240H | RESOLVE | CLASS - 1 | CEASE USE(05L10) 26B07, 35M07, 71X10, 71B10, 80B10, 70O02, 39M07. CEASEUE USE ITEM=05-L=REPAIR DOOR RESTRICTOR & CONT... | $0 | $0 | Jun 20, 2019 |
| Feb 26, 2019 | 38268404K | RESOLVE | CLASS - 2 | 39Q03,58B10,42B10,70O02,80M07,64M07. 39Q-PROVIDE AND INSTALL; 58B-REPAIR; 42B-PROVIDE READABLE FUSES. 70O-CLEAN HOIST... | $0 | $0 | Jun 13, 2019 |
| Feb 7, 2019 | 38267897N | RESOLVE | CLASS - 1 | CU32H11,59B7,CU59H10. 32H11-REPLACED COUNTERWEIGHT GUIDE FACE ROLLER WORN; 59B7-BRAKE MAINTENANCE TAG INSUFFICIENT MI... | $0 | $0 | Apr 18, 2019 |
| Sep 26, 2018 | 35361387P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. NOTED: AT ROOF 2ND LEVEL BULKHEAD EXTERIOR WALL HAS LOOSE CRAC... | $0 | $0 | Nov 29, 2018 |
| Sep 26, 2018 | 35361830K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED ON 9/26/18 AT ABOVE ADDRESS FERNCO COUPLING AND JIM C... | $0 | $0 | Nov 29, 2018 |
| Jul 3, 2018 | 32097184X | RESOLVE | CLASS - 2 | 50. SPILL SWITCH MISSING. CURRENT ALL VIOLATING CONDITIONS & SUBMIT C OF C. | $0 | $0 | Oct 11, 2018 |
| May 18, 2018 | 35331808R | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NO FIRE STOPPING PER BC 712.3 27-345. NOTED: AT CELLAR LEVEL S... | $0 | $0 | Aug 2, 2018 |
| May 18, 2018 | 35331809Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING WALLS OR APPURTENANCES. NOTED: CRACK IN CHIMNEY AND CRACKS IN BULKHEAD EXT WALL WHERE MA... | $0 | $0 | Aug 2, 2018 |
| Apr 27, 2018 | 35329499J | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN BUILDING CODE COMPLIANT MANNER. I OBSERVED IN BOILER ROOM IN CELLAR OS AND Y VALVE ON THE BACK OF... | $0 | $0 | Jun 28, 2018 |
| Apr 27, 2018 | 35329498H | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING CODE COMPLIANT MANNER. I OBSERVED IN CELLAR GAS METER AND GAS PIPING INSTALLED IN THE SA... | $0 | $0 | Jun 28, 2018 |
| Aug 31, 2017 | 35290532R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED ON 08/308/31/17 AT ABOVE ADSDRESS FERNCO COUPLINGS INS... | $0 | $0 | Dec 14, 2017 |
| Aug 31, 2017 | 35290533Z | ACTIVE | CLASS - 1 | 404.1 GAS PIPING PROHIBITED LOCATION-FIRE PUMP ROOM.OBSERVED ON 8/31/17 AT ABOVE ADDRESS GAS METER IS LOCATED IN TEH ... | $0 | $0 | Dec 14, 2017 |
| Aug 31, 2017 | 35290360J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES.NOTED:AT BULKHEAD EXTERIOR WALL CRACK ABOVE BULKHEADDDDDDDDD EX... | $0 | $0 | Dec 14, 2017 |
| Aug 31, 2017 | 35290359M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOT FIRE STOPPING PER BC 712.3;27-345.NOTED: AT CELLAR IN FIRE ... | $0 | $0 | Dec 14, 2017 |
| Mar 21, 2017 | 35235727P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. INSTALLATION/MAINTENANCE OF PLUMBING MATERIALS/EQUIPMENT PER P... | $0 | $0 | Apr 27, 2017 |
| Mar 21, 2017 | 35235728R | ACTIVE | CLASS - 1 | GAS PIPING IN A PROHIBITED LOCATION-FIRE PUMP ROOM OBSERVED ON 3/21/17GAS PIPING INSTALLED IN FIRE PUMP ROOM. RMDY: C... | $0 | $0 | Apr 27, 2017 |
| Sep 27, 2016 | 35212795P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:FAILURE TO COMPLY WITH LAW FOR DRAINAGE SYSTEM PER PC 702.1; 27... | $0 | $0 | Nov 17, 2016 |
| Sep 27, 2016 | 35213726X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG WALL(S) OR APPURTENANCES. DEFECTS NOTED:BULK HEAD ON ROOF HAS LOOSE BRICKS/MORTAR JOINTS, CR... | $0 | $0 | Nov 17, 2016 |
| Sep 27, 2016 | 35213727H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC712.3; 27-345. NOTED: MISSING FIRE STOPPING... | $0 | $0 | Nov 17, 2016 |
| Feb 2, 2016 | 35171401P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER:PROVIDE REQUIREDCORRIDOR W/PER BC 1016.2; 27-369 (PARTIAL OBSTR... | $0 | $0 | Mar 31, 2016 |
| Feb 2, 2016 | 35171400N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES (EXTERIOR). DEFECTS NOTED: BULKHEAD ON ROOF HAS LOOSE BRICKS MO... | $0 | $0 | Mar 31, 2016 |
| Aug 8, 2001 | 32025809Y | RESOLVE | Non-Hazardous | 19B-A.O. SMITH HOTWATER BOILES USED FOR DONESTIC HOT WATER HAS ASME "H" STAMP AND IS SUBIJECT TO N.Y.C BOILER CODE. N... | $180 | $0 | Sep 27, 2001 |
| May 22, 2001 | 38116776Z | RESOLVE | Non-Hazardous | 02X11 14I12 09I12 74H12 16H12 30Z11 31Q03 36T07 36D06 50T07 54T07 34T07 52M07 74-H12,CAR SADDLE, 16H-12, LOBBY GIBS, ... | $350 | $0 | Jul 13, 2001 |
| Feb 9, 1999 | 38084656K | RESOLVE | Non-Hazardous | 75U 22D | $350 | $0 | Mar 25, 1999 |
| Jan 29, 1997 | 38058447P | RESOLVE | Hazardous | 56X,55X,73M,22D,74AQ,11Q,74BX,74CX.56-REPAIR OIT SWICTH 55-RPAIR PIT LIGHT,73-ID EQUIPMENT 22-PROPERLY SECIRE EMERGEN... | $1,000 | $0 | Mar 17, 1997 |