ECB violations
100-124 West 11 Street, Manhattan • Block 00606 • Lot 0049
59 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Jun 29, 2026 | 35734507J | ACTIVE | CLASS - 2 | REISSUE ECB#35720614H FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED INSUFFICIENT LIGHTING AT CELLAR OIL... | $3,125 | $0 | Jul 27, 2026 |
| Jun 29, 2026 | 35734508L | ACTIVE | CLASS - 2 | REISSUE ECB#35720612Y FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.EXIT DOOR NOT SELF CLOSING.NOTED RUSTY AN... | $1,562 | $0 | Jul 27, 2026 |
| Jul 15, 2025 | 35720612Y | ACTIVE | CLASS - 2 | RE-ISSUE #35682920L. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: THE EXTERIOR DOORS AT EXIT 3 AND 4... | $3,125 | $0 | Aug 27, 2025 |
| Jul 15, 2025 | 35720613X | RESOLVE | CLASS - 2 | RE-ISSUE #35682919Y. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: EXIT SIGNS LOCATED THROUGH-OUT THE... | $3,125 | $0 | Aug 27, 2025 |
| Jul 15, 2025 | 35720614H | ACTIVE | CLASS - 2 | RE-ISSUE #35682918M. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: THE OIL TANK ROOM, LOCATED AT CELL... | $3,125 | $0 | Aug 27, 2025 |
| Aug 29, 2024 | 35682920L | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.EXTERIOR DOORS EXIT 3 & 4 HARD TO OPEN AND CLOSE,DOOR FRAME RUS... | $625 | $0 | Nov 7, 2024 |
| Aug 29, 2024 | 35682919Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.EXIT SIGN ORIGINAL MODEL REGULAR MINI BULBS,ALL UNIT ARE NON BA... | $625 | $0 | Nov 7, 2024 |
| Aug 29, 2024 | 35682918M | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.OIL TANK ROOM CELLAR LEVEL,LIGHTS NOT WORKING IN ROOM ONLY ONE ... | $625 | $0 | Nov 7, 2024 |
| Mar 20, 2023 | 35672352N | RESOLVE | CLASS - 2 | REISSUE #35643568J.FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.ILLUMINATION FOR EXITS,EXIT DISCHARGES & PUB... | $625 | $0 | Jun 15, 2023 |
| Mar 20, 2023 | 35672351L | RESOLVE | CLASS - 2 | REISSUE #35643569L EXIT DOOR NOT SELF CLSING.AT TIME OF INSPECTION OBSERVED AT 4THFL STAIRWAY "B" EXIT DOOR AT 3RD FL... | $1,562 | $0 | Jun 15, 2023 |
| May 4, 2022 | 35643568J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER ILLUMINATION FOR EXITS EXIT DISCHARGES & PUBLIC CORRIDORS PER B... | $625 | $0 | Sep 1, 2022 |
| May 4, 2022 | 35643569L | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF CLOSING PROPERLY AT TIME OF INSPECTION AT 4TH FL STAIRWAY "B" 1 EXIT DOOR AT 3RD FL AT STAIRWAY "A... | $625 | $0 | Sep 1, 2022 |
| Apr 15, 2020 | 35490939P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUIDLING IN CODE COMPLIANT MANNER LOCK OF EMERGNECY LIGHTING FOR EXITS EXIT DISCHARGES AND PUBLIC... | $1,250 | $0 | Jun 4, 2020 |
| Apr 15, 2020 | 35490938N | RESOLVE | CLASS - 2 | EXIT DORO NOT SELF CLSOING NOTED A ROOF LEVEL STAIRCASE B EXIT DOOR AND 2ND FLOOR STAIRCASE A EXIT DOOR NOT LCOSING P... | $625 | $0 | Aug 13, 2020 |
| Apr 4, 2019 | 35415355L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER: ILLUMINATION FOR EXITS, EXIT DISCHARGERS AND PUBLIC CORRIDORS ... | $0 | $0 | Jun 27, 2019 |
| Apr 4, 2019 | 35415356N | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING. NOTED: MAIN ENTRANCE EXIT #2 THE DOOR IS NOT CLOSING PROPERLY, THE DOOR IS JAMMING ON THE... | $0 | $0 | Jun 27, 2019 |
| Feb 26, 2018 | 35321640N | RESOLVE | CLASS - 2 | REISSUE NOV 35234875M FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: SMOKE DOORS ON 3RD FL,ADJACENT TO ROO... | $0 | $0 | May 3, 2018 |
| Feb 26, 2018 | 35321641P | RESOLVE | CLASS - 2 | SEC. 28-301.1 FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER 115.6(1968 CODE)FGC APENDIX E(E4)(2014 CODE) NOTE:... | $0 | $0 | May 3, 2018 |
| Mar 10, 2017 | 35234875M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:NOTED:AT TIME OFINSPECTION OBSERVED ON THE 3RD FLR, FIREPROOF S... | $0 | $0 | Apr 27, 2017 |
| Mar 10, 2017 | 35234876Y | RESOLVE | CLASS - 2 | 28-301.1 UNLAWFUL PLACEMENT OF FURNISHINGS,DECORATIONS OR OTHER OBJECTS AT EXITS THAT OBSTRUCT ACCESS TO, EGRESS FROM... | $0 | $0 | Apr 27, 2017 |
| May 6, 2015 | 35128641K | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING.NOTE:2ND FL CORRIDOR SMOKE DOOR NEAR ROOM 209 NOT CLOSING.GYM EXIT DOOR NEAR ROOM 232 NOT ... | $0 | $0 | Jun 18, 2015 |
| May 6, 2015 | 35128642M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER:NO FIRE STOPPING PERBC 712.3;27-345.NOTED:@ CELLAR LEVEL IN ELECTRI... | $0 | $0 | Jun 18, 2015 |
| Mar 17, 2014 | 35093358H | RESOLVE | CLASS - 2 | EMERGENCY LIGHTING IS DEFECTIVE.@ GYM WEST EXIT EMERGENCY LIGHTING NOTWORKING.REM:REPAIR OR REPLACE LIGHTING. | $0 | $0 | Jun 5, 2014 |
| Mar 17, 2014 | 35093357X | RESOLVE | CLASS - 2 | EXCESSIVE COMBUSTIBLES.@ FIRE STAIRS 2 FL & 3RD FL STAIR "A",BULLETIN BOARDS INSTALLED W/ PAPER POSTINGS IN STAIR LAN... | $0 | $0 | Jun 5, 2014 |
| Mar 17, 2014 | 35093356Y | RESOLVE | CLASS - 2 | PARTIAL CORRIDOR OBSTRUCTION.50% OBSTRUCTION OF FIRE CORRIDOR ADJACENTTO ROOM 106 W/ TABLES & CHARIS.REM:REMOVE ALL I... | $0 | $0 | Jun 5, 2014 |
| Jan 15, 2013 | 34996339N | RESOLVE | CLASS - 2 | REISSUE: 34941651J CORRIDOR SMOKE DOORS ARE DRAGGING ON THE FLR CAUSING DOORS NOT TO OPEN/CLOSE PROPERLY LOCATED ON T... | $0 | $0 | Apr 4, 2013 |
| Jan 15, 2013 | 34996340K | RESOLVE | CLASS - 2 | REISSUE: 34941650H. KITCHEN EXHAUST HOOD IS NOT IN OPERATIONAL AT TIMEOF INSPECTION ON THE 1ST FLR LEVEL. REMEDY: REP... | $0 | $0 | Apr 4, 2013 |
| Mar 21, 2012 | 34941650H | RESOLVE | CLASS - 2 | DEFECTIVE EXHAUST FOR KITCHEN HOOD, HOOD NOT OPERATIONAL AT TIME OF INSPECTION. REMEDY: REPAIR EXHAUST. | $0 | $0 | May 17, 2012 |
| Mar 21, 2012 | 34941651J | RESOLVE | CLASS - 3 | DEFECTIVE CORRIDOR DOOR NEAR ROOM 309 DOOR DRAGGING ON FLOOR. REMEDY: REPAIR/REPLACE DEFECTIVE DOOR. | $0 | $0 | May 17, 2012 |
| Apr 15, 2011 | 32070406M | RESOLVE | CLASS - 2 | B254,11C,18A,24B,50,A,B. 50- BOTH STEAM CONTROLS PIPED TO BOILER ON ONE 1/4 PIPE. 50A- LEAK AT OIL PUMP. 50B- OIL VAL... | $0 | $0 | Jun 16, 2011 |
| Apr 15, 2011 | 32070408X | RESOLVE | CLASS - 2 | B254,19B,32A. | $0 | $0 | Jun 16, 2011 |
| Apr 15, 2011 | 32070407Y | RESOLVE | CLASS - 2 | B254,18A,50,50A. 50- BOTH STEAM CONTROLS ON SINGLE 1/4 PIPE TO BOILER.50A- SHUT OFF VALVE MISSING TOP OF OIL TANK ON ... | $0 | $0 | Jun 16, 2011 |
| Feb 3, 2011 | 34897294P | RESOLVE | CLASS - 2 | PARTIAL OBSTRUCTION OF EXIT PASSAGEWAY @ STAIRWAY 4A, 4B TO BULKHEAD WITH WORK MATERIAL AN TOOL AND EQUIPMENT. @ 4B C... | $0 | $0 | Mar 17, 2011 |
| Feb 3, 2011 | 34897295R | RESOLVE | CLASS - 2 | DEFECTIVE BRICK MASONRY FACADE @ 4TH FL NORTH ABOVE GYM ALONG 11, HS STEP CRACKING AND LOOSE MORTAR JOINTS AND SPALLI... | $0 | $0 | Mar 17, 2011 |
| Feb 3, 2011 | 34897299Y | RESOLVE | CLASS - 2 | GRATES DEFECTING AT FRONT ALONG 11TH ST (EXPOSURE) THE GRATING SUPPORTS ARE ERODED W/ 2" DEFLEXTION AT LEFT AND RIGHT... | $0 | $0 | Mar 17, 2011 |
| Feb 3, 2011 | 34897296Z | RESOLVE | CLASS - 3 | DEFECTIVE GLAZED BLOCK TILE @ 4TH FL ROOF ACCESS, ACROSS FROM STAIRWAY4C THE BLOCK TILE IS DISLODGED AND SEPARATING W... | $0 | $0 | Mar 17, 2011 |
| Feb 3, 2011 | 34897298M | RESOLVE | CLASS - 2 | DOOR NOT CLOSING DOOR CHECK BROKEN @ 1ST FL STAIRWAY 'D; THE FIRE PROOF SELF CLOSING (FPSC) DOOR DOES NOT SELF CLOSE ... | $0 | $0 | Mar 17, 2011 |
| May 14, 2010 | 34847115P | RESOLVE | CLASS - 2 | CORRIDOR SMOKE DOORS ON THE FLOOR NEAR ROOM 428 NOT CLOSING REM: REPAIR REPLACE DOORS | $0 | $0 | Sep 16, 2010 |
| May 14, 2010 | 34847116R | RESOLVE | CLASS - 2 | ELECTRICAL ROOM AT CELLAR LVL IS BEING USED FOR STORAGE OF TOOLS WET VAC LADDER BOOK CASE BOXES ETC REM: REMOVE STORA... | $0 | $0 | Sep 16, 2010 |
| Jul 2, 2009 | 34780099K | RESOLVE | CLASS - 2 | REISSUE: 334711653J. EXTERIOR BRICK FACADE IS CRACKED/BULGING & MISSING MORTAR LOCATED AT WEST 11 ST & 6 AVE (4FL) & ... | $0 | $0 | Sep 17, 2009 |
| Jul 2, 2009 | 34793375K | RESOLVE | CLASS - 2 | THE GAS METER ROOM IS LACKING FIRE STOPPING AT CELLAR LEVEL. REMEDY:PROVIDE / MAINTAIN FIRE STOPPING. | $0 | $0 | Sep 17, 2009 |
| Nov 20, 2008 | 34711653J | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN BLDG WALLS OR APPURT.NOTE:SEPARATION CRACKS & MORTAR MISSING DEFECTIVE & BRICKWORK.LOCATIONS 1- E... | $0 | $0 | Jan 8, 2009 |
| Jun 25, 2008 | 34661997K | RESOLVE | Hazardous | SIDEWALK SHED NOT ADEQUATELY MAINTAIN. APPROX 100FT OF PARAPET COLLAPSE ONTO SCHOOL GROUNDS. | $0 | $0 | Nov 20, 2008 |
| Jun 25, 2008 | 34661998M | RESOLVE | Non-Hazardous | SIDEWALK SHED UNSAFE PARAPET IS LOOSE ON SIDEWALK SHED | $2,000 | $0 | Nov 20, 2008 |
| Aug 8, 2007 | 34592158N | RESOLVE | Hazardous | FAILURE TO MAINTAIN- INTERIOR. 1ST FL- AUDITORIUM- RIGHT SIDE OF STAGE- 2 EXIT DOORS DO NOT OPEN. 4TH FL- CORRIDOR FI... | $0 | $0 | Nov 15, 2007 |
| Jan 22, 2003 | 34373309L | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN BUILDING NOTED MISSING PANIC BAR AT FIRST FLOOR AUDITORIUM, STAGE EXIT DOOR, SOUTHSIDE TO CORRIDO... | $0 | $0 | Apr 10, 2003 |
| Jan 22, 2003 | 34373138X | RESOLVE | Non-Hazardous | EXIT PASSAGEWAY OR CORRIDOR REQUIRED WIDTH DECREASED BY OBSTRUCTIONS NOTED AT FOURTH FLOOR CORRIDOR CLASS ROOMS 402,4... | $0 | $0 | Apr 10, 2003 |
| Jan 22, 2003 | 34373308J | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN BUILDING. NOTED: BROKEN DOOR CHECKS AT. THIRD FLOOR CORRIDOR FIRESTOP DOOR NEAR ROOM 328 AND CELL... | $0 | $0 | Apr 10, 2003 |
| Jan 22, 2003 | 34373140P | RESOLVE | Hazardous | REQUIRED MEANS OF EGRESS OBSTRUCTED NOTED AT CELLAR EXIT ON WEST 11 ST SIDE NEAR MAIN ENTRANCE PERIMETER FENCE GATE P... | $0 | $0 | Apr 10, 2003 |
| Jan 7, 2002 | 34312190Y | RESOLVE | Non-Hazardous | REISSUE FAILURE TO PROVIDE PANIC HARDWARE WHERE REQUIRED BY LAW AT GYMNASIUM REMEDY PROVIDE PANIC HARDWARE | $0 | $0 | Apr 11, 2002 |