Issued Violation Status Severity Description Penalty Balance due Hearing
Aug 1, 2023 35671094P RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING EXTERIOR WALLS FACADE AND APPURTENANCES: AT THE TIME OF INSPECTION OBSERVED CRACK COPING... $0 $0 Mar 14, 2024
Oct 5, 2022 39071482N RESOLVE CLASS - 1 CLASS 1 CAR CEASE USE ,DOOR ZONE RESTRICTOR NOT WORKING TAMPERED WITH OR DISABLED (CU) 2/X/10 ALARM BELL INSIDE CAR D... $0 $0 Aug 24, 2023
Mar 3, 2021 35548981H ACTIVE CLASS - 2 FAILURE TO MAINTAIN BLDG EXTERIOR WALLS/FACADE & APPURTENANCES.NOTE:ATTHE TIME OF INSPECTION OBSERVED AT EXPO #1 SOUT... $1,250 $0 Aug 12, 2021
Nov 29, 2018 38266129X RESOLVE CLASS - 2 2X10,16D4,16B7-2X10)PROVIDE OUTSIDE COMMUNICATION. 16D4)PATCH HOLES IN HOISTWAY DOORS. 16B7)PROVIDE GUARD FOR TOP OF ... $0 $0 Mar 7, 2019
Apr 6, 2018 38262051R RESOLVE CLASS - 2 97X10 RESTORE TO SERVCIE AS PER CODE OF NYC DOB IMMEDIATELY. $625 $0 May 24, 2018
Jan 24, 2018 35264847M RESOLVE CLASS - 1 FAILURE TO MAINTAIN EXTERIOR BUILDING FACADE & APPURENTCES.AS NOTED:EXPOSURE 1,SPALLED TERRACOTTA WATER TABLE,CRACKS ... $0 $0 Jun 14, 2018
May 3, 2017 38254672J RESOLVE CLASS - 1 5X7,2X10,24B10,39B10. 5X7-DOOR RESTRICTOR INOPERATIVE PROVIDE BRACKETON DOOR TRACK; 2X10-REPAIR ALARM BELL INOPERATIV... $2,500 $0 Jun 22, 2017
Nov 30, 2016 38251509X RESOLVE CLASS - 2 56Y13,61M7,42N9,40M7. 56Y13-HAVY OIL UNDER MACHINE SEAL; 61M7-PROVIDESERVICE STICKER ON MAIN LINE;42N9-REMOVE BLOCK R... $0 $0 Jan 19, 2017
Nov 30, 2016 38251507M RESOLVE CLASS - 1 7X1,2B10,24B10,59B1,40B15. 7X11-DOOR RESTRICTOR IS INOPERATIVE ADJUST2B10-ALARM BELL INSUFFICIENT DOES NOT RING REPAI... $1,000 $0 Feb 16, 2017
Nov 30, 2016 38251510N RESOLVE CLASS - 1 59B10,7X1,2B10,40B7. 59B10-ELECTRICAL BREAK CONTRACT IS MISSING ONE CONTACT; 7X1-DOOR RESTRICTOR IS INOPERATIVE ADJUS... $1,000 $0 Feb 16, 2017
Aug 31, 2015 38238509J RESOLVE CLASS - 2 97X10,100M05, 97X10-DEVICE OUT OF SERVICE,REPAIR TO BRING BACK IN SERVICE; 100M07-NTC ID TAG MISSING IN CAR PROVIDED ... $250 $0 Oct 15, 2015
Aug 18, 2015 38238531X RESOLVE CLASS - 2 97X10 ELEVATOR NOT WORKING. RETURN TO SERVICE. $0 $0 Oct 8, 2015
Aug 18, 2015 38238530Y RESOLVE CLASS - 2 02L10 OUTSIDE COMMUNICATION DEFECTIVE. PHONE IS NOT CONNECTED. PROVIDECOMMUNICATION. $0 $0 Oct 8, 2015
Jan 11, 2011 38214474M RESOLVE CLASS - 2 97X10 98BB05 98M07 99BB05 99M07 97X-RETURN TO SERVICE 98BB-AS PER DOB RECORDS 99BB-AS PER DOB RECORDS $250 $0 Mar 3, 2011
Oct 19, 2010 38211945X ACTIVE CLASS - 2 97X10 - REPAIR ELEVATOR AND RESTORE TO SERVICE $500 $0 Dec 9, 2010
Sep 16, 2010 38212909N ACTIVE CLASS - 2 97/X/#/37X#-ENTIRE DEVICE INOPERATIVE-RESTORE DEVICE BACK TO SERVICE $500 $0 Nov 18, 2010
Aug 9, 2010 38210992Y ACTIVE CLASS - 2 97/X/10-97-X-10-ELEVATOR DEVICE 1P15541RETURN TO SERVICE.RECURRING CONDITION.PRIOR ECB VIOLATION 38211110H $500 $0 Sep 30, 2010
Jun 29, 2010 38208221N ACTIVE CLASS - 2 97X10 - 97 RESTORE ELEVATOR BACK TO SERVICE $500 $0 Aug 19, 2010
Jun 1, 2010 38211109K RESOLVE CLASS - 3 42B11,45M13,41B01,67X10,12L11. 42B- REPLACE CONTROLLER DOOR PANEL WITHCITY ID TAG. 15M- PROPERLY CALIBRATE GOVERNOR &... $0 $0 Jul 22, 2010
Jun 1, 2010 38211110H RESOLVE CLASS - 3 12L11,67X10,42B11,56Y11. 12L- REPLACE DEFECTIVE LIGHT BULBS. 42B- REPLACE CONTROLLER. DOOR PANEL WITH CITY ID TAG. 56... $0 $0 Jul 22, 2010
Jun 1, 2010 38211108Z ACTIVE CLASS - 2 97X10. 97X- DEVICE FOUND INOPERATIVE- RESTORE DEVICE BACK TO SERVICE CALL DOB FOR INSPECTION $500 $0 Jul 22, 2010
Jan 11, 2010 38208206P ACTIVE CLASS - 2 97.97 ELEVATOR UNDER C.U RECURRING CONDITION RESTORE AND REPAIR ELEVATOR BACK TO SERVICE $1,250 $0 Mar 4, 2010
Dec 4, 2009 38205824Z ACTIVE CLASS - 2 97X10.97 RECURRING CONDITION RESTORE BACK TO SERVICE $500 $0 Jun 24, 2010
Nov 13, 2009 38205820L ACTIVE CLASS - 2 97X10.RESTORE ELEVATOR BACK TO SERVICE RECURRING CONDITION ON C.U $2,500 $0 May 20, 2010
Oct 29, 2009 38205819Y ACTIVE CLASS - 2 97X10. 97-UNDER CEASE USE. RECURRING CONDITION RESTORE ELEV BACK TO SERVICE $500 $0 Dec 24, 2009
Oct 19, 2009 38205815R ACTIVE CLASS - 2 97X10.97 RECURRING CONDITION RESTORE ELEVATOR BACK TO SERVICE $500 $0 Dec 17, 2009
Sep 8, 2009 38205294K ACTIVE CLASS - 1 CU 97L10 44H10/11 60Q03 42L10 69M07 12Q03 46M07 64A15 97-CAR STARTING TO OVERSPEED IN DOWN DIRECTION W/ CAPACITY REPA... $1,000 $0 Oct 29, 2009
Sep 8, 2009 38205295M RESOLVE CLASS - 1 CEASE USE ITEM 59X10 - BRAKE MONITOR INSPECTIVE REPAIR CALL 212-566-5542 TO OBTAIN TO SERVICE $1,000 $0 Oct 29, 2009
Mar 31, 2009 32066488N RESOLVE CLASS - 3 36,50A,B,C. FULTON VT BOILER,10HP,NB 82217,GAS FIRED,1998.36-REFERENCED HIGH PRESSURE STEAM BOILER IN OPERATION IS NO... $0 $0 May 21, 2009
Mar 17, 2008 32056161M ACTIVE Non-Hazardous 50A,B,C,D,E,48A,B.HOT SHOT ELECTRIC HP STM BLR,4 SRW.50A-BLOWDOWN LINEREDUCED.INCREASE BLOWDOWN LINE TO UNIFORM SIZE.... $2,500 $0 May 8, 2008
Mar 17, 2008 32056160K RESOLVE Non-Hazardous 50A,B,C.FULTON VT BOILER,10HP,NB 82217,GAS,1998.50A-IMPROPER ARRANGEMENT OF THE BLOWDOWN VALVES.INSTALL SCREW TYPE (S... $0 $0 May 8, 2008
Mar 4, 2008 32055977K ACTIVE Non-Hazardous 50A,B.FULTON VT BOILER, 10HP,NB 72886, GAS 1995.50A-CLEAN OUT COVER ONFLUE PIPE MISSING.REPLACE.50B-IMPROPER ARRANGEM... $180 $0 Apr 24, 2008
Mar 4, 2008 32055978M RESOLVE Non-Hazardous 50.FULTON VT BOILER,10HP,NB 64736,GAS,1992.50-NO STRUCTURE SUPPORTS ONTHE LOADED FLUE PIPE SYSTEM.INSTALL A HEAVY DUT... $0 $0 Apr 24, 2008
Mar 4, 2008 32055979Y ACTIVE Non-Hazardous 36,50A,B.(REIMERS) ELECT MINIA HP STON BLR 8 KW 051909.36-REFERENCED ELECTRIC MINIATURE HIGH PRESSURE STEAM BOILER IS... $350 $0 Aug 22, 2008
Feb 21, 2008 38181337H RESOLVE Non-Hazardous 84R04.84-DOOR & GATE BYPASS SWITCHES IN CONTROLLER OPERATIONS,DISARM SWITCHES. $0 $0 Apr 28, 2008
Feb 21, 2008 38181336X ACTIVE Non-Hazardous 84R09,84L10.84-DOOR & ( )SWITCHES IN CONTROL OPERATIONS:( )SWITCH.84-WHY DOES PULLING M/L DISCONNECT ON THIS CAR MAKE... $0 $0 Feb 13, 2009
Dec 11, 2006 38162942M RESOLVE Non-Hazardous 84R09-HOISTWAY DOOR& GATE BYPASS SWITCHES OPERATIONAL IN CONTROLLER REMOVE SWITCHED FROM OPERATION $0 $0 Jan 25, 2007
Dec 11, 2006 38162274X RESOLVE Non-Hazardous 84R09 REMOVE ILLEGAL HOISTWAY DOOR & GATE BY PASS SWITCHES. $0 $0 Jan 25, 2007
Apr 25, 2006 32049965M ACTIVE Non-Hazardous BQ9,36,44C,50. 1993 FULTON NB66457.50)FIRE DOOR ON BOILER ROOM HAS LOUVERS THAT MUST BE CONVERTED. $850 $0 Nov 2, 2006
Apr 25, 2006 32049964K ACTIVE Non-Hazardous BQ9,50A,50B,36.1994 FULTON NB 72886.50A)PIPE DOWN GLASS DRAIN VALVE. 50B)HOLES IN WALL. $680 $0 Jun 15, 2006
Apr 25, 2006 32049967X ACTIVE Non-Hazardous 6A,BQ9,36,50. HOT SHOT SUSSMAN 69580.6A) SET PRESSURE ON SAFETY VALVE IS 150PSI MINATURE BOILER IS RATED FOR 100PS.50... $400 $0 Jun 29, 2006
Apr 25, 2006 32049963Z ACTIVE Non-Hazardous BQ9,50A,36,50D.1995 FULTON NB 72961.50A)HOLE IN WALL BY WINDOW.50B) HOLE IN WALL BY COMPRESSOR. $5,000 $5,000 Jun 15, 2006
Apr 25, 2006 32049966Y ACTIVE Non-Hazardous 36,50A,50B,50C,50D.1988 FULTON NB 39169.50A)REPLACE MISSING RODS ON GLASS ASSEMBLY.50B)BOILER DOOR IS WOOD.50C)INSTAL... $2,500 $0 Oct 12, 2006
Dec 30, 2005 38156365K RESOLVE Non-Hazardous 17H10. (17-H-10)REPAIR HOISTWAY DOOR GIBS. $180 $0 Feb 16, 2006
Feb 11, 2005 32046232L RESOLVE Non-Hazardous 50A/50B. 1992 FULTON NATL BD 64381. 50A SEAL ALL HOLES ABOVE DOOR. 50B REPAIR DOOR IT IS FALLING DOWN WHEN YOU TRY TO... $0 $0 Mar 31, 2005
Jun 18, 2004 32044746J ACTIVE Non-Hazardous 50A/50B FULTON V.T. BOILER, 10 HP, NB 63259, GAS-FIRED, 1991 50A IMPROPER ARRANGEMENT OF BLOWDOWN VALVES. REPLACE BAR... $180 $0 Sep 2, 2004
Jun 18, 2004 32044744X RESOLVE Non-Hazardous 50 FULTON V.T. BOILER, 10HP, NB64736, GAS-FIRED, 1992 50 IMPROPER ARRANGEMENT OF BLOWDOWN VALVES. REPLACE EXISTING BA... $0 $0 Aug 5, 2004
Jun 18, 2004 32044745H ACTIVE Non-Hazardous BQ9/18AB 44C/50A 50B FULTON V.T. BLR, 6HP, NB 32349, GAS-FIRED, 1976 REFERENCED BOILER WAS REMOVED FROM 262 WEST 38 S... $850 $0 Aug 5, 2004
Jun 18, 2004 32044743Y ACTIVE Non-Hazardous 50A/50B 50C FULTON V.T. BOILER, 10HP, NB65468, GAS-FIRED, 1992 50A IMPROPER ARRANGEMENT OF BLOWDOWN VALVES. REPLACE E... $180 $0 Aug 5, 2004
May 8, 2002 32033833Y ACTIVE Non-Hazardous 16, 36, 49. BQ9 27-147 FUCION HIGH PRESSURE BOILER FBOLOA NB #63259 BUILT 1991 INSTALLED WITHOUT A PERMIT FROM D.O.B.... $850 $0 Sep 19, 2002