ECB violations
159-161 Avenue B, Manhattan • Block 00393 • Lot 0001
128 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Dec 11, 2025 | 39170104J | ACTIVE | CLASS - 2 | CLASS 2: EMERGENCY PHONE INOPERATIVE, PROVIDE 2 WAY COMMUNICATION SERVICE. MISSING BRAILLE TAG FOR DOOR OPEN BUTTON, ... | $3,125 | $3,125 | Feb 19, 2026 |
| Dec 11, 2025 | 39170141Z | ACTIVE | CLASS - 2 | OBSERVED OUTSIDE IN THE STREET FIRE DEPARTMENT CONNECTION MISSING A CAP AND PAINTED GREEN WRONG COLOR WHEN THERE IS S... | $6,250 | $6,250 | Feb 19, 2026 |
| Dec 11, 2025 | 39170140R | ACTIVE | CLASS - 2 | OBSERVED ON THE FIRST FLOOR TWO GAS LINES AND GAS DRYERS INSTALLED AND COMPLETED 100 PERCENT WITH NO PERMITS ON FILE,... | $6,250 | $6,250 | Feb 19, 2026 |
| Dec 11, 2025 | 39170138H | ACTIVE | CLASS - 2 | OBSERVED IN BASEMENT SPRINKLER HEADS OBSTRUCTED AND BROKEN WASTE LINES. THE FIRST FLOOR BATHROOMS NO TRAP WRAP INSULA... | $6,250 | $6,250 | Feb 19, 2026 |
| Nov 18, 2025 | 39167376X | RESOLVE | CLASS - 2 | ALL CONDITIONS HAVE BEEN REMOVED; HOWEVER, NO CERTIFICATE OF CORRECTION IS ON FILE FOR VIOLATION #39140655Z ISSUED 3/... | $3,125 | $3,125 | Jan 22, 2026 |
| Nov 18, 2025 | 39167378J | ACTIVE | CLASS - 1 | AT TIME OF INSPECTION, I OBSERVED SEVERAL SPRINKLER HEADS PAINTED THROUGHOUT BASEMENT AS CITED IN ORIGINAL VIOLATION ... | $25,000 | $25,000 | Jan 22, 2026 |
| Nov 18, 2025 | 39167379L | ACTIVE | CLASS - 1 | AT THE TIME OF RE-HAZARDOUS INSPECTION, CONDITIONS REMAINED UNCORRECTED. OBSERVED UNPROTECTED HOLE PENETRATIONS AT TH... | $25,000 | $25,000 | Jan 22, 2026 |
| Nov 18, 2025 | 39167377H | ACTIVE | CLASS - 1 | FAILURE TO GROUND ELECTRICAL SYSTEM; GROUNDING ELECTRODE CONDUCTOR IN WATER-METER ROOM IS RUSTED THROUGH AND DISCONNE... | $25,000 | $0 | Jan 22, 2026 |
| Mar 6, 2025 | 39140658Y | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED SPRINKLER HEADS PAINTED THROUGHOUT BASEMENT LEVEL. AL... | $2,500 | $2,500 | Jun 12, 2025 |
| Mar 6, 2025 | 39140657M | ACTIVE | CLASS - 2 | OBSERVED IN LAUNDRY ROOM FLEX PIPING FOR GAS LINES TO DRYER. GAS LINESMUST BE HARD PIPE AND RIGID TO PREVENT LEAKAGE.... | $625 | $625 | Jun 12, 2025 |
| Mar 6, 2025 | 39140656K | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $2,500 | $0 | Jun 12, 2025 |
| Mar 6, 2025 | 39140655Z | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1 (2014 COD... | $2,500 | $0 | Jun 12, 2025 |
| Mar 4, 2025 | 39140301L | RESOLVE | CLASS - 2 | CLASS 2 ITEMS: IN-CAR EXHAUST FAN INOPERATIVE. REPLACE WORN CAR DOOR RETAINERS (GIBS). PROVIDE AN UPDATED MAINTENANCE... | $310 | $0 | May 8, 2025 |
| May 14, 2024 | 39114997J | RESOLVE | CLASS - 2 | UNLAWFUL ACTS: FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION# 39075202H ISSUED ON 12/... | $1,250 | $1,250 | Dec 17, 2024 |
| Mar 12, 2024 | 39108405X | ACTIVE | CLASS - 1 | CATEGORY 1 AND BRAKE MAINTENANCE TAGS EXPIRED. PROVIDE A UPDATED MAINTENANCE LOG. FIRE EXTINGUISHER NOT EXPIRATION TA... | $6,250 | $6,250 | Apr 10, 2025 |
| Feb 15, 2024 | 39106091N | RESOLVE | CLASS - 1 | UNLAWFUL ACTS: FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION#39075202H ISSUED ON 12/0... | $6,250 | $6,250 | Mar 20, 2025 |
| Dec 14, 2023 | 39101413Y | RESOLVE | CLASS - 1 | UNLAWFUL ACTS: FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION#039075202H ISSUED ON 12/... | $2,500 | $0 | Feb 22, 2024 |
| Dec 6, 2022 | 39075202H | RESOLVE | CLASS - 1 | OBSERVED: AT CELLAR LEVEL, STORAGE ROOM, CORRIDORS, UTILITIES ROOMS, SEVERAL OPENING DUE PIPE/ CABLES PENETRATION AND... | $2,500 | $0 | Sep 28, 2023 |
| Dec 6, 2022 | 39075200Y | ACTIVE | CLASS - 2 | OBSERVED IN BASEMENT/CELLAR ACTIVE WATER LEAK ON PUMP LOCATED IN BOILER ROOM. AS PER PC 102.3 INSTALLATIONS, BOTH EXI... | $3,125 | $3,125 | Jul 11, 2024 |
| Dec 6, 2022 | 39075201X | RESOLVE | CLASS - 1 | OBSERVED: CERTIFICATE OF OCCUPANCY # 103083/1993, INDICATED AT THE CELLAR LEVEL (BOILER, METER,COMPACTOR, LIFT, A.C, ... | $2,500 | $0 | Mar 14, 2024 |
| Nov 30, 2022 | 39074736H | ACTIVE | CLASS - 2 | AS PER ONE WEIL MCLAIN 688 HOT WATER HEATING BOILER. BOILER NOT REGISTERED AS PER DEPT. OF BUILDINGS RECORDS. APPLY F... | $625 | $0 | Feb 13, 2024 |
| Nov 30, 2022 | 39074749R | ACTIVE | CLASS - 2 | AS PER ONE AO SMITH, NATURAL GAS FIRED HW BOILER. MODEL NO. HW-670-300, ANSI NO. Z21. 13-2017; BOILER NOT REGISTERED.... | $625 | $0 | Feb 13, 2024 |
| May 31, 2022 | 35636544J | RESOLVE | CLASS - 2 | UNSAFE,UNSUITABLE ELECTRICAL EQUIPMENT IN USE.I OBSERVED ON EVERY FLOOR INCLUDING ROOF AND BASEMENT MULTIPLE EXIT,EME... | $2,000 | $0 | Sep 1, 2022 |
| May 31, 2022 | 35636543H | ACTIVE | CLASS - 1 | FAILURE TO GROUND ELECTRICAL SYSTEMS.I OBSERVED IN THE MAIN WATER METER ROOM THE GROUNDING ELECTRODE CONDUCTOR COMPLE... | $24,000 | $24,000 | Sep 1, 2022 |
| Jan 22, 2022 | 35644646K | RESOLVE | CLASS - 1 | UNLAWFUL ACTS.FAILURE TO COMPLY WITH COMMISSIONER'S ORDERS.RECORDS INDICATE NO APP WAS MADE TO CORRECT OR CERTIFY ECB... | $2,500 | $2,500 | Aug 25, 2022 |
| Dec 4, 2021 | 35634425H | ACTIVE | CLASS - 1 | UNLAWFUL ACTS FAILURE TO COMPLY WITH COMMISSIONER'S ORDERS.RECORDS INDICATE NO APP WAS MADE TO CORRECT OR CERTIFY ECB... | $2,500 | $2,500 | Jan 24, 2023 |
| Nov 20, 2021 | 35634369M | RESOLVE | CLASS - 1 | UNLAWFUL ACTS,FAILURE TO COMPLY W/AN ORDER OF THE COMMISSIONER. FAILURE TO CORRECT & CERTIFY SUMMONS#35361689K USE OF... | $2,500 | $2,500 | Jan 24, 2023 |
| Oct 14, 2021 | 35634219R | RESOLVE | CLASS - 1 | UNLAWFUL ACTS.FAILURE TO COMPLY W/AN ORDER OF THE COMMISSIONER.FAILURETO CORRECT & CERTIFY SUMMONS ECB#35415182M MISC... | $0 | $0 | Jan 13, 2022 |
| Sep 27, 2021 | 39048194N | ACTIVE | CLASS - 2 | I OBSERVED IN THE CORRIDOR OUTSIDE OF ROOM LABELED APT 13 A 3/4" CONDUIT UNSUPPORTED AS REQUIRED PER EC., PROPERLY SE... | $2,500 | $2,500 | Nov 18, 2021 |
| Sep 27, 2021 | 39048193L | ACTIVE | CLASS - 2 | I OBSERVED IN THE BOILER ROOM THE IMPROPER TERMINATION OF THE CONDUCTORS SUPPLYING POWER TO THE AQUASTAT ON THE HOT W... | $6,000 | $6,000 | Nov 18, 2021 |
| Sep 27, 2021 | 35592066M | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER.I OBSERVED GAS LEAK ON GAS PIPES TO BOILER.CONED CALLED&SHUT GAS VAL... | $3,125 | $3,125 | Jun 2, 2022 |
| Sep 15, 2021 | 39047477Z | RESOLVE | CLASS - 2 | BOILER ROOM CEILING NOY TOTALLY FIRE RATED.CORRECT VIOLATING CONDITION AND SUBMIT A CERTIFICATE OF CORRECTION. | $1,562 | $0 | Nov 4, 2021 |
| Aug 25, 2021 | 39046592J | ACTIVE | CLASS - 1 | DOOR LOCK MONITORING WAS INSTALLED AS MANDATED BY CODE 3.10.12. DOOR LOCK MONITORING IS WIRED AND POWERED UP ON THE C... | $1,250 | $0 | Oct 14, 2021 |
| Nov 30, 2020 | 35523869R | ACTIVE | CLASS - 1 | FAILURE TO COMPLY W/THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION #3537269L ISSUED ON 1/1//19 & TO FILE A C... | $6,250 | $6,250 | Jun 17, 2021 |
| Mar 2, 2020 | 39018714K | RESOLVE | CLASS - 1 | UPON INSPECTION DEVICE WAS FOUND TO BE OUT OF SERVICE. RESTORE TO SERVICE IMMEDIATELY AND CONTACT NYCDOB FOR A COMPLE... | $1,250 | $0 | Apr 16, 2020 |
| Feb 21, 2020 | 35517382Y | ACTIVE | CLASS - 1 | FAILURE TO COMPLY W/ THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION#35372690L ISSUED ON 1/18/19 AND TO FILE ... | $2,500 | $2,500 | Jul 1, 2021 |
| Jan 3, 2020 | 35513646K | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35372690L ISSUED ON 01/18/19 & TO FILE A C OF C PURSUAN... | $12,500 | $0 | Jan 14, 2021 |
| Dec 23, 2019 | 39014718J | ACTIVE | CLASS - 2 | 59/M/7 BRAKE TAG MISSING PROVIDE. MAINTENANCE LOG HAVE TO UPDATE PROVIDE, 99/M/7 ONE YEAR MISSING PROVIDE. | $625 | $0 | Jul 20, 2020 |
| Nov 23, 2019 | 35513134R | ACTIVE | CLASS - 1 | FAILURE TO COMPLY W/ THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION#35372690L ISSUED ON 1/18/19 AND TO FILE ... | $6,250 | $6,250 | Feb 4, 2021 |
| Oct 9, 2019 | 35427832N | ACTIVE | CLASS - 1 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35372690L ISSUED ON 12/03/18 & TO FILE A C OF C PURSUAN... | $6,250 | $6,250 | Jan 20, 2021 |
| Jul 30, 2019 | 35401356X | RESOLVE | CLASS - 1 | FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION#35372690L ISSUED ON 12/03/18 AND TO FIL... | $6,250 | $0 | Mar 12, 2020 |
| Jul 17, 2019 | 35423876R | RESOLVE | CLASS - 1 | AN UNLAWFUL ACT FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONERS FAILURE TO CORRECT AND CERTIFY SUMMOSN#S 3542368... | $0 | $0 | Mar 12, 2020 |
| May 31, 2019 | 35423687H | RESOLVE | CLASS - 1 | AN UNLAWFUL ACT.FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER.FAILURE TO CORRECT AND CERTIFY SUMMONS#35415182M.... | $0 | $0 | Mar 12, 2020 |
| May 18, 2019 | 35398718J | ACTIVE | CLASS - 1 | FAILURE TO COMPLY WITH THE COMMISSIONRS ORDER CONTAINED IN SUMMONS/ VIOLATION # 35372690L ISSUED ON 12/3/18 AND TO FI... | $2,500 | $2,500 | Sep 26, 2019 |
| Apr 15, 2019 | 39002125X | ACTIVE | CLASS - 2 | FOUND WEIL MCLAIN MODEL 688 OPERATING WITH DEFECTS. MISSING SPILL SWITCH. CORRECT ALL VIOLATING CONDITIONS AND SUBMIT... | $312 | $0 | Jul 25, 2019 |
| Apr 4, 2019 | 35415182M | RESOLVE | CLASS - 1 | EC110.11.FAILURE TO PROTECT AGAINST DETERIORATING AGENTS.OBSERVED IN ELECTRICAL METER ROOM EXTENSIVE CORROSION TO SER... | $0 | $0 | Jul 25, 2019 |
| Apr 4, 2019 | 35415181K | RESOLVE | CLASS - 2 | FAILURE TO SECURE/SUPPORT ELECTRICAL METALLIC TUBING (EMT)PROPERLY OBSERVED IN BASEMENT IN AC MECHANICAL ROOM #1 EMT ... | $0 | $0 | Jul 25, 2019 |
| Apr 4, 2019 | 35422400R | ACTIVE | CLASS - 2 | FAILURE TO PROVIDE EFFECTIVE ELECTRICAL CONTINUITY FOR METAL RACEWAYS ENCLOSURE/CABLE ARMOR.OBSERVED IN BASEMENT BOIL... | $6,000 | $6,000 | Jan 14, 2021 |
| Apr 4, 2019 | 35415179L | ACTIVE | CLASS - 2 | FAILURE TO PROVIDE GROUND FAULT CIRCUIT INTERRUPTER (GFCI) PROTECTION AS REQUIRED OBSERVED ON UPPER ROOFTOP DEFECTIVE... | $1,200 | $0 | Jul 25, 2019 |
| Apr 4, 2019 | 35415304L | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED ON 04/04/19 AT ABOVE ADDRESS NO SPRINKLER PROTECTION F... | $1,563 | $0 | Jul 25, 2019 |