ECB violations
331-333 Bowery, Manhattan • Block 00458 • Lot 0004
60 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Dec 16, 2025 | 39170660K | ACTIVE | CLASS - 2 | OBSERVED ON THE THIRD FLOOR IN STAIRCASE A SPRINKLER HEAD IS DAMAGED AND ON THE FIRST FLOOR SPRINKLER HEAD CAP IS PAI... | $1,250 | $0 | Dec 24, 2025 |
| Dec 16, 2025 | 39170661M | ACTIVE | CLASS - 2 | ON 5TH FLOOR INSTALLED NEW PIPING FOR SHOWER AND SINKS IN BATHROOM 95 PERCENT WORK COMPLETED NO PLUMBING PERMIT ON FI... | $1,250 | $0 | Dec 24, 2025 |
| Mar 13, 2025 | 39141472K | ACTIVE | CLASS - 1 | UNSAFE STORAGE OF COMBUSTIBLE MATERIAL AND EQUIPMENT. OBSERVED FLAMMABLE CONTAINERS IN FIRE PUMP ROOM. (CAR ANTI FREE... | $2,500 | $0 | Mar 25, 2025 |
| Mar 13, 2025 | 39141475X | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED BENT SPRINKLER HEAD AT 3RD FLOOR STAIRWELL LANDING. P... | $1,250 | $0 | Mar 25, 2025 |
| Mar 13, 2025 | 39141473M | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $2,500 | $0 | Mar 25, 2025 |
| Mar 13, 2025 | 39141476H | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1 (2014 COD... | $2,500 | $0 | Mar 25, 2025 |
| Mar 13, 2025 | 39141474Y | ACTIVE | CLASS - 1 | FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY. OBSERVED PUMP ROOM OBSTRUCTED WITH CONSTRUCTION MATERIAL AND PIPES A... | $1,250 | $0 | Mar 18, 2025 |
| May 15, 2024 | 39114410L | ACTIVE | CLASS - 1 | FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION# 39074958P ISSUED ON 11/30/2022 AND TO ... | $2,500 | $0 | Jul 9, 2024 |
| May 15, 2024 | 39114407K | ACTIVE | CLASS - 1 | FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION# 39074958N ISSUED ON 11/30/2022 AND TO ... | $2,500 | $0 | May 30, 2024 |
| May 15, 2024 | 39114411N | ACTIVE | CLASS - 1 | FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION #39074955H ISSUED ON 11/30/2022 AND TO ... | $2,500 | $0 | May 30, 2024 |
| Mar 27, 2024 | 39110101J | ACTIVE | CLASS - 2 | OBSERVED IN THE BOILER ROOM LOCATED IN THE BASEMENT/CELLAR ACTIVE LEAK ON PIPING FROM TEMP BOILER. AS PER 102.3 OF TH... | $625 | $0 | May 29, 2024 |
| Mar 27, 2024 | 39110100H | ACTIVE | CLASS - 2 | OBSERVED IN THE BASEMENT/CELLAR JIM CAPS INSTALLED ON CAST IRON FITTINGS., REPAIR AND/OR REPLACE | $625 | $0 | May 29, 2024 |
| Dec 15, 2023 | 39101589H | ACTIVE | CLASS - 1 | UNLAWFUL ACTS: FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION#39074958N ISSUED ON 11/3... | $2,500 | $0 | Jan 2, 2024 |
| Dec 15, 2023 | 39101596X | ACTIVE | CLASS - 1 | UNLAWFUL ACTS: FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION #39074959P ISSUED ON 11/... | $2,500 | $0 | Jan 2, 2024 |
| Dec 15, 2023 | 39101586M | ACTIVE | CLASS - 1 | UNLAWFUL ACTS: FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION#39074955H ISSUED ON 11/3... | $2,500 | $0 | Jan 2, 2024 |
| Dec 2, 2022 | 39074975P | ACTIVE | CLASS - 2 | AS PER ONE NATURAL GAS BURNHAM BOILER, YEAR BUILT 2006. SERIAL NO. 64938167; BOILER NOT REGISTERED. APPLY FOR PROPER ... | $625 | $0 | Dec 6, 2022 |
| Dec 2, 2022 | 39074974N | ACTIVE | CLASS - 2 | AS PER ONE NATURAL GAS, BURNHAM CAST IRON BOILER, YEAR BUILT 2015, SERIAL NO. 65539938; BOILER NOT REGISTERED. APPLY ... | $625 | $0 | Dec 6, 2022 |
| Dec 2, 2022 | 39074976R | ACTIVE | CLASS - 2 | AS PER ONE AO SMITH DOMESTIC HOT WATER BOILER, YEAR BUILT 2014, SERIAL NO. 1433M001233. BOILER NOT REGISTERED. APPLY ... | $625 | $0 | Dec 6, 2022 |
| Nov 30, 2022 | 39074960M | ACTIVE | CLASS - 2 | AT FIRST FLOOR, MECHANICAL ROOM, ACTIVE WATER FILTRATION FROM THE ROOF TO THE INTERIOR OF THE MECHANICAL ROOM., REPAI... | $625 | $0 | Dec 6, 2022 |
| Nov 30, 2022 | 39074955H | ACTIVE | CLASS - 1 | OBSERVED: AT EXPOSURE # 3, BACK YARD, DISCHARD FIRE SCAPE IS BEING OBSTRUCTED BY MATERIALS STORED. ALSO, AT FIRST FL,... | $1,250 | $0 | Dec 8, 2022 |
| Nov 30, 2022 | 39074956J | ACTIVE | CLASS - 2 | OBSERVED: AT FIRST FLOOR, MECHANICAL ROOM, WOODEN STRUCTURE THAT SUPPORTS THE ROOF OF THE MECHANICAL ROOM, IS BEING P... | $625 | $0 | Dec 6, 2022 |
| Nov 30, 2022 | 39074957L | ACTIVE | CLASS - 2 | OBSERVED: AT CELLAR LEVEL, FIRE PROOF WALLS & CEILING SHOWS SEVERAL HOLES, OPENINGS DUE TO CEILING DAMAGE OR PIPE PEN... | $3,125 | $0 | Dec 6, 2022 |
| Nov 30, 2022 | 39074958N | ACTIVE | CLASS - 1 | OBSERVED: AT FIRST FLOOR, MECHANICAL ROOM, WOODEN STRUCTURE THAT SUPPORTS THE ROOF OF THE MECHANICAL ROOM, IS BEING P... | $2,500 | $0 | Dec 6, 2022 |
| Nov 30, 2022 | 39074959P | ACTIVE | CLASS - 1 | OBSERVED: AT FIRST FL, MECHANICAL ROOM, FLAMMABLE MATERIAL IS BEING STORED. ALSO, WOODEN STRUCTURE THAT SUPPORTS THE ... | $1,250 | $0 | Dec 6, 2022 |
| Apr 7, 2022 | 35650619X | ACTIVE | CLASS - 2 | OCCUPANCY CONTRARY TO THAT ALLOWED BY CERTIFICATE OF OCCUPANCY OR BUILDING DEPT RECORDS.OBSERVED CERTIFICATE OF OCCUP... | $1,250 | $0 | Jul 21, 2022 |
| Apr 7, 2022 | 35650620N | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:OBSERVED:AT 1ST FL,MECHANICAL ROOM,EXPOSED WOOD CEILING W/O FIR... | $625 | $0 | Jul 21, 2022 |
| Oct 4, 2021 | 39048680Z | ACTIVE | CLASS - 2 | NOTED: OBSERVED AT CELLAR'S, GENERATOR/FIRE PUMP ROOM, FIREPROOF CEILING TILES ARE MISSING AT VARIOUS LOCATIONS EXPOS... | $3,125 | $0 | Oct 15, 2021 |
| Oct 4, 2021 | 39048679L | ACTIVE | CLASS - 2 | NOTED: OBSERVED AT FIRST FLOOR LEVEL (REAR) MECHANICAL ROOM, 6"X6" WOODEN VERTICAL POST THAT SUPPORTS THE CEILING IS ... | $1,562 | $0 | Oct 15, 2021 |
| Sep 21, 2021 | 39047820R | RESOLVE | CLASS - 2 | MOBILE BOILER MD165446-01 ON STREET IN FRONT OF AND SERVICING 333 BOWERY MN/HW GAUGE BOILER FRONT LEAKING/SAFETY VALV... | $1,562 | $0 | Sep 22, 2022 |
| Sep 25, 2019 | 39010119J | ACTIVE | CLASS - 2 | NOTE: OBSERVED AT FIRST FLOOR MECHANICAL ROOM, 6"X6" WOODEN SUPPORT MEMBERS THAT SUPPORT THE CEILING HAVE SHIFTED AND... | $0 | $0 | Oct 4, 2019 |
| Sep 25, 2019 | 39010120R | ACTIVE | CLASS - 2 | NOTED: OBSERVED AT FIRE PUMP/GENERATOR ROOM AT CELLAR, FIREPROOF CEILING TILES ARE MISSING THROUGHOUT ROOM AND EXPOSI... | $0 | $0 | Oct 4, 2019 |
| Sep 25, 2018 | 35361386N | RESOLVE | CLASS - 1 | UNSAFE STORAGE OF COMBUSTIBLE MATERIAL AND EQUIPMENT. NOTED:AT CELLAR,IN STORAGE ROOM OBSERVED A GAS POWERED WEEK WAC... | $0 | $0 | Nov 29, 2018 |
| Sep 25, 2018 | 35361385L | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:NO FIRE STOPPINGPER BC 712.3;27-345. NOTED:AT CELLAR, IN FIRE P... | $0 | $0 | Nov 29, 2018 |
| Sep 25, 2018 | 35361383H | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: AT 1ST STORY IN MECHANICAL ROOM, WATER PENETRATING CEIL... | $0 | $0 | Nov 29, 2018 |
| Sep 25, 2018 | 35361384J | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY. NOTED:AT 1ST STORY CORRIDOR, OUTSIDE MECHANICAL ROOM, CORRIDOR OBSTR... | $0 | $0 | Nov 29, 2018 |
| Sep 25, 2018 | 35361829N | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED ON 9/25/18 AT ABOVE ADDRESS GAS LEAK ON DRESSER COUPL... | $0 | $0 | Nov 29, 2018 |
| Mar 8, 2018 | 35322072Z | ACTIVE | CLASS - 2 | WORK W/OUT A PERMIT.OBSERVED ON THE UPPERMOST FL IN THE STIRWELL WHERETHE INSP TEST(VALVE)IS INSTALLED A PRESSURE GUA... | $0 | $0 | May 17, 2018 |
| Mar 8, 2018 | 35322073K | ACTIVE | CLASS - 1 | FAILURE TO HAVE NEW OR ALTERED PLUMBING SYSTEM TESTED.OBSERVED A PRESSURE GAUGE INSTALLED @THE UPPERMOST PART OF THE ... | $0 | $0 | May 17, 2018 |
| Mar 8, 2018 | 35312924K | RESOLVE | CLASS - 1 | UNLAWFUL ACTS, FAILURE TO COMPLY W/ AN ORDER OF THE COMMISSIONER. IN 1/10/2018 A ELECTRICAL VIOLATION WAS ISSUE TO TH... | $0 | $0 | May 3, 2018 |
| Mar 8, 2018 | 35317573K | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NO FIRE STOPPINGPER BC 712.3;27-345.NOTED:OBSERVED AT CELLAR-WI... | $0 | $0 | May 31, 2018 |
| Mar 8, 2018 | 35317574M | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:OBSERVED AT FIRST FLOOR MECHANICAL ROOM,6INCH X 6INCH POS... | $0 | $0 | May 31, 2018 |
| Jan 10, 2018 | 35312601X | RESOLVE | CLASS - 1 | UNLAWFUL ACTS. FAILURE TO COMPLY W/AN ORDER OF THE COMMISSIONER. IN AUGUST 31,2017 AN ELECTRICAL VIOLATION WAS ISSUED... | $0 | $0 | Mar 8, 2018 |
| Aug 31, 2017 | 35290311N | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER.OBSERVED @TOP OF STAIRWELL INSP TEST W/NO PRESSURE GAUGE INSTALLED ... | $0 | $0 | Dec 21, 2017 |
| Aug 31, 2017 | 35290653N | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER:NOTED.FIRE STOP MISSING IN THE FIRE PUMP ROOM THRU OUT ROOM HOLE IN... | $0 | $0 | Dec 21, 2017 |
| Aug 31, 2017 | 35290296Y | RESOLVE | CLASS - 1 | ELECTRICAL WORK WITHOUT A PERMIT.OBSERVED ON SECOND FLOOR ROOF(EXIT C2):THE ELECTRICAL,INSTALLATION OF POWER FEEDERS,... | $0 | $0 | Dec 14, 2017 |
| Jul 19, 2016 | 35200982M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG CODE COMPLIANT: LACK OF EMERGENCY LIGHTING PER BC1006.1; 27-542. NOTED: @ 1ST & 3RD FLR STAI... | $0 | $0 | Sep 15, 2016 |
| Jul 19, 2016 | 35200981K | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF CLOSING. NOTED: 1ST FLR REAR EXIT DOOR HAS A BROKEN DOOR CLOSER & REMAINS OPEN AFTER USE. REM: COM... | $0 | $0 | Sep 15, 2016 |
| Jul 19, 2016 | 35200983Y | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG CODE COMPLIANT: NO FIRE STOPPING PER BC 712.3; 27-345. NOTED: @ CELLAR BOILER ROOM, APPROX 3... | $0 | $0 | Sep 15, 2016 |
| Jun 17, 2016 | 35181049Y | ACTIVE | CLASS - 1 | WORK W/O PERMIT ON SANDPIPE TIME OF INSPECTION 1:15PM. AT TIME OF INSPECTION I OBSERVED DISCONNECTED AND CAPPED FIRE ... | $0 | $0 | Sep 15, 2016 |
| May 18, 2004 | 34430102M | RESOLVE | Non-Hazardous | WORK WIHTOUT A PERMIT EXPIRED PERMIT UPON INSPECTION AT THE ABOVE PROPERTY ALT PERMIT#103760921 EXPIRED 4/28/04 APPRO... | $0 | $0 | Jul 15, 2004 |