ECB violations
Earth School, Manhattan • Block 00387 • Lot 0001
98 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Mar 30, 2012 | 34953885K | RESOLVE | CLASS - 2 | PLASTER DAMAGE IN STAIRCASE D ROOF SKYLIGHT AREA EVIDENT SIGN OF FALLING PLASTER REM; MAKE SAFE FORTHWITH | $0 | $0 | May 31, 2012 |
| Mar 30, 2012 | 34953880L | RESOLVE | CLASS - 2 | DEFECTIVE FIRE DAMPERS IN BOILER ROOM NOT FUNCTIONING AT TIME OF INSP REM: REPAIR DAMPERS | $0 | $0 | May 31, 2012 |
| Mar 30, 2012 | 34953884Z | RESOLVE | CLASS - 2 | DEFECTIVE SUMP PUMP AT B64 BOILER ROOM PUMP BEING HELD OPEN W/ ROPE TO KEEP INOPERATION REM: MAKE REPAIRS | $0 | $0 | Jun 14, 2012 |
| Mar 30, 2012 | 34953883R | RESOLVE | CLASS - 2 | DEFECTIVE DOORS MAIN ENTRANCE VESTIBULE DOORS 3FL STAIR ABC CORRIDOR NEAR 338 2FL STAIR A-B-C-D 1FL B-C CORRIDOR NEAR... | $0 | $0 | May 31, 2012 |
| Mar 30, 2012 | 34953882P | RESOLVE | CLASS - 2 | DEFECTIVE EMERGENCY LIGHTS THROUGHOUT GYM CAFETERIA LIGHT NOT OPERATIONAL AT TIME OF INSP REM; REPLACE REPLACE LIGHTING | $0 | $0 | May 31, 2012 |
| Mar 30, 2012 | 34953881N | RESOLVE | CLASS - 2 | DEFECTIVE FLOORING IN ROOMS 204 NEAR CLOSET SINK SOFT SPOTS IN SUB FLOORING ALSO ROOM 169 NEAR WINDOW WARPING WOOD FL... | $0 | $0 | May 31, 2012 |
| Mar 30, 2012 | 34953886M | RESOLVE | CLASS - 3 | WATER PENETRATION INTO LIBRARY ALONG WINDOW REM: SEAL PENETRATION | $0 | $0 | May 31, 2012 |
| Mar 10, 2011 | 34906812H | RESOLVE | CLASS - 3 | CEILING OPEN-PLASTER SURFACE.@ 3RD FLR ROOM 334 & 2ND FLR ROOM 220,W/APPROX 2'X2'OPENING IN EACH CEILING W/CONDUIT WO... | $0 | $0 | May 5, 2011 |
| Mar 10, 2011 | 34906813J | RESOLVE | CLASS - 3 | BROKEN STAIR TREAD.@ STAIRWAY B BETWEEN 2 & 3RD FLR,THE LEFT STAIRS, THE TOP TREAD IS BROKEN W/APPROX 2"X3"PC MISSING... | $0 | $0 | May 5, 2011 |
| Mar 10, 2011 | 34906302H | RESOLVE | CLASS - 2 | PONDING WATER.@ CELLAR LEVEL, 50% OF AREA WITH MOISTURE & WATER PRESENT NOTD RECENT PIPELOAD-UNABLE TO DETERMINE CAUS... | $0 | $0 | May 5, 2011 |
| Mar 10, 2011 | 34906811X | RESOLVE | CLASS - 2 | PARTIAL CORRIDOR OBSTRUCTION.@ 1ST FLR ADJACENT TO SMOKE DOORS @ ROOM 154,PARTIALLY OBSTRUCTED CORRIDOR W 6 TABLES, 4... | $0 | $0 | May 5, 2011 |
| Mar 10, 2011 | 34906814L | RESOLVE | CLASS - 2 | CRACKED BRICK MASONRY.@ SOUTH EAST CORNER OF STAIRWAY B ROOF PARAPET,AAPROX 3'VERTICAL CRACK IN PARAPET WALL.RE,:REPA... | $0 | $0 | May 5, 2011 |
| May 26, 2010 | 34846384Z | RESOLVE | CLASS - 2 | REISSUE #34724179Y, 34793415X. MULTIPLE (GLAZED) BLOCKS CRACKED THROUGHOUT GYM. REMEDY: REPAIR GYM WALLS. | $0 | $0 | Sep 16, 2010 |
| May 26, 2010 | 34846386M | RESOLVE | CLASS - 2 | DEFECTIVE BATHROOM, 2ND FLR, GIRLS BATHROOM, 3 TOILETS INOPERABLE. ALSO STALL DOORS HARDWARE BROKEN. REMEDY: REPAIR B... | $0 | $0 | Sep 16, 2010 |
| May 26, 2010 | 34846385K | RESOLVE | CLASS - 2 | DEFECTIVE DOORS. NOTED: CAFETERIA DOORS HITTING FRAMES, STUCK SHUT. REMEDY: REPAIR/REPLACE DOORS. | $0 | $0 | Sep 16, 2010 |
| Mar 24, 2010 | 38208215R | RESOLVE | CLASS - 2 | 97X10.97 SIDEWALK CAR NOT WORKING RESTORTE TO SERVICE | $0 | $0 | May 13, 2010 |
| Jul 2, 2009 | 34793415X | RESOLVE | CLASS - 2 | RE:34724179Y. GLAZED BLOCK INSIDE GYM W/VERTICAL CRACKS NEAR EXIT 8 & AT DOOR DIVIDE ENDS MIDDLE OF GYM. REMEDY:REPAI... | $0 | $0 | Sep 17, 2009 |
| Jul 2, 2009 | 34793416H | RESOLVE | CLASS - 2 | DEFECTIVE DOORS EXIT #8, BROKEN DOOR ALSO EXIT DOOR FROM CAFETERIA NEXT TO ROOM B1. REMEDY:REPAIR DOORS FORTHWITH! | $0 | $0 | Sep 17, 2009 |
| Nov 20, 2008 | 34724181N | RESOLVE | CLASS - 2 | ALL BULK HEAD DOORS HAVE WATER DAMAGE DUE TO WATER PENETRATION THAT'S SPALLED PLASTER AROUND DOORS WITH NO LOCK DEVIC... | $0 | $0 | Jan 8, 2009 |
| Nov 20, 2008 | 34724179Y | RESOLVE | CLASS - 2 | GYM GLAZED CEMENT BLOCK WITH VERTICAL CRACKS NEAR EXIT '8' & AT DOOR DIVIDER ENDS IN MIDDLE OF GYM ON BOTH SIDES. REM... | $0 | $0 | Jan 8, 2009 |
| Nov 20, 2008 | 34724180L | RESOLVE | CLASS - 2 | FIRE DOOR IS MISSING AT EXIT '8' VESTIBULE STWY 'B' 1ST & 2ND FLR DOOR CHECK BROKEN. REMEDY: REPAIR/REPLACE DOOR. | $0 | $0 | Jan 8, 2009 |
| Nov 20, 2008 | 34724178M | RESOLVE | CLASS - 2 | ENTIRE BASEMENT FLR IS TAKEN ON WATER FROM SLAB. REMEDY: STOP WATER PENETRATION. | $0 | $0 | Jan 8, 2009 |
| Nov 20, 2008 | 34724177K | RESOLVE | CLASS - 2 | #34563194H PLASTER IS SPALLING AWAY FROM THE CEILING & WALL LOCATED AT STAIRWAY 'D' ON THE 3RD FLR ADJACENT TO THE SK... | $0 | $0 | Jan 8, 2009 |
| Mar 8, 2007 | 34563194H | RESOLVE | Hazardous | REISSUE: 34513104J. PLASTER IS SPALLING AWAY FROM THE CEILING & WALL LOCATED @ STAIRWAY "D" ON THE 3RD FLOOR ADJACENT... | $0 | $0 | Apr 19, 2007 |
| Mar 2, 2006 | 34513101Y | RESOLVE | Non-Hazardous | RE-ISSUE VIO # 34427945N. NOTED: AT 1ST FL MAIN ENTRANCE STAIRWAY 2 FIRE STOP DOORS WIRE GLASS PANELS WERE REPLACED B... | $0 | $0 | Apr 20, 2006 |
| Mar 2, 2006 | 34513104J | RESOLVE | Non-Hazardous | NOTED: PLASTER IS SPALLING FALLING APART AT 3RD FL STAIRWAY "D". REMEDY: REPAIR PLASTER. | $0 | $0 | Apr 20, 2006 |
| Mar 2, 2006 | 34513106N | RESOLVE | Non-Hazardous | NOTED: FAILURE TO PROVIDE FIRE STOPPING AT ELECTRICAL RM # B40 AT WALL PIPES (BASEMENT LEVEL) REMEDY: PROVIDE FIRE ST... | $0 | $0 | Apr 20, 2006 |
| Mar 2, 2006 | 34513105L | RESOLVE | Non-Hazardous | NOTED: WATER IS LEAKING FROM ROOF AT AUDITORIUM . REMEDY: REPAIR ROOF. | $0 | $0 | Apr 20, 2006 |
| Mar 2, 2006 | 34513103H | RESOLVE | Non-Hazardous | NOTED: VESTIBULE DOORS ARE MISSING AT 1ST FL STAIRCASE "A", "B" & "C".REMEDY: REPLACE/INSTALL VESTIBULE DOORS. | $0 | $0 | Apr 20, 2006 |
| Jan 6, 2004 | 34427928L | RESOLVE | Non-Hazardous | EXIT DOORS ARE NOT SELFCLOSING NOTED EXIT DOOR AT THE TWO EXITS (5 DOORS)ON AVENUE B DO NOT SELF CLOSE DUE TO CORRODE... | $0 | $0 | Apr 1, 2004 |
| Jan 6, 2004 | 34427945N | RESOLVE | Non-Hazardous | RE-ISSUE FAILURE TO MAINTAIN BUILDING NOTED AT 1ST FLOOR MAIN ENTRANCESTAIRWAY TWO FIRE STOP DOORS REMOVED WIRE-GLASS... | $0 | $0 | Apr 1, 2004 |
| Jan 3, 2003 | 34372829K | RESOLVE | Non-Hazardous | EXIT PASSAGEWAY OR CORRIDOR REQUIRED WIDTH DECREASED BY OBSTRUCTIONS. NOTED : AT THRID FLOOR EAST SIDE ( DIVISION OF ... | $0 | $0 | Mar 13, 2003 |
| Jan 3, 2003 | 34372910H | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN BUUILDING. NOTED: AT FIRST FLOOR MAIN ENTRANCE, STAIRWELL TWO FIRE STOP DOORS REMOVED WIRED- GLAS... | $0 | $0 | Mar 13, 2003 |
| Jan 3, 2003 | 34372830H | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN BUILDING NOTED : AT FIRST FLOOR NEAR ROOM 154, SMOKE STOP DOOR, PANIC HARDWARE DEFECTIVE MISSING ... | $0 | $0 | Mar 13, 2003 |
| Jan 8, 2002 | 34312256H | RESOLVE | Non-Hazardous | RE-ISSUE- FAILURE TO MAINTAIN. DEFECT, SIDEWALK ELEVATOR IS INOPERABLE, DEFECTIVE AND BROKEN. REMEDY: MAINTAIN BUILDI... | $0 | $0 | Apr 11, 2002 |
| Jan 8, 2002 | 34312255X | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN: DEFECT NOTED; PERIMETER WROUGHT IRON FENCE (AVE B SIDE) IS DEFECTIVE, CORRODED, PULLING AWAY, OU... | $0 | $0 | Apr 11, 2002 |
| Feb 13, 2001 | 34281360Z | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN DEFECT IS SPALLING FLAKING DETERIORATING PLASTER DUE TO WATER LEAK FROM ROOF AT ROOM # 210,110, 1... | $0 | $0 | Oct 11, 2001 |
| Feb 13, 2001 | 34281361K | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN:DEFECT IS DOOR FRAME ON EXIT DOOR ON EAST 6TH ST IS BROKEN AND FALLING APART. REMEDY: MAINTAIN BU... | $0 | $0 | Oct 11, 2001 |
| Feb 13, 2001 | 34281358J | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN DEFECT IS ENTRACE BAILING ARE BROKEN DEFECTIVE FALLING APART AT MAIN ENTRANCES. REMEDY: MAINTAIN ... | $0 | $0 | Oct 11, 2001 |
| Feb 13, 2001 | 34281357H | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN DEFECT IS SIDE WALK ELEVATOR IS INOPERABLE DEFECTIVE AND BROKEN. REMEDY; MAINTAIN BUILDING REPAIR... | $0 | $0 | Oct 11, 2001 |
| Feb 13, 2001 | 34281359L | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN DEFECT IS WATER PENETRATION DAMAGING CELLING PLASTER AT ROOM #210,110,108 AND #B04 | $0 | $0 | Oct 11, 2001 |
| Mar 1, 2000 | 34240405M | RESOLVE | Hazardous | FAILURE TO MAINTAIN BLDG. EXTERIOR DEFECT IS GATES OVER SIDE WALK ELEVATOR IS BROKEN AND IS IN DANGER OF COLLASPING I... | $0 | $0 | Mar 23, 2000 |
| Jul 28, 1999 | 34177067J | RESOLVE | Non-Hazardous | FAILURE TO PROVIDE 3" FL # ID SIGNS ALL FLS. FAILURE TO PROVIDE 3" STAIR LETTER ID SIGNS ON ALL STAIRS & FLS. REMEDY:... | $0 | $0 | Sep 23, 1999 |
| Jul 28, 1999 | 34177068L | RESOLVE | Non-Hazardous | FAILURE TO PROVIDE EMERGENCY POWER EMERGENCY LIGHTS THROUGHOUT FLS & STAIRCASE. FAILURE TO PROVIDE EMERGENCY POWER TO... | $0 | $0 | Sep 23, 1999 |
| Apr 15, 1996 | 34135386L | RESOLVE | Non-Hazardous | ALTERED BUILDING OCCUPIED WITHOUT A VALID CERTIFCATE OF OCCUPANCY NOTED: ALTERED PARKING LOT OCCUPIED AS SCHOOL WITHO... | $500 | $0 | Jul 18, 1996 |
| Aug 23, 1995 | 34128837X | RESOLVE | Non-Hazardous | ALTERED BUILDING OCCUPIED WITHOUT A VALID CERTIFICATE OF OCCUPANCY. NOTED: ALTERED PARKING LOT OCCUPIED WITHOUT A VAL... | $500 | $0 | Nov 6, 1995 |
| May 31, 1991 | 34052824Z | RESOLVE | Hazardous | FAILRUE TO SAFEGUARD PUBLIC AND PROPERTY AFFECTED BY CONSTRUCTION OPERATIONS REPARIS BEING DONE TO ROOF PARAPET NEW B... | $345 | $0 | Jul 18, 1991 |
| Jun 27, 1988 | 34010032P | RESOLVE | Non-Hazardous | ALTERED PARKING LOT OCCUPIED WITHUT A VALID C OF O. REMEDY: OBTAIN VALID C OF O. | $1,000 | $0 | Nov 17, 1988 |