Issued Violation Status Severity Description Penalty Balance due Hearing
Nov 13, 2012 32072628R ACTIVE CLASS - 2 B254,16,32A,48A,36. 36- DOB RECORDS INDICATE A FAILED FIRST TEST IN 2011.; NO RECORD OF SUBSEQUENT TEST. OPERATING (X... $250 -$250 Jan 3, 2013
Dec 5, 2007 32055173P RESOLVE Hazardous 50A,B. 50A CARBON MONOXIDE SPILLAGE FROM DRAFT HOOD AREA LEVELS OF 3550 PPM READ DANGEROUS LEVELS MUST REPAIR IMMEDIA... $400 $0 Oct 16, 2008
Dec 5, 2007 32055171L RESOLVE Hazardous 50A,B,C,51,48B,18B. 50A CARBON MONOXIDE SPILLAGE FROM DRAFT REGULATOR LEVELS OF 350 PPM READ 50B REPOSITION FLUE PIPE... $400 $0 Oct 16, 2008
Dec 5, 2007 32055172N RESOLVE Hazardous 50A,B,C,48B,51. 50A CARBON MONOXIDE SPILLAGE FROM DRAFT REGULATOR LEVELS OF 275 PPM READ 50B INSTALL SLOW OPENING VAL... $400 $0 Oct 16, 2008
Jun 20, 2006 32050121K RESOLVE Non-Hazardous 18B/50 48AB FULTON V.T. BOILER,15HP, NB64481,GAS,1992 50 WATER COLUMN DRAIN VALVE CORRODED AND LEAKING. 18B)SCALE ACC... $0 $0 Aug 10, 2006
Jun 20, 2006 32050122M RESOLVE Non-Hazardous 18B FULTON V.T. BOILER,10HP, NB 86880,GAS 2000 18B SCALE ACCUMULATION AND LEAKAGE AT HAND HOLES. RE-GASKET OPENINGS. $0 $0 Aug 10, 2006
Jun 16, 2004 32044742M RESOLVE Non-Hazardous FULTON/48AB/50A FULTON V.T BOILER 15HP NB64481 GAS FILES 1992 50(A)SCREW THREADS FOUND AT THE OULET END OF THE SAFTEY... $180 $0 Nov 4, 2004
Jun 16, 2004 32044741K RESOLVE Non-Hazardous 50 FULTON V.T BOILER 15HP NB86880 GAS FIRED 2000 50 SCREW THREADS FOUND AT THE OUTLET END OF THE SAFTEY VALVE DISCHAR... $0 $0 Nov 18, 2004