ECB violations

257-267 West 39 Street, Manhattan • Block 00789 • Lot 0009

103 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Jul 1, 2025 37036019P ACTIVE CLASS - 2 FAILURE TO FILE REQUIRED ANNUAL BOILER INSPECTION REPORTS FOR LOW-PRESSURE BOILER 10000829079N0001 IN ACCORDANCE WITH... $3,125 $3,125 Oct 16, 2025
Jun 7, 2023 39088230H RESOLVE CLASS - 1 I OBSERVED ON ROOFTOP AREA TWO NEWLY INSTALL PRESSURE VESSELS TANKS FOR BUILDING SPRINKLER SYSTEM. AS PER ASME CODE D... $0 $0 Jan 25, 2024
Mar 23, 2022 39058622J RESOLVE CLASS - 3 GAS METER ROOM FRESH AIR DUCT 1/2 CLOGGED/OUTSIDE COMBUSTION AIR INLET BLOCKED BY ROLL DOWN GATE WITHOUT OPENINGS/OUT... $0 $0 May 12, 2022
Mar 23, 2022 39058621H RESOLVE CLASS - 3 KING VALVE LEAKING ONTO BOILER/STEAM MAIN ISOLATION VALVE LEAKING ABOVE THE RED GAS TRAIN SHUTOFF VALVE;CORRECT VIOLA... $500 $0 Jan 12, 2023
Sep 29, 2020 37020272M RESOLVE CLASS - 2 SEC. 27-929.1 FAILURE TO COMPLETE THE INSTALLATION OF A FULL SYSTEM OFAUTOMATIC SPRINKLERS & FILE A FINAL SPRINKLER R... $0 $0 May 13, 2021
Aug 3, 2020 37020123Z RESOLVE CLASS - 2 FAILURE TO COMPLY WITH COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION#39004998Y ISSUED ON 7/2/2019,AND TO FILE A... $1,250 $0 Mar 10, 2022
Nov 15, 2019 37016157P ACTIVE CLASS - 2 A.C.27-929.1 FAILURE TO COMPLETE THE INSTALLATION OF A FULL YSTSEM OF AUTOMATIC SPRINKLERS AND FILE A FINAL SPRINKLER... $1,250 $0 Feb 13, 2020
Jul 16, 2019 39006177X RESOLVE CLASS - 2 SUSSMAN ELECTRIC BOILER MODEL#ES24 24KW NB#31827 BASEMENT WEST, UNREGISTERED , MAINTAIN BOILER $625 $0 Feb 13, 2020
Jul 16, 2019 39006158K RESOLVE CLASS - 2 ELECTRIC REIMERS MODEL#AR8 8KW NB#102854 9 FLOOR WEST UNREGISTERED , MAINTAIN BOILER $310 $0 Sep 12, 2019
Jul 16, 2019 39006137L RESOLVE CLASS - 2 FULTON FB010A NB#73511 11 FLOOR WEST FAILURE TO MAINTAIN, MISSING PIPE INSULATION, CO DETECTOR, FLUE & INDUCER SUPPOR... $0 $0 Sep 12, 2019
Jul 16, 2019 39006162N RESOLVE CLASS - 2 PACIFIC ELECTRIC BOILER MODEL# PSE-12 KW12 NB#13917 10 FLOOR WEST, UNREGISTERED , MAINTAIN BOILER $310 $0 Sep 12, 2019
Jul 16, 2019 39006132M RESOLVE CLASS - 2 FULTON FB015A NB#72438 9 FLOOR EAST, FAILURE TO MAINTAIN CO DETECTOR, SPILL SWITCH, PIPE INSULATION, MISSING SUPPORT ... $0 $0 Sep 12, 2019
Jul 16, 2019 39006143H ACTIVE CLASS - 2 FULTON FB010A NB#62216 12 FLOOR WEST FAILURE TO MAINTAIN, MISSING PIPE INSULATION, CO DETECTOR, FLUE SUPPORT, SECURE ... $625 $0 Sep 12, 2019
Jul 2, 2019 39004991L RESOLVE CLASS - 2 HP FULTON VT FB-010-A NB#66734 BTU'S 470000 1993 STEAM GAS 13FL EAST FAILURE TO MAINTAIN, MISSING PIPE INSULATION, FL... $0 $0 Aug 22, 2019
Jul 2, 2019 39004993P RESOLVE CLASS - 2 HP FULTON VT FB-006-A NB#61794 BTU'S 200000 1994 STEAM GAS BOILER 15FL WEST FAILURE TO MAINTAIN, MISSING PIPE INSULAT... $310 $0 Aug 22, 2019
Jul 2, 2019 39004997M RESOLVE CLASS - 2 XP FULTON VT FB-010-A NB#76359 BTU,S 420000 15FL EAST 1996 STEAM GAS BOILER, FAILURE TO MAINTAIN, MISSING PIPE INSULA... $0 $0 Aug 22, 2019
Jul 2, 2019 39004995Z RESOLVE CLASS - 2 HP FULTON VT FB-015-A NB#71615 3RD FL EAST BTU'S 630000 1994 STEAM GAS, FAILURE TO MAINTAIN, CO DETECTOR REQUIRED, CL... $310 $0 Aug 22, 2019
Jul 2, 2019 39004990J RESOLVE CLASS - 2 HP FULTON VT FB-010-A NB#76359 BTU'S 420000 1996 STEAM GAS BOILER 15FL EAST FAILURE TO MAINTAIN MISSING PIPE INSULATI... $310 $0 Aug 22, 2019
Jul 2, 2019 39004998Y ACTIVE CLASS - 2 HP MINIATURE ELECTRICAL BOILER REIMER RH20 20KW 13FL WEST STEAM GAS, FAILURE TO MAINTAIN, CORROSION ON WATER FEED CHE... $625 $0 Aug 22, 2019
Jul 2, 2019 39004992N RESOLVE CLASS - 2 XP FULTON VT FB-015-A NB#69201 BTU'S690000 1994 STEAM GAS BOILER 7FL WEST, FAILURE TO MAINTAIN MISSING PROPER SUPPORT... $0 $0 Aug 22, 2019
Jul 2, 2019 39004996K RESOLVE CLASS - 2 XP FULTON VT FB-010-A NB#65022 BTU'S 470000 1992 STEAM GAS BOILER 16FLEAST FAILURE TO MAINTAIN SECURE PROBE ELECTRODE... $310 $0 Aug 22, 2019
Dec 14, 2018 35374517R RESOLVE CLASS - 2 WORK W/O A PERMIT. AT 7TH FL REMOVED PARTITION WALLS IN VARIOUS LOCATIONS TO COMBINE FACTORY ON WEST SIDE TO THE EAST... $625 $0 Apr 4, 2019
Nov 30, 2018 35347988J RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NO FIRE STOPPING PER BC 712.3; 27-345 IN MECHANICAL AND BOILER... $1,250 $0 May 23, 2019
Nov 30, 2018 35347987H RESOLVE CLASS - 1 BC1011 ILLUMINATED EXIT SIGN REMOVED AT 9TH FLOOR (WEST) EXIT DOOR. ACCESS TO EXITS NOT MARKED BY READILY VISIBLE EXI... $2,500 $0 Jan 31, 2019
Nov 30, 2018 35347985Y ACTIVE CLASS - 1 OCCUPANCY CONTRARY TO THAT ALLOWED BY THE C/O #10865. ILLEGAL OCCUPAN CY NOTED: 10TH FLOOR (FACTORY) EAST, CONVERTED/... $2,500 $0 May 23, 2019
Nov 30, 2018 35347989L RESOLVE CLASS - 1 FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAYS TO STAIRWAYS AND EXITDOOR WAY THROUGHOUT BUILDING FROM FLOORS 2 TO 1... $1,250 $0 Jan 31, 2019
Nov 30, 2018 35347986X RESOLVE CLASS - 1 WORK W/O A PERMIT. WORK NOTED: AT 10TH FLOOR (EAST) ERECTED FULL HEIGHT PARTITIONS TO CREATE 14 STUDIO/OFFICES. AT 4T... $2,500 $0 May 23, 2019
May 25, 2018 35318932H RESOLVE CLASS - 2 FAILURE TO MAINTAIN EXTERIOR BLDG NORTH ELEV EXP#3 & SOUTH ELEV EXP#1 OBSERVED CRACKED WINDOW GLASS,RUSTING WINDOW FR... $1,250 $0 Apr 4, 2019
May 18, 2018 37011350Y ACTIVE CLASS - 2 FAILURE TO SUBMIT ACCEPTABLE 8TH ROUND REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALLS AND APP... $1,250 $0 Mar 21, 2019
Feb 23, 2008 32055817L ACTIVE Non-Hazardous 36. REIMERS ELECTRIC MINIATURE HP STOP BLR. 20 LW. (36) REFRENCED HIGHPRESSURE ELECTRIC STEAM BOILER IS NOT REGISTERE... $2,500 $0 Apr 10, 2008
Feb 23, 2008 32055815H RESOLVE Non-Hazardous 1650. FULTON V.T BOILER, 15HO NB72438 GAS 1996. 16 NYC DOB BOILER INSPCERT NOT POSTED IN BOILER ROOM. BOILER JURISDIC... $10,000 $0 Apr 10, 2008
Feb 23, 2008 32055819P RESOLVE Non-Hazardous 50A. FUCTON V.T BOILER 6 HP, NB61794 GAS 1991. 50A SECONDARY LOW CUTOFF MANUAL RESET SWITCH MISSING IN BOILER CONTROL... $0 $0 Apr 10, 2008
Feb 23, 2008 32055816J RESOLVE Non-Hazardous 18AB50, FULTON VT BOILER 6 HP NB45294 GAS 1984. 18AB CORRODED & LEAKING HAND HOLES. CLEAN & RE-GASKET OPENINGS. 50 ST... $180 $0 Apr 10, 2008
Feb 16, 2008 32055813Y RESOLVE Non-Hazardous 50. FULTON V.T BOILER, 15HP NB 73659 GAS 1995. 50 AIR COMPRESSOR MOTORDRIVE SHAFT NOT PROTECTED IN THE BOILER ROOM. I... $0 $0 Apr 10, 2008
Feb 16, 2008 32055814X RESOLVE Non-Hazardous 50. FUCTON V.T BOILER,15HP,NB82750 GAS 1998 (50) DIAL GLASS MISSING ONSTEAM PRESSURE GAUGE REPLACE DEFECTIVE GAUGE. $0 $0 Apr 10, 2008
May 3, 2006 32050077M RESOLVE Non-Hazardous 48B/50. 1991-FULTON NB #62567. 50)REPAIR DAMAGED CASEING AROUND THE TOP HANDHOLE. $0 $0 Jun 22, 2006
Apr 24, 2006 32049962R RESOLVE Non-Hazardous BQ9,43B,50B,36,50A,50C/1991 FULTON N.B#62216/50A-BOILER RM DOOR MADE OF WOOD/50B-ADD SLOW OPENING VALVE TO THE BOTTOM... $680 $0 Jun 8, 2006
Apr 24, 2006 32049960N RESOLVE Non-Hazardous BQ9/1996 FULTON N.B. 76359 $0 $0 Jul 6, 2006
Apr 24, 2006 32049961P RESOLVE Hazardous BQ9,36,32A/MINITURE BLR RIMERS ELECTRIC N.B. 3659 $850 $0 Jun 8, 2006
Jun 23, 2004 32044857M RESOLVE Non-Hazardous 50A,50B.FULTON V.T. BOILER,20HP,NB83778,GAS-FIRED,1999.50A-SECONDARY LOW WATER CUT OFF MANUAL RESET SWITCH NOT FULLY ... $0 $0 Aug 12, 2004
Jun 23, 2004 32044859X RESOLVE Non-Hazardous 50A,50B.FULTON V.T. TBLS BLR,20 HP,NB62567,GAS,1991.50A-NO DISCHARGE PIPE ON THE SAFETY VALVE.50B-IMPROPER ARRANGEMEN... $0 $0 Aug 12, 2004
Jun 23, 2004 32045011N RESOLVE Non-Hazardous 32A,34B,50A,32B,38.1991 FULTON NATL BO 61794.50A-ADD A BLOW OPENING VALVE TO THE BOTTOM BLOW DOWN LINE. $0 $0 Aug 12, 2004
Jun 23, 2004 32044856K RESOLVE Non-Hazardous 44C,50.FULTON VERT. TBLS. BLR.,15HP,NB82750,GAS-FIRED,1998.50-IMPROPER ARRANGEMENT OF BLOWDOWN VALVES ON THE REFERENC... $0 $0 Aug 12, 2004
Jun 23, 2004 32044861P RESOLVE Non-Hazardous 48A,B.50.FULTON V.T. BOILER,10HP,NB73511,GAS FIRED,1995.48A,B- DIRTY AND LEAKING GAUGE GLASS.50-IMPROPER ARRANGEMENT ... $180 $0 Aug 12, 2004
Jun 23, 2004 32044860N RESOLVE Non-Hazardous 50.FULTON V.T. BOILER,10HP,NB65253,GAS-FIRED,1992.50-IMPROPER ARRANGEMENT OF BLOWNDOWN VALVES.INSPEC. SCREW -TYPE ANG... $0 $0 Aug 12, 2004
Jun 23, 2004 32045010L RESOLVE Non-Hazardous 50A,50B,50C,50D,32A,38,BQ9,36.1994 FULTON N.BO 69201.50A-THREADED ENDS ON SAFETY VALVE PIPE DOWN.50B-HOLE IN WALL ABO... $430 $0 Aug 12, 2004
Jun 23, 2004 32044855Z RESOLVE Non-Hazardous FULTON V.T. BOILER,15HP,NB73659,GAS-FIRED,1995.50A-IMPROPER ARRANGEMENT OF BLOWDOWN VALVES ON THE REFERENCED BOILER.I... $0 $0 Aug 12, 2004
Jun 23, 2004 32044858Y RESOLVE Non-Hazardous 5OA,50B.FULTON V.T. BOILER,20HP,NB68930,GAS-FIRED,1999.50A-FRESH AIR INTAKE DUCT TO BURNING RESTING ON THE GAS FUEL T... $0 $0 Aug 12, 2004
Jun 23, 2004 32045012P RESOLVE Non-Hazardous 1984 FULTON NATL. BD 45294 11A> ADD A SLOW OPENING VALVE ON THE BOTTOMBLOWDOWN 50A WIRE A MANUAL RESET CONTROL IN FOR... $2,500 $0 Oct 28, 2004
Jun 23, 2004 32045013R RESOLVE Non-Hazardous BQ9,32A,11A,36,48B,50.REIMOR MINIATURE NATL BO 3659.50-PROVIDE A BALL COCK VALVE ON THE PRESSURE GAUGE. $5,000 $0 Aug 12, 2004