ECB violations
265 East 4 Street, Manhattan • Block 00387 • Lot 0049
53 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Jan 8, 2026 | 39173027Z | ACTIVE | CLASS - 2 | OBSERVED THROUGHOUT THE BUILDING NO TRAP WRAP INSULATION FOR TRAPS IN BATHROOMS. FOURTH FLOOR TWO SHOWERS NOT OPERATI... | $1,250 | $0 | Feb 6, 2026 |
| Apr 24, 2025 | 39146002Z | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN, AT TIME OF INSPECTION, I OBSERVED FIRE PUMP IN FUEL TANK ROOM, PROHIBITED BY NYC BC 913.2.1 SECT... | $1,250 | $0 | May 8, 2025 |
| Apr 16, 2025 | 39145021J | RESOLVE | CLASS - 2 | CLASS 2 ITEMS: IN-CAR COMMUNICATION INOPERATIVE. PROVIDE AN UPDATED MAINTENANCE LOG. PROVIDE A MAINTENANCE PROGRAM. P... | $625 | $0 | May 8, 2025 |
| Dec 7, 2023 | 39100936Z | ACTIVE | CLASS - 2 | I OBSERVED ON THE ROOF TOP LEVEL, A BX CABLE EXTENDED FROM THE WALL ABOVE THE EXIT DOOR NOT TERMINATED AS REQUIRED. A... | $800 | $0 | Jan 2, 2024 |
| Dec 7, 2023 | 39100961K | ACTIVE | CLASS - 2 | OBSERVED IN THE BASEMENT/CELLAR INADEQUATE VENTILATION IN THE GAS METER ROOM., REPAIR AND/OR REPLACE | $625 | $0 | Jan 4, 2024 |
| Dec 7, 2023 | 39100935R | ACTIVE | CLASS - 2 | I OBSERVED ON THE ROOFTOP THE RACEWAY AND JUNCTION BOXES SUPPLYING POWER TO VARIOUS EXHAUST FANS UNSUPPORTED AND LAYI... | $800 | $0 | Jan 2, 2024 |
| Dec 5, 2022 | 39075071R | ACTIVE | CLASS - 2 | OBSERVED: AT ROOF LEVEL, WATERPROOFING MEMBRANE SHOWS DETACHMENT/HOLES AND OTHER FAILURES THAT ALLOW WATER PENETRATIO... | $625 | $0 | Dec 6, 2022 |
| Dec 5, 2022 | 39075072Z | ACTIVE | CLASS - 2 | OBSERVED: AT EXPOSURE # 2 & 3 FACADE, SEVERAL CRACKS IN DIFFERENT LOCATIONS. PREVIOUS VIOLATION # 39063664Y, MAINTAIN... | $1,250 | $0 | Dec 6, 2022 |
| Dec 5, 2022 | 39075073K | ACTIVE | CLASS - 2 | OBSERVED: AT ROOF LEVEL,BUCKHEAD, CEILING DAMAGES DUE WATER PENETRATION, ALSO, LOSS OF CORNERS OF THE EXTERIOR METAL ... | $1,250 | $0 | Dec 6, 2022 |
| Dec 5, 2022 | 39075078J | ACTIVE | CLASS - 2 | GAS METER ROOM NOT PROPERLY VENTED, AS PER APPENDIX E OF THE 2014 FGC AN OPENING TO THE OUTSIDE AIR IN THE WALL OF SU... | $625 | $0 | Dec 6, 2022 |
| Jun 30, 2022 | 39065074N | ACTIVE | CLASS - 2 | NO VENTILATION IN THE GAS METER ROOM. AS PER FGC GAS METER ROOMS SHALL BE PROPERLY VENTILATED., REPAIR AND/OR REPLACE | $1,562 | $1,562 | Jul 8, 2022 |
| Jun 30, 2022 | 39065075P | RESOLVE | CLASS - 2 | JIM CAPS INSTALLED ON CAST IRON FITTINGS LOCATED IN THE GAS METER ROOM, REPAIR AND/OR REPLACE | $625 | $0 | Jul 8, 2022 |
| Jun 7, 2022 | 39063665X | ACTIVE | CLASS - 2 | BULKHEAD AT ROOF LEVEL, PLASTER FALLING WATER IS COMING IN FROM ROOF. TEMPORARY BLUE NYLON TARP PLACE OVER FULL ROOF ... | $625 | $0 | Jun 8, 2022 |
| Jun 7, 2022 | 39063664Y | ACTIVE | CLASS - 2 | CRACKS IN FACADE ON EXP1(HAS SHED), EXP2, EXP3 REAR., MAINTAIN EXTERIOR BUILDING WALL | $1,250 | $0 | Jun 8, 2022 |
| May 31, 2022 | 35636545L | RESOLVE | CLASS - 1 | FAILURE TO GROUND ELECTRICAL SYSTEMS I OBSERVED IN THE MAIN WORKER METER ROOM,THE ELECTRICAL GROUNDING ELECTRODE COND... | $4,800 | $0 | Sep 1, 2022 |
| May 31, 2022 | 35636546N | ACTIVE | CLASS - 2 | UNSAFE UNSUITABLE ELECTRICAL WIRING,EQUIPMENT IN USE.I OBSERVED AT THEROOF LEVEL OVER THE EXIT DOORS,ARMORED CABLE TH... | $800 | $0 | Sep 1, 2022 |
| Sep 21, 2021 | 39047879L | ACTIVE | CLASS - 2 | BULKHEAD AT ROOF LEVEL, PLASTER FALLING WATER IS COMING IN FROM ROOF. TEMPORARY BLUE NYLON TARP PLACE OVER FULL ROOF ... | $625 | $0 | Oct 15, 2021 |
| Sep 21, 2021 | 39047880Z | ACTIVE | CLASS - 2 | CRACKS IN FACADE ON EXP1(HAS SHED), EXP2, EXP3 REAR., MAINTAIN EXTERIOR BUILDING WALL | $1,250 | $0 | Oct 15, 2021 |
| Jun 30, 2021 | 35557795Z | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NO NATURAL OR MECHANICAL VENTILATION IN GAS METER ROOM AT CELL... | $3,125 | $0 | Oct 7, 2021 |
| Apr 1, 2021 | 35553961R | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER - NO NATURAL ON MECHANICAL EXHAUST IN PLACE AT CELLAR GAS METER... | $1,250 | $0 | Jun 24, 2021 |
| Feb 19, 2021 | 35546161N | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER NOTE FAILURE TO PROVIDE FRESH AIR TO GAS METER RM@CELLAR LEVEL.PROV... | $3,125 | $0 | May 20, 2021 |
| Dec 15, 2020 | 35542862H | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER.FAILURE TO PROVIDE FRESH AIR TO GAS METER ROOM AT CELLAR LEVEL.PROV... | $3,125 | $0 | Mar 11, 2021 |
| Sep 25, 2020 | 35502897L | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTE AT CELLAR LEVEL IN GAS METER ROOM NO NATURAL FRESH AIR VE... | $3,125 | $0 | Jan 28, 2021 |
| Feb 21, 2020 | 35476083X | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED:AT TIME OF INSPECTION I OBSERVED AT CELLAR LEVEL AT GAS ... | $3,125 | $0 | May 7, 2020 |
| Jan 9, 2020 | 35467656J | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER - NOTED AT CELLAR GAS METER ROOM NO NATURAL OR MECHANICAL VENTI... | $3,125 | $0 | Mar 26, 2020 |
| Nov 23, 2019 | 35461486Z | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER AT CELLAR GAS METER ROOTS NOT NATURAL OR MECHANICAL VENTALATION... | $1,250 | $0 | Feb 13, 2020 |
| Oct 9, 2019 | 35452412L | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTE AT CELLAR LEVEL AT GAS METER ROOM NO VENTILATION FOR FRESH... | $3,125 | $0 | Dec 26, 2019 |
| Sep 20, 2019 | 39009905Z | ACTIVE | CLASS - 2 | I OBSERVED ON THE ROOFTOP UNSUPPORTED METAL RACEWAYS BOTH RIGID TYPE( INTERMEDIATE CONDUIT) AND FLEXIBLE TYPE(SEALTIT... | $0 | $0 | Oct 4, 2019 |
| Sep 20, 2019 | 39009835M | ACTIVE | CLASS - 2 | NO VENTILATION IN THE GAS METER ROOM. , REPAIR AND/OR REPLACE | $0 | $0 | Oct 4, 2019 |
| Sep 20, 2019 | 39009830N | ACTIVE | CLASS - 2 | NOTED: OBSERVED AT EXPOSURE #1, HORIZONTAL CRACKS ALONG THE LENGTH OF THE RAMP, VERTICAL CRACKS AT EXPOSURE #2 FROM G... | $0 | $0 | Oct 4, 2019 |
| Jul 31, 2019 | 35442483J | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER NOTED: AT CELLARGAS MOTOR ROOM HAS NO NATURAL OR MECHANICAL VEN... | $0 | $0 | Oct 17, 2019 |
| Jun 8, 2019 | 35434282N | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTE: AT BASEMENT LEVEL GAS METER ROOM NO FRESH AIR VENTILATION... | $0 | $0 | Aug 15, 2019 |
| May 18, 2019 | 35414912K | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER AT TIME OF INSPECTION NOTED AT CELLAR GAS METER ROOM NO VENTIAT... | $0 | $0 | Jul 18, 2019 |
| Apr 15, 2019 | 35293805R | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: OBSERVED SPALLLING PLASTER AT STAIR "A" BULKHEAD SOME P... | $0 | $0 | Apr 22, 2019 |
| Apr 15, 2019 | 35293804P | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. NOTED: OBSERVED THROUGHOUT EXPOSURE #1 T VARIOUS LOCATIONS-CRA... | $0 | $0 | Apr 22, 2019 |
| Apr 5, 2019 | 35415305N | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED ON 4/5/19 AT ABOVE ADDRESS NO VENTILATION IN GAS METE... | $0 | $0 | Jun 13, 2019 |
| Mar 23, 2019 | 35386112R | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANER AT TIME OF INSPECTIONNOTED AT CELLAR GAS METER ROOM HAS NO VENTALATI... | $0 | $0 | May 16, 2019 |
| Jan 14, 2019 | 35379854K | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: AT TIME OF INSPECTION,I OBSERVED AT CELLAR LEVEL AT GAS MET... | $0 | $0 | Mar 7, 2019 |
| Dec 18, 2018 | 35636127Z | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. AT TIME OF INSPECTION NOTED: CELLAR GAS METER ROOM DOES NOT HA... | $3,125 | $0 | Apr 14, 2022 |
| Dec 3, 2018 | 35372689Y | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED: CELLAR LEVEL,GAS METER ROOM HAS NO FRESH AIR VENT. REMED... | $0 | $0 | Feb 14, 2019 |
| Sep 27, 2018 | 35361831M | RESOLVE | CLASS - 1 | FGC411.1 RESIDENTIAL GAS FLEX USED ON COMMERCIAL EQUIPMENT. OBSERVED ON 9/27/18 AT ABOVE ADDRESS RESIDENTIAL GAS FLEX... | $0 | $0 | Nov 29, 2018 |
| Sep 27, 2018 | 35361388R | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. NOTED:AT EXP#3 THERE ARE SEVERAL VERTICAL CRACKS AT BUILDING W... | $0 | $0 | Nov 29, 2018 |
| Sep 27, 2018 | 35361832Y | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED ON 9/27/18 AT ABOVE ADDRESS NO FRESH AIR VENT IN GAS ... | $0 | $0 | Nov 29, 2018 |
| Jul 20, 2018 | 32097407Y | RESOLVE | CLASS - 2 | B254,50A,50B,50C. AS PER CLASS 2 (B254) 28.301.1 FAILURE TO MAINTAIN 50A-"U" RATED EXPANSION TANK WITH NO PRESSURE RE... | $0 | $0 | Oct 25, 2018 |
| Mar 8, 2018 | 35322074M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN A CODE-COMPLIANT MANNER.OBSERVED @TOP OF STAIRWELL NO INSPS TEST (VALUE) INSTALLED W/PRES... | $0 | $0 | May 17, 2018 |
| Mar 8, 2018 | 35325201J | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER.OBSERVED IN CELLAR NO VENTILATION IN THE GAS METER ROOM AS IS REQUI... | $0 | $0 | May 17, 2018 |
| Aug 31, 2017 | 35290391M | RESOLVE | CLASS - 2 | FAIL TO PROVIDE GROUND FAULT CIRCUIT INTERROPTOR (GFCI) AS REQUIRED OBSERVED 1 H KITCHEN;CONVENIENCE RECEPTACLE OUTLE... | $0 | $0 | Dec 14, 2017 |
| Aug 31, 2017 | 35290361L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3; 27-345. NOTED: IN GAS METER ROO... | $0 | $0 | Dec 21, 2017 |
| Aug 31, 2017 | 35290534K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSRVED ON 8/31/17 AT ABOVE ADDRESS NO BALL DRIP (AUTOMATIC DRI... | $0 | $0 | Dec 14, 2017 |
| Aug 31, 2017 | 35290539J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED ON 8/31/17 AT ABOVE ADDRESS NO SPRINKLER GAUGE ON THE ... | $0 | $0 | Dec 14, 2017 |