ECB violations
247-263 West 37 Street, Manhattan • Block 00787 • Lot 0011
59 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Jul 1, 2025 | 37035476X | RESOLVE | CLASS - 2 | FAILURE TO FILE REQUIRED ANNUAL BOILER INSPECTION REPORTS FOR LOW-PRESSURE BOILER 10000165587N0001 IN ACCORDANCE WITH... | $0 | $0 | Sep 18, 2025 |
| Apr 11, 2024 | 37027638J | RESOLVE | CLASS - 2 | FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 9B REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WA... | $1,250 | $0 | Oct 17, 2024 |
| Apr 8, 2024 | 39111045Z | RESOLVE | CLASS - 2 | AT TIME OF INSPECTION, I OBSERVE GAS PIPING IN BASEMENT WITH A BUSHING USED ON DRIP END OF TEE. AS PER 2008 FGC SECTI... | $625 | $0 | Jun 13, 2024 |
| Nov 1, 2021 | 39050382N | RESOLVE | CLASS - 2 | BROKEN BAROMETRIC DEVERTER, NO SPILL SWITCH. NO MANUAL RESET LOW WATER CUT OFF | $0 | $0 | Dec 16, 2021 |
| Jan 14, 2020 | 38272155K | RESOLVE | CLASS - 1 | 42M07:42-M-07-NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 ... | $1,250 | $0 | Oct 15, 2020 |
| Jan 14, 2020 | 38272153R | RESOLVE | CLASS - 1 | 42M07:42-M-07-NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 ... | $1,250 | $0 | Oct 15, 2020 |
| Jan 14, 2020 | 38272154Z | RESOLVE | CLASS - 1 | 42M07:42-M-07-NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 ... | $1,250 | $0 | Oct 15, 2020 |
| Nov 15, 2019 | 37016150M | RESOLVE | CLASS - 2 | 27-929.1 A.C. 27-929.1,FAILURE TO COMPLETE THE INSTALLATION OF A FULL SYSTEM OF AUTOMATIC SPRINKLERS AND FILE A FINAL... | $1,250 | $0 | Oct 15, 2020 |
| Oct 15, 2018 | 37013728X | RESOLVE | CLASS - 2 | FALIURE TO SUBMIT A REQUIRED CYCLE 8B REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALL AND APPUR... | $1,250 | $0 | Jun 27, 2019 |
| Aug 21, 2017 | 38256693H | RESOLVE | CLASS - 2 | 67L10,16F1,59BB15,52B14,68B7. 67-2WAY COMMUNICATION DEFECTIVE; 16-HOISTWAY DOOR 19 FL ADJUST; 59-BRAKE MAINTENANCE TA... | $500 | $0 | Apr 19, 2018 |
| Jan 20, 2016 | 35154524K | ACTIVE | CLASS - 2 | OCCUPANCY CONTRARY TO THAT ALLOWED BY THE C OF O OR BLDG DEPT RECORDS.WORK NOTED:AS PER C OF O #8913.2BD FL TO 18TH F... | $1,200 | $0 | Mar 10, 2016 |
| Nov 22, 2013 | 35073633P | RESOLVE | CLASS - 2 | WORK W/O A PERMIT. WORK NOTED: HAVING ERECTED FULL HEIGHT PARTITIONS ON 2ND FL TO CREATE 8 TIERS W/NEW ELECTRICAL WOR... | $800 | $0 | Jan 9, 2014 |
| Mar 12, 2012 | 34944102K | RESOLVE | CLASS - 2 | SIDEWALK SHED DOES NOT MEET DOB CODE SPECIFICATIONS. NOTED: SIDEWALK SHED ROOF IS FULL OF DEBRIS & USED AS STORAGE FO... | $2,400 | $0 | Oct 25, 2012 |
| May 11, 2010 | 38210441H | RESOLVE | CLASS - 2 | 98M07,99M07,100X10,70P16,39X10,39Q03. 100- VENTILATION FAN IN MR INOPERATIVE, REPAIR. 70- NO ACCESS TO PIT, STORE FOR... | $500 | $0 | Jul 1, 2010 |
| Mar 20, 2009 | 32066481K | RESOLVE | CLASS - 3 | 6A.50D.50A.FULTON VT BER 10HP NB63877 GAS FIRED 1992 6A SLOW STEAM LEAKAGE AT THE SAFETY VALVE REPLACE 50A NO STRUCTU... | $0 | $0 | May 14, 2009 |
| Mar 20, 2009 | 32066480Z | RESOLVE | CLASS - 3 | 36 FULTON VT BOILER 10HP NB64401 GAS 1992 36 REFERENCED BOILER DESIGNATED NYC 10532701 WAS REMOVED FROM ITS ACTIVE LO... | $0 | $0 | May 14, 2009 |
| Feb 12, 2008 | 32055807H | RESOLVE | Non-Hazardous | 50A,B,C,18A,B.FULTON VT BOILER,15HP,NB 47761,GAS, 1985.50A-NO GAUGE GLASS DRAIN LINE & SHUT OFF VALVE.50B-IMPROPER AR... | $0 | -$180 | Apr 3, 2008 |
| Feb 12, 2008 | 32055803K | RESOLVE | Non-Hazardous | 48A,B,50A. FULTON VT BOILER,10HP,NBN 43906,GAS, 1983.50A-BOILER ROOM DIRTY & CONGESTED. CLEAN & CLEAR ENCLOSURE FOR C... | $2,500 | $0 | Apr 3, 2008 |
| Feb 12, 2008 | 32055806X | RESOLVE | Non-Hazardous | 50A,B,C,18A,B.FULTON VT BOILER,15HP,NB 34872,GAS,1978.50A-NO DRAIN LINE ON THE GAUGE GLASS ASSEMBLY.50B-IMPROPER ARRA... | $0 | -$180 | Apr 3, 2008 |
| Feb 12, 2008 | 32055802Z | RESOLVE | Non-Hazardous | 50A,B. FULTON VT BLR,10 HP,NB 63877,GAS, 1992.50A-SCALE ACCUMULATION,CORROSION & LEAKAGE AT HANDHOLES.CLEAN,FLUSH BOI... | $0 | $0 | Apr 3, 2008 |
| Feb 12, 2008 | 32055804M | RESOLVE | Non-Hazardous | 50A,B,C. FULTON V.T. BLR,10HP, NB 64964,GAS.50A-CORROSION & LEAKAGE ATUPPER HANDHOLE.CLEAN & RE-GASKET OPENINGS.50B-I... | $180 | $0 | Jul 17, 2008 |
| Jun 1, 2007 | 38166574X | RESOLVE | Non-Hazardous | 83X10.83-RETURN TO SERVICE.86-PROVIDE | $0 | $0 | Jul 26, 2007 |
| Sep 23, 2005 | 38154914P | RESOLVE | Non-Hazardous | 67I10. 67-I-10 REPAIR RAIL FIRST PLATE TOP OF SHAFTWAY RIGHT SIDE. | $350 | $0 | Nov 10, 2005 |
| Dec 28, 2004 | 38149122K | RESOLVE | Non-Hazardous | 85BB05 FILE AND PERFORM 5 YEAR TEST | $180 | $0 | Jul 7, 2005 |
| Jun 29, 2004 | 32045200M | RESOLVE | Non-Hazardous | 50A/50B FULTON VERTIBRATES BLR, 10HP, NB 64964, GAS, 1992 50A NO DISCHARGE PIPE ON THE SAFETY VALVE. 50B NO SECONDARY... | $0 | $0 | Aug 19, 2004 |
| Jun 29, 2004 | 32044874Y | RESOLVE | Non-Hazardous | 18A/48AB 50A/50B FULTON V.T. BLR, 10HP, NB 71565 GAS 1995 50A INADEQUATE FLUE PIPE SUPPORT SYSTEM, INSTALL HEAVY DUTY... | $180 | $0 | Aug 19, 2004 |
| Jun 29, 2004 | 32044873M | RESOLVE | Non-Hazardous | 50 FULTON V.T. BOILER, 10HP, NB 64401, GAS, 1992 50 INADEQUATE STRUCTURAL SUPPORT ON THE FLUE PIPE. INSTALL A HEAVY D... | $180 | $0 | Aug 19, 2004 |
| Jun 29, 2004 | 32044871Z | RESOLVE | Non-Hazardous | 44C/50A 50B/50C FULTON V.T. BLR, 10HP, NB 63877, GAS-FIRED, 1992 50A NO APPROVED HANGER ON THE FLUE PIPE.INSTALL ROD ... | $0 | $0 | Aug 19, 2004 |
| Jun 29, 2004 | 32044870R | RESOLVE | Non-Hazardous | 34A/50 FULTON V.T. BOILER, 10HP, NB 43906, GAS, 1983 50 SECONDARY LOW WATER CUT OFF MANUAL RESET SWITCH DISCONNECTED.... | $180 | $0 | Aug 19, 2004 |
| Jun 29, 2004 | 32044872K | RESOLVE | Non-Hazardous | 50A/50B 50C FULTON V.T. BOILER,6HP,NB 41982,GAS,1982 50A LOOSE STRUCTURAL SUPPORT AND MISALIGNMENT OF FLUE PIPE. RE-A... | $0 | $0 | Aug 19, 2004 |
| Mar 30, 2004 | 32044502N | RESOLVE | Non-Hazardous | 36/44C 44C-GLASS MISSING ON PIESSURE STEAM GAUGE | $0 | $0 | May 20, 2004 |
| May 21, 1998 | 32015307P | RESOLVE | Non-Hazardous | 36-BOILER NOT REGISTERED. | $400 | $0 | Aug 6, 1998 |
| Sep 23, 1997 | 32015141Y | RESOLVE | Non-Hazardous | — | $400 | $0 | Jan 15, 1998 |
| Sep 23, 1997 | 32015140M | RESOLVE | Non-Hazardous | — | $400 | $0 | May 21, 1998 |
| Aug 25, 1997 | 38063232Y | RESOLVE | Non-Hazardous | 75UXO02X57O35M05E 75-PROVIDE 5 YEAR TEST X-CLEAN CAR TOP 02-ALARM BELL NOT WORKING 52-CLEAN PIT 35-COVER ON MOTOR WIR... | $0 | $0 | Nov 20, 1997 |
| Aug 25, 1997 | 38063236L | RESOLVE | Non-Hazardous | 75U37G52M18M57OXO14M 75-PERFORM 5 YEAR TEST 37-REMOVE WIRES ON CONTROLLER FUSES 52-BRAKE WIRES OUT OF BOX NO COVER 18... | $0 | $0 | Nov 20, 1997 |
| Aug 25, 1997 | 38063237N | RESOLVE | Non-Hazardous | 75U37G52M14MXO57O 75-PERFORM 5 YEAR TEST 37-REMOVE WIRES FROM CONTROLLER FUSES 52-PROVIDE COVER FOR BRAKE WIRE BOX 14... | $0 | $0 | Nov 20, 1997 |
| Aug 25, 1997 | 38063238P | RESOLVE | Non-Hazardous | 75U37G57O14MXO 75-PERFORM 5 YEAR TEST 37-REMOVE WIRE ON CONTROLLER FUSE 57-CLEAN PIT 14-PROVIDE CERTIFICATE FRAME X-C... | $0 | $0 | Nov 20, 1997 |
| Aug 25, 1997 | 38063239R | RESOLVE | Non-Hazardous | 75U37G50M57O14MX0 75-PERFORM 5 YEAR TEST 37-REMOVE WIRE FROM FUSES 50-PROVIDE COVER FOR BRAKE WIRES BOX 57-CLEAN PIT ... | $0 | $0 | Nov 20, 1997 |
| Aug 25, 1997 | 38063240Y | RESOLVE | Non-Hazardous | 73P73-PROVIDE ACCESS TO SUSPECT DIVICE. | $0 | $0 | Nov 20, 1997 |
| Aug 25, 1997 | 38063235J | RESOLVE | Non-Hazardous | 75U57O 75-PERFORM 5 YEAR TEST 57-CLEAN PIT. | $0 | $0 | Nov 20, 1997 |
| Aug 25, 1997 | 38063233X | RESOLVE | Non-Hazardous | 75UXO02X57O35M 75-PERFORM 5 YEAR X-CLEAN CAR TOP 02-ALARM BELL NOT WORKING 57-CLAAN PIT 35-COVER ON MOTOR WIRES MISSING. | $0 | $0 | Nov 20, 1997 |
| Aug 25, 1997 | 38063234H | RESOLVE | Non-Hazardous | 75U02XX035M 75-PERFORM 5 YEAR TEST 02-ALARM BELL NOT WORKING X-CLEAN PIT. 35-COVER ON MOTOR WIRES MISSING. | $0 | $0 | Nov 20, 1997 |
| Jul 7, 1995 | 34106912J | RESOLVE | Non-Hazardous | WORK WITHOUT A PERMIT--HAVING INSTALLED PARTITIONS & A SUSPENDED CEILING WITHOUT A PERMIT. HAVING A SUSPENDED CEILING... | $700 | $0 | Aug 24, 1995 |
| Mar 23, 1994 | 32012504K | RESOLVE | Non-Hazardous | 36. | $0 | $0 | May 5, 1994 |
| Dec 6, 1993 | 32010531R | RESOLVE | Non-Hazardous | 36, H.P. STEAM BOILER ON 12TH FL- FULTON- NOT REGISTERED | $100 | $0 | Feb 10, 1994 |
| May 26, 1993 | 34087463M | RESOLVE | Non-Hazardous | FAILURE TO PROVIDE ADEQUATE EMERGENCY POWER EXIT LIGHT IN TENANTS SPACE AND FREIGHT ELEVTR FOYERS THROUGHOUT ALL FLOO... | $0 | $0 | Sep 23, 1993 |
| Jan 15, 1993 | 34072716J | RESOLVE | Non-Hazardous | FAILURE TO PROVIDE ADEQUATE EMERGENCY POWER EXIT LIGHTS ON TENANT FL. AREAS. DIRECTIONAL EXIT SIGNS NEEDED ON FLOOR A... | $0 | $0 | Aug 4, 1994 |
| Apr 15, 1992 | 38024852N | RESOLVE | Non-Hazardous | 28H,46H | $0 | $0 | Jun 25, 1992 |
| Apr 15, 1992 | 38024853P | RESOLVE | Non-Hazardous | 73M, #73 FAILURE TO PROVIDE FIREMAN SERVICE OPERATION AS PER SECTION -27-996-02 OF BUILDING CODE. FOR 4 SERVICE ELV'S... | $150 | $0 | Aug 27, 1992 |