ECB violations
197 Bowery, Manhattan • Block 00425 • Lot 0008
52 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Jun 11, 2026 | 39192172Z | ACTIVE | CLASS - 1 | CLASS 1 C/U: FIREFIGHTER SERVICE PHASE I NOT OPERATING AS REQUIRED; KEY CANNOT BE REMOVED WHEN FIRE RECALL IS ACTIVAT... | $1,250 | $1,250 | Aug 20, 2026 |
| Jun 9, 2026 | 39191819X | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT TIME OF INSPECTION, OBSERVED THE FOLLOWING VIOLATING. .HOLE... | $6,250 | $6,250 | Oct 1, 2026 |
| Jun 9, 2026 | 39191824K | ACTIVE | CLASS - 1 | AT TIME OF INSPECTION GAS LEAK WAS OBSERVED IN THE BASMENT AS PER PC 102.3 . INSTALLATIONS, BOTH EXISTING AND NEW, AN... | $2,500 | $2,500 | Oct 1, 2026 |
| Jun 9, 2026 | 39191825M | ACTIVE | CLASS - 1 | AT TIME OF INSPECTION MISSING TRAP WRAPS AND OPEN ENDED TOILETS SEATS THROUGHOUT BUILDING 420.3 WATER CLOSET SEATS. W... | $2,500 | $2,500 | Oct 1, 2026 |
| Jan 8, 2026 | 39172990M | RESOLVE | CLASS - 2 | NO CERTIFICATE OF CORRECTION ON FILE FOR CLASS 1 VIOLATION #39101575R ISSUED 12/15/2023 FOR NONCOMPLIANCE RELATED TO ... | $1,250 | $1,250 | Oct 27, 2026 |
| Jan 8, 2026 | 39172993H | ACTIVE | CLASS - 2 | ACCESS GRANTED. NO CERTIFICATE OF CORRECTION ON FILE FOR CLASS 1 AGGRAVATED VIOLATION #39151201H ISSUED 6/16/2025. FI... | $1,250 | $1,250 | Oct 27, 2026 |
| Jan 8, 2026 | 39172992X | ACTIVE | CLASS - 2 | ACCESS GRANTED, NO CERTIFICATE OF CORRECTION ON FILE FOR CLASS 1 AGGRAVATED VIOLATION #39114531H ISSUED 5/16/2024. OB... | $1,250 | $1,250 | Oct 27, 2026 |
| Jan 8, 2026 | 39172991Y | ACTIVE | CLASS - 2 | ACCESS GRANTED. NO CERTIFICATE OF CORRECTION ON FILE FOR CLASS 1 VIOLATION #39151203L ISSUED 6/16/2025. ALTHOUGH THE ... | $1,250 | $1,250 | Oct 27, 2026 |
| Jan 8, 2026 | 39172989P | ACTIVE | CLASS - 2 | ACCESS GRANTED, NO CERTIFICATE OF CORRECTION ON FILE FOR CLASS 1 VIOLATION #39074772P ISSUED 11/30/2022. OBSERVED SAF... | $1,250 | $1,250 | Oct 27, 2026 |
| Jan 8, 2026 | 39172988N | RESOLVE | CLASS - 2 | NO CERTIFICATE OF CORRECTION ON FILE FOR CLASS 1 VIOLATION #39105724J ISSUED 2/6/2024 FOR NONCOMPLIANCE RELATED TO OR... | $1,250 | $1,250 | Oct 27, 2026 |
| Jul 23, 2025 | 39154718Y | RESOLVE | CLASS - 1 | CEASE USE ITEM: IN-CAR ALARM AND COMMUNICATION ARE INOPERATIVE. . REMEDY: TO RESTORE SERVICE, EMAIL THE D.O.B. EIR@BU... | $1,250 | $0 | Apr 13, 2026 |
| Jun 16, 2025 | 39151203L | ACTIVE | CLASS - 1 | UNSAFE STORAGE OF COMBUSTIBLE MATERIAL AND EQUIPMENT. OBSERVED EXCESSIVE STORAGE UNDERNEATH STAIRCASE. LOCATED IN STO... | $2,530 | $2,530 | Jul 16, 2026 |
| Jun 16, 2025 | 39151201H | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $2,530 | $2,530 | Jul 16, 2026 |
| Jun 16, 2025 | 39151202J | ACTIVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING. OBSERVED NON SELF CLOSING DOORS IN RPZ ROOM ON FIRST FLOOR AND GAS METER ROOM AT BASEMENT... | $655 | $655 | Jul 16, 2026 |
| Jun 13, 2025 | 39150987Y | ACTIVE | CLASS - 2 | CLASS 2 ITEMS: DOOR OPERATOR COVER MISSING, PROVIDE. IN CAR 4 FLOOR BUTTON LIGHT INOPERATIVE, REPAIR. PIT DIRTY, CLEA... | $655 | $655 | Jul 16, 2026 |
| May 16, 2024 | 39114514X | RESOLVE | CLASS - 1 | UNLAWFUL ACTS: FAILURE TO COMPLY WITH COMMISSIONER'S ORDER AS STATED IN ECB# 39074771N ISSUED ON 11/30/2022 AND FILE ... | $6,250 | $4,985 | Jun 5, 2025 |
| May 16, 2024 | 39114530X | ACTIVE | CLASS - 2 | I OBSERVED THROUGHOUT THE ENTIRE FIRST FLOOR THE INSTALLATION OF NEW LIGHTS CONDUITS AND RACEWAYS TO SUPPLY POWER TO ... | $4,000 | $4,000 | Aug 22, 2024 |
| May 16, 2024 | 39114531H | ACTIVE | CLASS - 1 | I OBSERVED IN THE ROOFTOP GENERATOR ROOM THE GENERATOR STILL IN A STATE OF DISREPAIR AND NOT IN USE AS REQUIRED FOR A... | $16,000 | $16,000 | Jun 5, 2025 |
| May 16, 2024 | 39114528R | RESOLVE | CLASS - 1 | UNLAWFUL ACTS: FAILURE TO COMPLY WITH COMMISSIONERS ORDER AS STATED IN ECB# 39074772P AND FILE A CERTIFICATE OF CORRE... | $6,250 | $6,250 | Jun 5, 2025 |
| May 16, 2024 | 39114529Z | ACTIVE | CLASS - 2 | I OBSERVED IN THE BASEMENT AREA THE UNPERMITTED STORAGE BENEATH THE ATS EQUIPMENT OF FURNITURE AND BUILDING EQUIPMENT... | $2,500 | $2,500 | Jun 5, 2025 |
| Mar 26, 2024 | 39109907K | RESOLVE | CLASS - 2 | TENANT PROTECTION PLAN WAS NOT POSTED AND DISTRIBUTED AS REQUIRED BY BUILDING CODE (JOB NO.141024718)., POST/DISTR. N... | $1,250 | $0 | May 30, 2024 |
| Feb 9, 2024 | 39105728R | RESOLVE | CLASS - 1 | FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION# 39074772P ISSUED ON 11/30/22 AND TO FI... | $2,500 | $0 | Apr 18, 2024 |
| Feb 6, 2024 | 39105724J | ACTIVE | CLASS - 1 | FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION# 39074771N ISSUED ON 11/30/22 AND TO FI... | $2,500 | $0 | Apr 18, 2024 |
| Dec 15, 2023 | 39101575R | RESOLVE | CLASS - 1 | UNLAWFUL ACTS: FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION#39074771N ISSUED ON 11/3... | $2,530 | $0 | Feb 22, 2024 |
| Dec 15, 2023 | 39101576Z | RESOLVE | CLASS - 1 | UNLAWFUL ACTS: FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION#39074772P ISSUED ON 11/3... | $2,530 | $0 | Feb 22, 2024 |
| Jul 12, 2023 | 39090067J | RESOLVE | CLASS - 2 | ALARM BELL NOT WORKING, TOP OF CAR LIGHT BROKEN;REPAIR; CLEAN TOP OF CAR,CLEAN PIT, PIT DIRTY, MISSING CAT 1 AND CAT ... | $312 | $0 | Oct 19, 2023 |
| Nov 30, 2022 | 39074763N | RESOLVE | CLASS - 2 | OBSERVED: AT ROOF LEVEL GENERATOR ROOM & FIRE PUMP ROOM, AT CELLAR LEVEL, BOILER ROOM, ELECTRICAL ROOM AND SPRINKLER ... | $312 | $0 | Feb 9, 2023 |
| Nov 30, 2022 | 39074772P | ACTIVE | CLASS - 1 | I OBSERVED ON THE ROOFTOP LEVEL THE GENERATOR DEFECTIVE AND INOPERABLE. THE SAFETY SYSTEM SHALL BE MAINTAIN AND IN OP... | $1,600 | $0 | Mar 9, 2023 |
| Nov 30, 2022 | 39074770L | RESOLVE | CLASS - 2 | I OBSERVED ON THE UPPER FLOORS THE INSTALLATION OF THE MOTION SENSOR CONTROLS FOR THE HALLWAY LIGHTS THE JUNCTION BOX... | $400 | $0 | Feb 9, 2023 |
| Nov 30, 2022 | 39074764P | RESOLVE | CLASS - 1 | OBSERVED: AT FIRST FL EXIT CORRIDOR FROM CAFETERIA TO EXP #1, AT CELLAR LEVEL EXIT PASSAGEWAY ARE BEING OBSTRUCTED FO... | $1,250 | $0 | Feb 9, 2023 |
| Nov 30, 2022 | 39074771N | RESOLVE | CLASS - 1 | I OBSERVED IN THE ELECTRICAL ROOM THE DETAIL END BOX IN A STATE OF SEVERE CORROSION, THE CONDUIT AND FITTINGS SUPPLYI... | $1,600 | $0 | Mar 9, 2023 |
| Apr 7, 2022 | 39059824M | ACTIVE | CLASS - 2 | I OBSERVED AN ACTIVE LEAK ON A DEFECTIVE HOT WATER STORAGE TANK IN THE BOILER ROOM THAT IS LOCATED IN THE BASEMENT/CE... | $625 | $0 | Sep 1, 2022 |
| Nov 23, 2021 | 39051616L | RESOLVE | CLASS - 2 | NOTED: ROOFING MATERIAL OF SMALL PATIO HAS BECOME POROUS, ALLOWING WATER TO PENETRATE INTO THE 6TH. FLOOR LOUNGE ROOM... | $625 | $0 | May 12, 2022 |
| Apr 1, 2021 | 37021226X | RESOLVE | CLASS - 2 | FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 8A REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WA... | $3,125 | $0 | Apr 14, 2022 |
| Mar 17, 2020 | 39019874Y | RESOLVE | CLASS - 1 | IMPROPER FUSING ON THE CONTROLLER. HOLLISTER WHITNEY ELECTRICAL BRAKE MONITORING NOT WORKING . CLEAN THE PIT. | $1,280 | $0 | Apr 15, 2021 |
| Sep 9, 2019 | 39009143L | RESOLVE | CLASS - 2 | I OBSERVED TEMPORARY WIRING IN USE FEEDING OUTSIDE CONSTRUCTION. THE TEMPORARY WIRING IS CONNECTED TO THE SERVICE EQU... | $2,000 | -$2,000 | Oct 24, 2019 |
| Sep 9, 2019 | 39009142J | ACTIVE | CLASS - 2 | I OBSERVED IN THE CELLAR THE GROUNDING ELECTRODE CONDUCTOR WATER CLAMP DETERIORATED TO THE POINT OF DISREPAIR, I OBSE... | $4,000 | $0 | Oct 24, 2019 |
| Sep 6, 2018 | 35360587P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER. OBSERVED IN THE CELLAR A BALL VALVE INSTALLED ON THE PIPING ... | $0 | $0 | Nov 8, 2018 |
| May 18, 2018 | 37010223R | RESOLVE | CLASS - 2 | FAILURE TO SUBMIT ACCEPTABLE 8TH ROUND REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALLS & APPUR... | $1,250 | $0 | Aug 30, 2018 |
| Feb 2, 2018 | 35265130J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN EXTERIOR BLDG GENERAL NOTE:(EIF)-VERTICAL &HORIZONTAL CRACKS @VARIOUS LOCNS WEST ELEV.EXP#1 2FL S... | $500 | $0 | May 24, 2018 |
| Nov 22, 2017 | 35297186P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED ON 11/22/17 AT ABOVE ADDRESS (BD)NO FRESH AIR INTAKE I... | $0 | $0 | Jan 18, 2018 |
| Nov 22, 2017 | 35297185N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED ON 11/22/17 AT ABOVE ADDRESS SPRINKLER MAIN THROUGHOUT... | $0 | $0 | Jan 18, 2018 |
| Jul 12, 2016 | 35200750N | RESOLVE | CLASS - 2 | FAILURE TO PAINT DEDICATED SPRINKLER PIPING IN ACCORDANCE W/SECTION. NOTED: SPRINKLER MAIN,CROSS CONNECTIONS & RISERS... | $800 | $0 | Sep 8, 2016 |
| Jun 16, 2015 | 38236343J | RESOLVE | CLASS - 2 | 02B10,01B10. 02B10-ALARM BELL NOT WORKING REPAIR; 01B10-ALARM BELL ON STOP SWITCH NOT WORKING REPAIR. | $0 | $0 | Aug 6, 2015 |
| Mar 4, 2008 | 34611125H | RESOLVE | Hazardous | SEC. 27-3018B. FAILURE TO POST PERMITS: AT FRONT OF PREMISES ERECTED SIDEWALK SHED W/LIGHTING INSTALLED ON SHED. NO P... | $130 | $0 | Apr 24, 2008 |
| Aug 30, 2007 | 34579881X | RESOLVE | Non-Hazardous | SEC. 27-1014(A). FAILURE TO PROVIDE AN ELEVATOR IN READINESS. NOTED: NO FUNCTIONING ELEVATOR IN BLDG FOR FIREFIGHTING... | $800 | $0 | Apr 17, 2008 |
| Aug 30, 2007 | 34579882H | RESOLVE | Non-Hazardous | SEC. 27-1014 (B)(1). FAILURE TO PROVIDE A FUNCTIONING STANDPIPE. NOTED: NO FUNCTIONING STANDPIPE TO COVER THE ENTIRE ... | $800 | $0 | Apr 17, 2008 |
| Sep 15, 2005 | 34490094X | RESOLVE | Non-Hazardous | QUESTIONABLE CONSTRUCTION PRACTICES. AT 2ND FL CENTER EXISTING BATHROOM WALL ADJACENT TO NEWLY ENLARGED STAIR SHAFTWA... | $0 | $0 | Nov 3, 2005 |
| Aug 2, 2005 | 34484169K | RESOLVE | Non-Hazardous | FAILURE TO SAFELY AND PROPERLY REMOVE MATERIAL AND DEBRIS FROM CONSTRUCTION SITE-IN THAT ROOF IS BEING OVERLOADED WIT... | $500 | $0 | Sep 22, 2005 |
| Oct 22, 2003 | 34401408M | RESOLVE | Hazardous | PLUMBING WORK W/O A PERMIT.NEW INSTALLATION OF NO HUB CAST IRON PIPING USED FOR LAVATORY ON BATHROOM IN BACK.ALSO NEW... | $1,000 | $0 | Dec 11, 2003 |