ECB violations
119 Christopher Street, Manhattan • Block 00619 • Lot 0045
45 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Jun 3, 2024 | 39115855Z | RESOLVE | CLASS - 2 | ATOI OBSERVED EXCESSIVE AMOUNT OF CONSTRUCTION DUST SPREAD THROUGHOUT BUILDING. OBSERVED ON AND AROUND STAIRWELL'S/HA... | $0 | $0 | Aug 8, 2024 |
| Oct 16, 2017 | 35249744Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN ADEQUATE HOUSEKEEPING PER SECTION REQUIREMENTS.AT THE TIME OF INSEPCTION AT THE 3RD,2ND AND 1ST F... | $2,000 | $0 | Dec 7, 2017 |
| Apr 25, 2017 | 35125784Y | RESOLVE | CLASS - 1 | WORK W/O A PERMIT. WORK NOTED: AT THE TIME OF INSPECTION 3:20PM OBSERVED APPROX 70' OF 2" BLACK STEEL(MALLEABLE)GAS P... | $1,600 | $0 | Nov 20, 2017 |
| Mar 16, 2016 | 35141735H | RESOLVE | CLASS - 1 | FAILURE TO HAVE NEW OR ALTERED PLUMBING SYSTEM TESTED. OBSERVATION HAS BEEN MADE DURING A SAFETY SWEEP IN APT#54 UNDE... | $1,000 | $0 | Sep 1, 2016 |
| Mar 16, 2016 | 35176777X | RESOLVE | CLASS - 2 | FAIL TO PROVIDE APPROVED/ACCEPTED PLANS @JOB SITE.NOTE:APPROVED PLANS UNDER JOB #140448567 NOT PROVIDED BY CONSTRUCTI... | $250 | $0 | Jun 30, 2016 |
| Mar 16, 2016 | 35176775M | RESOLVE | CLASS - 1 | WORK W/O PERMIT.NOTE:APT #21 IS BEING GUTTED AND IS UNDER FULL DEMOLITION:WALLS, PLASTER,SHEETROCK,LATHE,ELECTRICAL R... | $800 | $0 | Jun 30, 2016 |
| Mar 16, 2016 | 35176776Y | RESOLVE | CLASS - 2 | WORK DOES NOT CONFORM TO APPROVED CONSTRUCTION DOCS/AMENDMENTS.NOTE:@APT #43 UNDER APPLICATION #122394051 INSTALLATIO... | $0 | $0 | May 5, 2016 |
| Mar 16, 2016 | 35176778H | RESOLVE | CLASS - 2 | WORK DOES NOT CONFORM TO APPROVED PLANS/DOCS/AMENDMENTS.NOTE:@APT #22 BATHROOM DOES NOT CONFORM TO APPR PLANS PRESENT... | $0 | $0 | May 5, 2016 |
| Mar 16, 2016 | 35176780R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN HOUSEKEEPING PER SECTION REQUIREMENTS.@ ROOF EXCESSIVE CONSTRUCTION DEBRIS WOOD,(LATHE) FLOORING,... | $0 | $0 | May 5, 2016 |
| Mar 16, 2016 | 35141734X | RESOLVE | CLASS - 1 | WORK W/OUT PERMIT.WORK NOTED: OBSERVATION HAS BEEN MADE DURING A SAFETY SWEEP IN APT#64,THE TOILET WAS REMOVED & THE ... | $800 | $0 | Sep 1, 2016 |
| Mar 16, 2016 | 35141731K | RESOLVE | CLASS - 1 | WORK W/OUT PERMIT. WORK NOTED: OBSERVATION HAS BEEN MADE DURING A SAFETY SWEEP IN CELLAR A 2" GAS HAS BEEN RAN TO A D... | $0 | $0 | Sep 1, 2016 |
| Mar 16, 2016 | 35176779J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.NO FIRE PROTECTION-STOPPING PER BC712.3,27-345.NOTED @ APT21 WALLS,... | $0 | $0 | Jun 30, 2016 |
| Mar 16, 2016 | 35159010X | RESOLVE | CLASS - 2 | ELECTRICAL WORK W/O PERMIT. OBSERVED AT 2PM BRANCH CIRCUIT WIRING INSTALLED FOR OUTLETS,SWITCHES,FIXTURES,PANELS IN A... | $0 | $0 | May 19, 2016 |
| Mar 16, 2016 | 35176781Z | RESOLVE | CLASS - 1 | FAIL TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.NOTE:STAIRWAY TO CELLAR IS BROKEN W/OVERHEAD WOOD SHED,BROKEN.BROKEN H... | $0 | $0 | Jul 21, 2016 |
| Mar 16, 2016 | 35169068H | RESOLVE | CLASS - 2 | FAILURE TO SAFEGUARD PUBLIC & PROPERTY.NOTED WORK ON GIVING IN APT41,UNDER PERMIT#140403953 & WATER LEAK IN BATHROOM ... | $1,200 | $0 | Jun 2, 2016 |
| Mar 16, 2016 | 35141732M | RESOLVE | CLASS - 1 | FAILURE TO HAVE NEW OR ALTERED PLUMBING SYSTEM TESTED. OBSERVATION HASBEEN MADE DURING A SAFETY SWEEP IN APT#44 UNDER... | $1,000 | $0 | Sep 9, 2016 |
| Mar 16, 2016 | 35141733Y | RESOLVE | CLASS - 1 | FAILURE TO HAVE NEW OR ALTERED PLUMBING SYSTEM TESTED. OBSERVATION HAS BEEN MADE DURING A SAFETY SWEEP IN APT#43 UNDE... | $1,000 | $0 | Sep 1, 2016 |
| Feb 10, 2016 | 35140252Z | RESOLVE | CLASS - 1 | GAS BEING SUPPLIED TO BUILDING W/O INSPECTION AND CERTIFICATION BY DOBOBSERVATION HAS BEEN MADE DURING SAFETY SWEEP T... | $0 | $0 | Sep 1, 2016 |
| Feb 10, 2016 | 35140253K | RESOLVE | CLASS - 1 | WORK WITHOUT PERMIT WORK NOTED, OBSERVATION HAS BEEN MADE DURING SAFETY SWEEP A 12 PM UNDER LAA 122294659 WHICH IS DI... | $1,600 | $0 | Sep 1, 2016 |
| Feb 10, 2016 | 35159549J | RESOLVE | CLASS - 2 | UNAPPROVED UNSAFE UNSUITABLE ELECTRICAL EQUIPMENT APPARATUS,MATERIALS DEVICES APPLIANCES OR WIRING IN USE. ON 2/10/16... | $400 | $0 | Jun 30, 2016 |
| Feb 10, 2016 | 35140251R | RESOLVE | CLASS - 1 | PIPING AND/OR EQUIPMENT INSTALLED IMPROPERLY: OBSERVATION HAS BEEN MADE DURING SAFETY SWEEP IN APT 31 GAS FLEX HAS BE... | $1,600 | $0 | Sep 1, 2016 |
| Dec 4, 2015 | 35123644N | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN ADEQUATE HOUSEKEEPING PER SECTION REQUIRMENTS:NOTED:EXCESSIVE AMOUNT OF CONST DEBRIS STORED @ THE... | $400 | $0 | Feb 18, 2016 |
| Dec 4, 2015 | 35123643L | RESOLVE | CLASS - 1 | WORK W/O PERMIT:OBSERVED REMOVAL OF PARTITION WALLS,BLD MATERIAL(NEW)&CONST DEBRIS @ CELLAR LEVEL OF MENTIONED ADDRES... | $1,600 | $0 | Feb 18, 2016 |
| Dec 4, 2015 | 35123646R | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLAINT MANNER:NO FIRE STOPPING PERBC 712.3;27-345.OBSERVED SEVERAL OPENINGS IN FI... | $1,000 | $0 | Feb 18, 2016 |
| Dec 4, 2015 | 35123647Z | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN A CODE COMPLAINT MANNER:IMPROPER EXIT/EXITACCESS DOORWAY ARRANGEMENT PER BC 1014.2.NOTED:... | $1,200 | $0 | Feb 18, 2016 |
| Dec 4, 2015 | 35123649M | RESOLVE | CLASS - 1 | 28-104.8.4,TENANT PROTECTION PLAN IS INADEQUAETE:NOTED:THE TENANT SAFETY PLAN FOR ALT 2 APP #140403953 IS INADEQAUTE ... | $1,600 | $0 | Feb 18, 2016 |
| Dec 4, 2015 | 35123648K | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN A CODE COMPLIANT MANNER:FL NUMBERING SIGNSMISSING.PER BC1019.1.7.NOTED:NONE OF THE FL OF ... | $1,000 | $0 | Feb 18, 2016 |
| Dec 4, 2015 | 35123645P | RESOLVE | CLASS - 1 | WORK DOES NOT CONFORM TO APPROVED CONST DOCUMENTS 7/OR APPROVED AMENDMENTS.NOTE:ALT2 JOB #122331306 MADE NO(MANTAIN)O... | $1,000 | $0 | Feb 18, 2016 |
| Nov 2, 2015 | 35047133J | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/ THE COMM'S ORDER CONTAINED IN NOV#35136751L ISSUED ON 6/5/15 & TO FILE A CERT OF CORRECTION PURS... | $4,000 | $0 | Dec 17, 2015 |
| Oct 1, 2015 | 35074850X | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.NOTED:AT REAR THE FIRE ESCAPE IS OBSTRUCTED WITH HOUSE HOLD MATERIA... | $1,000 | $0 | Dec 10, 2015 |
| Oct 1, 2015 | 35074851H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.NOTED,IN APT.#64 THERE ARE CRACKS ON THE WALLS AND CEILING AND THE ... | $250 | $0 | Dec 10, 2015 |
| Oct 1, 2015 | 35159277P | RESOLVE | CLASS - 2 | ELECTRICAL WORK W/OUT A PERMIT ON 10/1/15 @12:45PM I OBSERVED:NEW BRANCH CIRCUIT WIRING FOR ELECTRICAL STOVE IN APT #... | $0 | $0 | Dec 3, 2015 |
| Oct 1, 2015 | 35136299Y | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.NOTED:JOB.#122331306 ALT.2(PERMITTED)TENANT PROTECTION PLAN DOES NO... | $1,000 | $0 | Dec 10, 2015 |
| Aug 2, 2015 | 35044765Y | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/ THE COMM'S ORDER CONTAINED IN NOV#35136784H ISSUED ON 6/17/15 & TO FILE A CERT OF CORRECTION PUR... | $25,000 | $0 | Dec 31, 2015 |
| Jul 24, 2015 | 35044832P | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN NOV#3513 6751L ISSUED ON 6/5/15 AND TO FILE A CERTIFICAT... | $4,000 | $0 | Dec 31, 2015 |
| Jun 17, 2015 | 35136784H | RESOLVE | CLASS - 1 | WORK W/O PERMIT(S). AT APT 43 REMOVED ALL WALLS,PLUMBING AND ELECTRIC (GUT REHAB) NO PERMITS POSTED. RMDY: STOP ALL W... | $1,600 | $0 | Aug 6, 2015 |
| Jun 5, 2015 | 35136751L | RESOLVE | CLASS - 1 | 28-103.13 RIGHT OF ENTRY TO SITE DENIED NOTED.OBSERVED 2 WORKERS CAME OUT OF SITE UNDER APP 140312533 & 140344946 W/K... | $1,600 | $0 | Jul 23, 2015 |
| Jun 16, 2009 | 34789500Z | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING WALLS OR APPURTENANCES. NOTED: BUILDINGS PARAPET WALL (WEST SIDE) IS IN DANGER OF COLLAP... | $1,000 | $0 | Dec 10, 2009 |
| Jun 16, 2009 | 34789501K | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: ROOF COVERING & FLASHING IS SEPARATING AT VARIOUS LOCAT... | $0 | $0 | Dec 10, 2009 |
| Apr 19, 2005 | 34400105K | RESOLVE | Non-Hazardous | ILLEGAL USE IN A RESIDENTIAL DISTRICT.BSA PERMIT WHICH PROVIDES FOR USE OF FIRST FLOOR EAST AS A USE GROUP 6 RETAIL S... | $480 | $0 | Jul 21, 2005 |
| Apr 28, 2004 | 34432589M | RESOLVE | Non-Hazardous | FAILURE TO COMPLY WITH MAXIMUM RISER HEIGHT NOTE:AT FRONT ENTRANCE LEVEL EXIST A RISER HEIGHT OF 9 1/2" WHICH EXCEEDS... | $0 | $0 | Dec 9, 2004 |
| Apr 28, 2004 | 34432590J | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN NOTE:AT 1ST FLOOR CEILING LEVEL EXIST A FIRE ESCAPE DROP LADDER WITHOUT IT'S SHOE (27-380) REMEDY... | $350 | $0 | Sep 23, 2004 |
| Jan 20, 1998 | 34184890L | RESOLVE | Hazardous | FAILURE TO COMPLY WITH VARIANCE/SPECIAL PERMIT ISSUED BY B S A FOR ZONING RESOLUTION IN THAT PERMIT #818-85 EXPIRED O... | $480 | $0 | Mar 11, 1999 |
| Dec 1, 1992 | 34081428J | RESOLVE | Non-Hazardous | WORK WITHOUT PERMIT: WORK NOTED IN CELLAR. INSTALLED DROP CEILING THROUGH- CONTRARY TO (RS-5-16 OF ADMINSTRATIVE CODE... | $350 | $0 | Feb 4, 1993 |
| Dec 1, 1992 | 34081427H | RESOLVE | Non-Hazardous | WORK WITHOUT PERMIT: WORK NOTED, IN CELLAR OF VIDEO STORE- ERECTED AND INSTALLED PARTITIONS CHANGING ARRANGEMENT IN C... | $350 | $0 | Feb 4, 1993 |