Skip to content

ECB violations

108 Forsyth Street, Manhattan • Block 00418 • Lot 0036

32 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Jan 21, 2026 39174589P ACTIVE CLASS - 2 AO SMITH BOILER HAS SAFETY VALVE INCORRECTLY INSTALLED+ILLEGAL DRAFT INDUCER+INCORRECT CHIMNEY TERMINATION+INOPERABLE... $1,250 $1,250 May 14, 2026
Jan 21, 2026 39174590M ACTIVE CLASS - 2 AO SMITH HOT WATER BOILER DATE STAMPED 2023 IS INSTALLED+OPERATING IN THIS COMMERCIAL BUILDING WITHOUT A DOB PERMIT, ... $620 $0 May 14, 2026
Jan 20, 2026 39174424R RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED WATER HOSE FUNNELED INTO FLUTE PIPING. POTENTIAL HAZA... $2,500 $2,500 Oct 1, 2026
Jan 20, 2026 39174423P RESOLVE CLASS - 2 EXIT DOOR NOT SELF-CLOSING. OBSERVED EMERGENCY EXIT DOOR NOT SELF CLOSING. LOCATED ON GROUND FLOOR., REPAIR/REPLACE DOOR $312 $0 Apr 23, 2026
Jan 20, 2026 39174421L RESOLVE CLASS - 1 UNSAFE STORAGE OF COMBUSTIBLE MATERIAL AND EQUIPMENT. EXCESSIVE STORAGE IN MECHANICAL/UTILITIES ROOMS (PLYWOOD, ELECT... $2,500 $2,500 Mar 26, 2026
Jan 20, 2026 39174425Z RESOLVE CLASS - 1 FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY. SECUIRTY COMPUTER CHAIRS PROHIBITED IN HALLWAYS. GARBAGE BINS AND LA... $625 $0 Mar 26, 2026
Jan 20, 2026 39174422N RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED HOLE PENETRATIONS THROUGHOUT BASEMENT. PLASTIC COVERI... $2,500 $2,500 Oct 1, 2026
Aug 2, 2024 39120747H RESOLVE CLASS - 2 NO FIRE-STOPPING FOR HOLE PENETRATIONS ON WALLS AND CEILINGS LOCATED THROUGHOUT BUILDING AND ALL MECHANICAL ROOMS CEL... $625 $625 Mar 13, 2025
Aug 2, 2024 39120692J RESOLVE CLASS - 1 I OBSERVED IN THE BASEMENT AREA THE USE OF AN EXTENSION CORD FROM THE FIRE ALARM ATS ROOM TO SUPPLY POWER FOR REFRIGE... $1,600 $1,600 Mar 6, 2025
Aug 2, 2024 39120693L RESOLVE CLASS - 2 I OBSERVED IN THE UNLABELED 200 AMP SWITCH IN THE MAIN ELECTRICAL ROOM THE CROSSING OF THE LINE AND LOAD CONDUCTORS W... $400 $400 Mar 6, 2025
Aug 2, 2024 39120694N RESOLVE CLASS - 2 I OBSERVED ON THE ROOF IN THE A.C SWITCH NO EQUIPMENT GROUND CONDUCTOR INSTALLED AS REQUIRED FOR FIXED EQUIPMENT AND ... $400 $400 Mar 6, 2025
Aug 2, 2024 39120695P ACTIVE CLASS - 1 I OBSERVED IN THE HALLWAYS THROUGHOUT THE BUILDING THE RECEPTACLES NOT TAMPER RESISTANT/PROOF AS REQUIRED BY LL 39/20... $1,600 $1,600 Mar 6, 2025
Aug 2, 2024 39120742Z RESOLVE CLASS - 1 WOOD SHELVING FOR OVERHEAD STORAGE OF PIPES AND COSTRUCTION MATERIAL, SECURITY SEATING/CHAIRS IN EMERGENCY EXITS PATH... $1,250 $1,250 Mar 13, 2025
Aug 2, 2024 39120749L RESOLVE CLASS - 2 ILLEGAL HARDWARE INSTALLED ON DOORS THROUGHOUT BUILDING., PROVIDE LEGAL HARDWARE $312 $312 Mar 13, 2025
Aug 2, 2024 39120691H RESOLVE CLASS - 1 I OBSERVED IN THE MAIN ELECTRICAL ROOM FAILURE TO PROVIDE/ MAINTAIN ACCESS TO THE ELECTRICAL EQUIPMENT THE INSTALLATI... $0 $0 Mar 6, 2025
Aug 2, 2024 39120690X RESOLVE CLASS - 1 I OBSERVED IN THE MAIN ELECTRICAL ROOM IN THE CENTER 400 AMP DISCONNECT SWITCH THE IMPROPER FUSING OF THE CONDUCTORS,... $4,800 $4,800 Mar 6, 2025
Aug 2, 2024 39120696R RESOLVE CLASS - 1 I OBSERVED IN THE MAIN ELECTRICAL ROOM THE EXCESSIVE STORAGE OF CABINETS, LOCKERS, BUILDING MATERIALS AND EQUIPMENT. ... $1,200 $1,200 Mar 6, 2025
Aug 2, 2024 39120750Z RESOLVE CLASS - 2 WOOD DECKING INSTALLED OVER ENTIRE ROOF THAT HAS DETERIORATED AND DETACHED FROM ROOF CAUSING A TRIP HAZARD LOCATED RO... $0 $0 Mar 13, 2025
Aug 2, 2024 39120748J RESOLVE CLASS - 2 NO EMERGENCY LIGHTING FOR STAIRCASE A & B THROUGHOUT BIULDING., REPAIR AND/OR REPLACE LIGHTING $625 $625 Mar 13, 2025
Jul 30, 2024 39120272N RESOLVE CLASS - 1 OBSERVED EXCESSIVE STORAGE IN THE BOILER AND GAS METER ROOM. AS PER APPENDIX E 3 OF THE FCG GAS METER ROOMS, WHEN PRO... $312 $0 Jul 10, 2025
Jul 30, 2024 39120309H RESOLVE CLASS - 1 DOOR ZONE RESTRICTOR AND DOOR LOCK MONITORING INOPERATIVE. THIS IS A SAFETY FEATURE WHICH ENSURES PASSENGER SAFETY. R... $1,250 $1,250 Dec 26, 2024
Jan 16, 2008 38179862N RESOLVE Non-Hazardous 85M07,38O02,60M07,25D06.85-PROVIDE 5YR TEST TAG.38-REMOVE MATERIALS FROM CAR TOP.60-PROVIDE EMERGENCY PHONE # ON MAIN... $0 $0 Mar 13, 2008
Oct 25, 2000 34267029H RESOLVE Hazardous NO GUARD RAILS. NOTED:ELEVATOR SHAFT IN NEW BLDG. UNDER CONSTRUCTION HAS NO GUARD RAILS TO PROTECT WORKERS FROM FALLI... $0 $0 Dec 14, 2000
Jun 28, 1999 34217462N RESOLVE Non-Hazardous WORK WITHOUT A PERMIT NOTED ERECTED ARE APPROX 12 HIGH X 100 CHAIN LINT FENCE GATES MOVABLE WITH VENTICAL STEEL SUPPO... $2,500 $0 Aug 19, 1999
Sep 29, 1997 34161473Z RESOLVE Non-Hazardous WORK WITHOUT A PERMIT. NOTED:-ERECTED 12 FT, HIGH CHAIN LINK FENCE WITH STRUCTURAL STEEL OVERHEAD 40 FT. AT BROOME ST... $1,000 $0 Jan 15, 1998
Jul 9, 1994 34078868X RESOLVE Non-Hazardous FAILURE TO MAINTAIN. DEFECT IS: A SECTION OF THE CHAIN LINK FENCE(SOUTHERN MOST SECTION)IS BENT TOWARD THE PUBLIC SID... $1,000 $0 Aug 25, 1994
Jun 9, 1994 34110899X RESOLVE Non-Hazardous OCCUPANCY CONTRARY TO THAT ALLOWED BY BUILDING DEPT. RECORDS. FROM: VACANT LOT TO: PRIVATE PARKING LOT WITH LOT 7 CAR... $1,000 $0 Sep 1, 1994
Jun 9, 1994 34110898Y RESOLVE Non-Hazardous WORK WITHOUT A PERMIT. NOTED: ERECTED 12' HIGH CHAIN LINK FENCE 40' AT BROOME STREET SIDE AND 100' AT FORSYHTE STREET... $5,000 $0 Sep 1, 1994
Mar 26, 1993 34089291Y RESOLVE Non-Hazardous OCCUPANCY CONTRARY TO THAT ALLOWED BY THE BUILDING DEPARTMENT RECORDS.FROM 8 MULTIPLE DWELLING. TO:-PRIVATE PARKING L... $1,000 $0 Jun 3, 1993
Mar 26, 1993 34089290M RESOLVE Non-Hazardous WORK WITHOUT A PERMIT. WORK NOTED: -ERECTED APPROX 12FT. HIGH CHAIN LINK FENCE WITH STRUCTURAL STEEL OVERHEAD & GATE ... $1,000 $0 Jun 3, 1993
Sep 25, 1990 34047173H RESOLVE Non-Hazardous WORK WITHOUT A PERMIT. ERECTED 12 FOOT HIGH CHAIN LINK FENCE WITH STRUCTURAL STEEL OVERHEAD AT 40' AT BROOM STREET AN... $1,000 $0 Nov 29, 1990
Sep 25, 1990 34047301N RESOLVE Non-Hazardous OCCPUANCY CONTRARY TO THAT ALLOWED BY BUILDING DEPARTMENT RECORDS FROM MULTIDWELLING TO PRIVATE PARKING LOT. REMEDY: ... $1,000 $0 Nov 29, 1990