Skip to content

ECB violations

265-269 West 37 Street, Manhattan • Block 00787 • Lot 0001

99 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Jun 17, 2026 39192816P ACTIVE CLASS - 1 I OBSERVED INSTALLATION OF THREE NEW ILLUMINATED SIGNS "BARBIE DUNKIN' DREAMHOUSE" WITH AND APPROXIMATELY DIMENSIONS ... $2,500 $0 Aug 27, 2026
Jun 17, 2026 39192817R ACTIVE CLASS - 2 I OBSERVED IN "BARBIE DUNKIN' DREAM HOUSE" INSTALLATION/REPLACEMENTS OF LIGHT FIXTURES THROUGHOUT THE STORE WITHOUT A... $1,250 $0 Aug 27, 2026
Oct 15, 2024 39533397M RESOLVE CLASS - 2 OBSERVED SIDEWALK SHED IN PLACE AT EXP#1&4 NOT AS PER DRAWINGS. OBSERVED DRAWINGS CALLS FOR 20FT HIGH SHED WITH 3X2" ... $1,250 $0 Dec 19, 2024
Jun 28, 2024 39530060N ACTIVE CLASS - 2 AT TIME OF INSPECTION OBSERVED SIDEWALK SHED ERECTED AT EXPOSURE #1- .OBSERVED NO LIGHT UNDER THE SIDEWALK SHED CREAT... $2,400 $0 Sep 5, 2024
Aug 17, 2021 35585899L RESOLVE CLASS - 2 FAILURE TO COMPLY WITH COMMISSIONERS ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDINGS OF BU... $0 $0 Nov 4, 2021
Jan 28, 2021 35544544L RESOLVE CLASS - 2 PEDESTRIAN PROTECTION DOESN'T MEET CODE SPECIFICATIONS @TIME OF INSPECTION RESPONDING TO COMPLAINT ON 23STYBLDG OBSER... $2,430 $0 Jul 22, 2021
Aug 26, 2020 35492507K RESOLVE CLASS - 2 FAILURE TO MAINTAIN/DISPLAY ON SITE DOCUMENTS REQUIRED BY BC CHAPTER 33.AT TIME OF INSPECTION ON AN ACTIVE JOBSITE OF... $0 $0 Nov 5, 2020
Aug 26, 2020 35492506Z RESOLVE CLASS - 2 FAILURE TO PROVIDE APPROVED PLANS AT JOBSITE AT TIME OF INSPECTION ON AN ACTIVE JOBSITE OF A 23 STORY EXISTING BUILDI... $0 $0 Nov 5, 2020
Jan 22, 2020 35467533J RESOLVE CLASS - 2 PEDESTRIAN PROTECTION DOES NOT MEET CODE SPECIFICATION.AT ITME OF IMY INSPECTION I OBSERVED SIDEWALK SHED IN PLACE WI... $2,400 $0 Nov 12, 2020
Dec 30, 2019 35468378N ACTIVE CLASS - 2 PEDESTRIAN PROTECTION DOES NOT MEET CODE SPECIFICATION:SIDEWALK SHED MAINTENANCE. AT THE TIME OF MY INSPECTION OF A P... $10,000 $10,000 Mar 5, 2020
Mar 22, 2019 35365322M RESOLVE CLASS - 1 FAILURE TO TAKE ADEQUATE REQUIRED MEASURES TO SECURE PUBLIC SAFETY FROM DOCUMENTED UNSAFE FACADE. AS PER 1RCNY 103-04... $10,000 $0 May 16, 2019
Aug 1, 2018 37012331N RESOLVE CLASS - 2 FAILURE TO FILE ACCEPTABLE CYCLE 8B REPOPRT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRIBED IN INITIAL FACADE RE... $3,125 -$3,125 Feb 7, 2019
Aug 1, 2014 35096401H RESOLVE CLASS - 2 SEC. 42-411 FAILURE TI COMPLY W/USES LOCATED W/I A COMPLETELY ENCLOSEDBLDG IN A M-1 ZONING DISTRICTS. NOTED: ILLEGALL... $0 $0 Sep 18, 2014
May 31, 2012 38221781H ACTIVE CLASS - 1 28-116.4.1: 97R07,45R07: 97;FAILURE TO OBTAIN CERT OF COMPLIANCE. NO REPORT OF INSPECTION SUBMITTED TO DOB & NO WITNE... $1,600 $0 Sep 27, 2012
Feb 17, 2012 38220241M ACTIVE CLASS - 1 100I/K10/11 05B07 34O02 100I10 KM07 100H/I11 01I10 38#09 77X10 53O02 77O02 75K10 76X10 76I11. 100-SB LOCK DAMAGED/RUS... $1,000 $0 Sep 27, 2012
Jul 28, 2010 38210990K RESOLVE CLASS - 3 98BB05. 98BB- FILE & PERFORM 5 YR TEST, TAG EXPIRED $200 $0 Sep 16, 2010
Apr 22, 2010 34832542H RESOLVE CLASS - 1 FAILURE TO PERFORM SAFE/PROPER INSPECTION OF SUSPENDED SCAFFOLD. NOTEDNO CONTINUITY OF DAILY INSPECTION IN DAILY INSP... $2,400 $0 Jun 17, 2010
Apr 22, 2010 34832541X RESOLVE CLASS - 1 INADEQUATE SAFETY MEASURES OPERATION OF HOISTING EQUIPMENT IN UNSAFE MANNER. NOTED: MULTIPLE TIE BACK CABLES AND LIFE... $4,800 $0 Jun 17, 2010
Mar 25, 2009 32066485H ACTIVE CLASS - 3 36.50D.50A.50C SUSSMAN MINATURE ELECTRICAL BOX 17KW MB 124455 36 REFERENCES ELECTRICAL MINATURE STEAM BOILER IN OPERA... $200 $0 May 14, 2009
Mar 25, 2009 32066486J ACTIVE CLASS - 3 36. SUSSMAN ELECTRICAL MINATURE 8CR 8KW 2008 6509 36 REFERENCED ELECTRICAL HIGH PRESSURE STEAM BOILER ISN'T REGISTERE... $200 $0 May 14, 2009
Mar 17, 2008 32056158L ACTIVE Non-Hazardous 18A,B.FULTON V.T. BLR 10HP NB 65252, GAS, 1992.18A,B-SCALE ACCUMULATION CORROSION & LEAKAGE AT UPPER & LOWER HANDHOLE... $180 $0 Aug 28, 2008
Mar 17, 2008 32056159N ACTIVE Non-Hazardous 50A,50B.FULTON V.T BLR,10HP,NB 69874,GAS,1994.50A-INADEQUATE STRUCTURESUPPORT OF THE LOADED FLUE PIPE SYSTEM INSTALLE... $180 $0 May 8, 2008
Jan 19, 2008 32055705R ACTIVE Non-Hazardous 36,5A.ELECTRIC HP STEAM BOILER,MINIATURE(36)REFERENCED BOILER IS NOT REGISTERD ON THE DOB DATABASE.RESPONDENT IS REQU... $350 $0 Jul 17, 2008
Jan 19, 2008 32055704P ACTIVE Non-Hazardous 36,50A.REIMERS HP MINIATURE ELECTRIC BLR 6KW.36-REFERENCED BOILER IS NOT REGISTERED ON THE DOB DATABASE.RESPONDENT MU... $350 $0 May 15, 2008
Jan 16, 2008 32055700H RESOLVE Non-Hazardous 50A.B.C.FULTON VT BLR 15HP,NB 65660,GAS 1992.50A-SECONDARY LOW WATER CUT OFF MANUAL RESET SWITCH DISCONNECTED.RESTORE... $180 $0 Mar 13, 2008
Jan 12, 2008 32055393R ACTIVE Non-Hazardous 36,50A,B.REIMERS ELECTRIC MINIATURE HP STEAM BLR.4 -5 SLW.36-REFERENCED BOILER NOT REGISTERED ON THE DOB DATABASE.RES... $350 $0 Jul 7, 2008
Jan 12, 2008 32055394Z ACTIVE Non-Hazardous 50A,B,C.FULTON VT BLR.10HP,NB 41279,GAS FIRED,1982.50A-SECTION OF BLOWDOWN DRAIN PIPING CORRODED.REPLACE DEFECTIVE PI... $180 $0 Feb 28, 2008
Apr 19, 2006 32049673K RESOLVE Non-Hazardous 50. FULTON V.T. BOILER 6 HP, NB46981, GAS 1985. 50- IMPROPER ARRANGEMENT OF THE BLOWDOWN VALVES ON THE HIGH PESSURE S... $0 $0 Jun 8, 2006
Apr 18, 2006 32049672Z ACTIVE Non-Hazardous 50A/50C/50B. FULTON V.T. VOILER, 15HP, NB65660 GAS, 1992. 50A- SECONDARY LOW WATER MANUAL RESET SWITCH DISCONNECTED. ... $180 $0 Jun 8, 2006
Apr 17, 2006 32049669H RESOLVE Non-Hazardous 50A,50B/ FUCTON V.T. BOILER, 10HP, NB 69573, GAS, 1994/ 50A-IMPROPER ARRANGEMENT OF THE BROWDOWN VALVES. INSTALL A SC... $0 $0 Jun 1, 2006
Apr 17, 2006 32049670P RESOLVE Non-Hazardous 50/ FUCTON V.T. BOILER, 10HP, NB 60612, GAS, 50-NO PROTECTIVE GUARD OVER THE DRIVE SHAFT COUPLING OF THE BOILER'S AIR... $0 $0 Jun 1, 2006
Apr 17, 2006 32049671R RESOLVE Non-Hazardous 50/ FUCTON V.T. BOILER, 10HP, NB65001, GAS, 1992. 50-BROKEN SANDARD STRAP HANGER ON THE FLUE PIPE. REPLACE WITH A HEA... $0 $0 Jun 1, 2006
Jul 7, 2004 32045212J RESOLVE Non-Hazardous 18AB 50A 50C 34A 50B FULTON VT BOILER, 10HP, NB62159, GAS, 1991 50A BLOWDOWN LINE CORRODED & VALVES IN WRONG POSITION... $0 $0 Aug 26, 2004
Jul 7, 2004 32045213L ACTIVE Non-Hazardous 44C 50B 50A FULTON VT BOILER, 10HP, NB64104, GAS 1992 50A DEFICIENT STRUCTURE SUPPORT OF THE FLUE PIPE SYSTEM. INSTAL... $180 $0 Aug 26, 2004
Jul 7, 2004 32045214N RESOLVE Non-Hazardous 50A 50C 50E 50B 50D FULTON VT BOILER, 10HP, NB72433, GAS, 1995 50A INADEQUATE STRUCTURAL SUPPORT FOR THE FLUE PIPE. I... $0 $0 Aug 26, 2004
Jul 7, 2004 32045215P RESOLVE Non-Hazardous 50A 50C 50B FULTON VT BOILER, 10HP, NB68979, GAS, 1993 50A INADEQUATE STRUCTURAL SUPPORT ON THE FLUE PIPE SYSTEM. INS... $180 $0 Oct 14, 2004
Jul 7, 2004 32045211H RESOLVE Non-Hazardous 44C 50B 50A 50C FULTON VT BOILER, 10HP, NB69874, GAS, 1994 50A CORRODED STEAM STOP VALVE. REPLACE. 50B NO SECONDARY S... $180 $0 Oct 21, 2004
Jul 6, 2004 32045208R RESOLVE Non-Hazardous 48AB 50B 50A 50C FULTON VT BOILER, 10HP, NB25689, GAS-FIRED, 1971 50A SECONDARY LOW WATER CUT OFF MANUAL RESET SWITCH... $180 $0 Apr 21, 2005
Jul 6, 2004 32045210X ACTIVE Non-Hazardous 18AB 50B 50A FULTON VT BOILER 10HP, NB65252, GAS 1992 50A CORRODED & LEAKING FEED WATER INCET LINE NEAR CHECK VALVE 5... $350 $0 Nov 18, 2004
Jul 6, 2004 32045207P ACTIVE Non-Hazardous 18AB 48AB 50B 50D 34B 50A 50C FULTON VT BOILER, 10HP, NB30837, GAS-FI RED, 1973. 50A NO SECONDARY SCREW-TYPE SHUT OFF... $180 $0 Dec 2, 2004
Jul 6, 2004 32045209Z ACTIVE Non-Hazardous 18AB 50A 48AB 50B FULTON VT BOILER, 10HP, NB41279, GAS-FIRED, 1982 50ASTEAM PRESSURE GAUGE HAS A DIAL RANGE OF 0-160P... $2,500 $0 Aug 26, 2004
Jul 2, 2004 34400006P RESOLVE Non-Hazardous FILING A FALSE STATEMENT OF CORRECTION WITH NYC DOB.PRIOR ECB 34399936X ISSUED 10/24/03.FOUND IN VIOLATION 12/18/03 F... $0 $0 Sep 9, 2004
Jul 2, 2004 34400005N RESOLVE Non-Hazardous (1)OPERATION OF NORTHERN MOST 1ST FLOOR MEZZANINE AS A PLACE OF ASSEMBLY (2)OPERATION OF A STRIP CLUB ON NORTHERN MOS... $0 $0 Sep 9, 2004
Jun 30, 2004 32045204J ACTIVE Non-Hazardous 50A FULTON VERTIBRATES BLR. 10HP, NB 60612, GAS, 1990 50A IMPROPER ARRANGEMENT OF BROW DOWN VALVES. SWITCH EXISTING V... $180 $0 Jan 27, 2005
Jun 30, 2004 32045205L RESOLVE Non-Hazardous 50A/50B 50C/16 FULTON V.T. BOILER, 10HP, NB 44911, GAS, 1984 50A INADEQUATE SUPPORT OF THE BOILER FLUE PIPE SYSTEM. F... $0 $0 Aug 19, 2004
Jun 30, 2004 32045202X ACTIVE Non-Hazardous 50A/50B FULTON V.T. BOILER 15 HP, NB 65660, GAS, 1992 50A INADEQUATE STRUCTURAL SUPPORT OF THE FLUE PIPE. INSTALL HEA... $2,500 $0 Aug 19, 2004
Jun 30, 2004 32045203H RESOLVE Non-Hazardous 50A/50B FULTON V.T. BOILER, 10HP, NB 65001, GAS, 1992 50A IMPROPER ARRANGEMENT OF BROWDOWN VALVES. SWITCH VALVES AROU... $0 $0 Aug 19, 2004
Jun 30, 2004 32045201Y RESOLVE Non-Hazardous 50A/50B FULTON V.T. BOILER, 10HP, NB 65494, GAS; 1992 50A NO STRUCTURAL SUPPORT ON THE FLUE PIPE. INSTALL HEAVY DUTY ... $180 $0 Nov 18, 2004
Jun 30, 2004 32045206N RESOLVE Non-Hazardous 50A/50B FULTON V.T. BLR 10HP, NB 69573, GAS, 1994 50A NO STRUCTURAL SUPPORT ON THE FLUE PIPE. INSTALL HEAVY DUTY HANG... $0 $0 Aug 19, 2004
Feb 3, 2004 38144930X RESOLVE Non-Hazardous 38L10/1B10/16B1/83O2/31H10/51K11/71M7/21M7/11M7/38B10/71B11/73B1/37A9.38L10=REPAIR INSPECTION TOP OF CPC/01-B-10 REPA... $350 $0 Mar 25, 2004