ECB violations
257-267 West 39 Street, Manhattan • Block 00789 • Lot 0009
103 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Jul 1, 2025 | 37036019P | ACTIVE | CLASS - 2 | FAILURE TO FILE REQUIRED ANNUAL BOILER INSPECTION REPORTS FOR LOW-PRESSURE BOILER 10000829079N0001 IN ACCORDANCE WITH... | $3,125 | $3,125 | Oct 16, 2025 |
| Jun 7, 2023 | 39088230H | RESOLVE | CLASS - 1 | I OBSERVED ON ROOFTOP AREA TWO NEWLY INSTALL PRESSURE VESSELS TANKS FOR BUILDING SPRINKLER SYSTEM. AS PER ASME CODE D... | $0 | $0 | Jan 25, 2024 |
| Mar 23, 2022 | 39058622J | RESOLVE | CLASS - 3 | GAS METER ROOM FRESH AIR DUCT 1/2 CLOGGED/OUTSIDE COMBUSTION AIR INLET BLOCKED BY ROLL DOWN GATE WITHOUT OPENINGS/OUT... | $0 | $0 | May 12, 2022 |
| Mar 23, 2022 | 39058621H | RESOLVE | CLASS - 3 | KING VALVE LEAKING ONTO BOILER/STEAM MAIN ISOLATION VALVE LEAKING ABOVE THE RED GAS TRAIN SHUTOFF VALVE;CORRECT VIOLA... | $500 | $0 | Jan 12, 2023 |
| Sep 29, 2020 | 37020272M | RESOLVE | CLASS - 2 | SEC. 27-929.1 FAILURE TO COMPLETE THE INSTALLATION OF A FULL SYSTEM OFAUTOMATIC SPRINKLERS & FILE A FINAL SPRINKLER R... | $0 | $0 | May 13, 2021 |
| Aug 3, 2020 | 37020123Z | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION#39004998Y ISSUED ON 7/2/2019,AND TO FILE A... | $1,250 | $0 | Mar 10, 2022 |
| Nov 15, 2019 | 37016157P | ACTIVE | CLASS - 2 | A.C.27-929.1 FAILURE TO COMPLETE THE INSTALLATION OF A FULL YSTSEM OF AUTOMATIC SPRINKLERS AND FILE A FINAL SPRINKLER... | $1,250 | $0 | Feb 13, 2020 |
| Jul 16, 2019 | 39006177X | RESOLVE | CLASS - 2 | SUSSMAN ELECTRIC BOILER MODEL#ES24 24KW NB#31827 BASEMENT WEST, UNREGISTERED , MAINTAIN BOILER | $625 | $0 | Feb 13, 2020 |
| Jul 16, 2019 | 39006158K | RESOLVE | CLASS - 2 | ELECTRIC REIMERS MODEL#AR8 8KW NB#102854 9 FLOOR WEST UNREGISTERED , MAINTAIN BOILER | $310 | $0 | Sep 12, 2019 |
| Jul 16, 2019 | 39006137L | RESOLVE | CLASS - 2 | FULTON FB010A NB#73511 11 FLOOR WEST FAILURE TO MAINTAIN, MISSING PIPE INSULATION, CO DETECTOR, FLUE & INDUCER SUPPOR... | $0 | $0 | Sep 12, 2019 |
| Jul 16, 2019 | 39006162N | RESOLVE | CLASS - 2 | PACIFIC ELECTRIC BOILER MODEL# PSE-12 KW12 NB#13917 10 FLOOR WEST, UNREGISTERED , MAINTAIN BOILER | $310 | $0 | Sep 12, 2019 |
| Jul 16, 2019 | 39006132M | RESOLVE | CLASS - 2 | FULTON FB015A NB#72438 9 FLOOR EAST, FAILURE TO MAINTAIN CO DETECTOR, SPILL SWITCH, PIPE INSULATION, MISSING SUPPORT ... | $0 | $0 | Sep 12, 2019 |
| Jul 16, 2019 | 39006143H | ACTIVE | CLASS - 2 | FULTON FB010A NB#62216 12 FLOOR WEST FAILURE TO MAINTAIN, MISSING PIPE INSULATION, CO DETECTOR, FLUE SUPPORT, SECURE ... | $625 | $0 | Sep 12, 2019 |
| Jul 2, 2019 | 39004991L | RESOLVE | CLASS - 2 | HP FULTON VT FB-010-A NB#66734 BTU'S 470000 1993 STEAM GAS 13FL EAST FAILURE TO MAINTAIN, MISSING PIPE INSULATION, FL... | $0 | $0 | Aug 22, 2019 |
| Jul 2, 2019 | 39004993P | RESOLVE | CLASS - 2 | HP FULTON VT FB-006-A NB#61794 BTU'S 200000 1994 STEAM GAS BOILER 15FL WEST FAILURE TO MAINTAIN, MISSING PIPE INSULAT... | $310 | $0 | Aug 22, 2019 |
| Jul 2, 2019 | 39004997M | RESOLVE | CLASS - 2 | XP FULTON VT FB-010-A NB#76359 BTU,S 420000 15FL EAST 1996 STEAM GAS BOILER, FAILURE TO MAINTAIN, MISSING PIPE INSULA... | $0 | $0 | Aug 22, 2019 |
| Jul 2, 2019 | 39004995Z | RESOLVE | CLASS - 2 | HP FULTON VT FB-015-A NB#71615 3RD FL EAST BTU'S 630000 1994 STEAM GAS, FAILURE TO MAINTAIN, CO DETECTOR REQUIRED, CL... | $310 | $0 | Aug 22, 2019 |
| Jul 2, 2019 | 39004990J | RESOLVE | CLASS - 2 | HP FULTON VT FB-010-A NB#76359 BTU'S 420000 1996 STEAM GAS BOILER 15FL EAST FAILURE TO MAINTAIN MISSING PIPE INSULATI... | $310 | $0 | Aug 22, 2019 |
| Jul 2, 2019 | 39004998Y | ACTIVE | CLASS - 2 | HP MINIATURE ELECTRICAL BOILER REIMER RH20 20KW 13FL WEST STEAM GAS, FAILURE TO MAINTAIN, CORROSION ON WATER FEED CHE... | $625 | $0 | Aug 22, 2019 |
| Jul 2, 2019 | 39004992N | RESOLVE | CLASS - 2 | XP FULTON VT FB-015-A NB#69201 BTU'S690000 1994 STEAM GAS BOILER 7FL WEST, FAILURE TO MAINTAIN MISSING PROPER SUPPORT... | $0 | $0 | Aug 22, 2019 |
| Jul 2, 2019 | 39004996K | RESOLVE | CLASS - 2 | XP FULTON VT FB-010-A NB#65022 BTU'S 470000 1992 STEAM GAS BOILER 16FLEAST FAILURE TO MAINTAIN SECURE PROBE ELECTRODE... | $310 | $0 | Aug 22, 2019 |
| Dec 14, 2018 | 35374517R | RESOLVE | CLASS - 2 | WORK W/O A PERMIT. AT 7TH FL REMOVED PARTITION WALLS IN VARIOUS LOCATIONS TO COMBINE FACTORY ON WEST SIDE TO THE EAST... | $625 | $0 | Apr 4, 2019 |
| Nov 30, 2018 | 35347988J | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NO FIRE STOPPING PER BC 712.3; 27-345 IN MECHANICAL AND BOILER... | $1,250 | $0 | May 23, 2019 |
| Nov 30, 2018 | 35347987H | RESOLVE | CLASS - 1 | BC1011 ILLUMINATED EXIT SIGN REMOVED AT 9TH FLOOR (WEST) EXIT DOOR. ACCESS TO EXITS NOT MARKED BY READILY VISIBLE EXI... | $2,500 | $0 | Jan 31, 2019 |
| Nov 30, 2018 | 35347985Y | ACTIVE | CLASS - 1 | OCCUPANCY CONTRARY TO THAT ALLOWED BY THE C/O #10865. ILLEGAL OCCUPAN CY NOTED: 10TH FLOOR (FACTORY) EAST, CONVERTED/... | $2,500 | $0 | May 23, 2019 |
| Nov 30, 2018 | 35347989L | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAYS TO STAIRWAYS AND EXITDOOR WAY THROUGHOUT BUILDING FROM FLOORS 2 TO 1... | $1,250 | $0 | Jan 31, 2019 |
| Nov 30, 2018 | 35347986X | RESOLVE | CLASS - 1 | WORK W/O A PERMIT. WORK NOTED: AT 10TH FLOOR (EAST) ERECTED FULL HEIGHT PARTITIONS TO CREATE 14 STUDIO/OFFICES. AT 4T... | $2,500 | $0 | May 23, 2019 |
| May 25, 2018 | 35318932H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN EXTERIOR BLDG NORTH ELEV EXP#3 & SOUTH ELEV EXP#1 OBSERVED CRACKED WINDOW GLASS,RUSTING WINDOW FR... | $1,250 | $0 | Apr 4, 2019 |
| May 18, 2018 | 37011350Y | ACTIVE | CLASS - 2 | FAILURE TO SUBMIT ACCEPTABLE 8TH ROUND REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALLS AND APP... | $1,250 | $0 | Mar 21, 2019 |
| Feb 23, 2008 | 32055817L | ACTIVE | Non-Hazardous | 36. REIMERS ELECTRIC MINIATURE HP STOP BLR. 20 LW. (36) REFRENCED HIGHPRESSURE ELECTRIC STEAM BOILER IS NOT REGISTERE... | $2,500 | $0 | Apr 10, 2008 |
| Feb 23, 2008 | 32055815H | RESOLVE | Non-Hazardous | 1650. FULTON V.T BOILER, 15HO NB72438 GAS 1996. 16 NYC DOB BOILER INSPCERT NOT POSTED IN BOILER ROOM. BOILER JURISDIC... | $10,000 | $0 | Apr 10, 2008 |
| Feb 23, 2008 | 32055819P | RESOLVE | Non-Hazardous | 50A. FUCTON V.T BOILER 6 HP, NB61794 GAS 1991. 50A SECONDARY LOW CUTOFF MANUAL RESET SWITCH MISSING IN BOILER CONTROL... | $0 | $0 | Apr 10, 2008 |
| Feb 23, 2008 | 32055816J | RESOLVE | Non-Hazardous | 18AB50, FULTON VT BOILER 6 HP NB45294 GAS 1984. 18AB CORRODED & LEAKING HAND HOLES. CLEAN & RE-GASKET OPENINGS. 50 ST... | $180 | $0 | Apr 10, 2008 |
| Feb 16, 2008 | 32055813Y | RESOLVE | Non-Hazardous | 50. FULTON V.T BOILER, 15HP NB 73659 GAS 1995. 50 AIR COMPRESSOR MOTORDRIVE SHAFT NOT PROTECTED IN THE BOILER ROOM. I... | $0 | $0 | Apr 10, 2008 |
| Feb 16, 2008 | 32055814X | RESOLVE | Non-Hazardous | 50. FUCTON V.T BOILER,15HP,NB82750 GAS 1998 (50) DIAL GLASS MISSING ONSTEAM PRESSURE GAUGE REPLACE DEFECTIVE GAUGE. | $0 | $0 | Apr 10, 2008 |
| May 3, 2006 | 32050077M | RESOLVE | Non-Hazardous | 48B/50. 1991-FULTON NB #62567. 50)REPAIR DAMAGED CASEING AROUND THE TOP HANDHOLE. | $0 | $0 | Jun 22, 2006 |
| Apr 24, 2006 | 32049962R | RESOLVE | Non-Hazardous | BQ9,43B,50B,36,50A,50C/1991 FULTON N.B#62216/50A-BOILER RM DOOR MADE OF WOOD/50B-ADD SLOW OPENING VALVE TO THE BOTTOM... | $680 | $0 | Jun 8, 2006 |
| Apr 24, 2006 | 32049960N | RESOLVE | Non-Hazardous | BQ9/1996 FULTON N.B. 76359 | $0 | $0 | Jul 6, 2006 |
| Apr 24, 2006 | 32049961P | RESOLVE | Hazardous | BQ9,36,32A/MINITURE BLR RIMERS ELECTRIC N.B. 3659 | $850 | $0 | Jun 8, 2006 |
| Jun 23, 2004 | 32044857M | RESOLVE | Non-Hazardous | 50A,50B.FULTON V.T. BOILER,20HP,NB83778,GAS-FIRED,1999.50A-SECONDARY LOW WATER CUT OFF MANUAL RESET SWITCH NOT FULLY ... | $0 | $0 | Aug 12, 2004 |
| Jun 23, 2004 | 32044859X | RESOLVE | Non-Hazardous | 50A,50B.FULTON V.T. TBLS BLR,20 HP,NB62567,GAS,1991.50A-NO DISCHARGE PIPE ON THE SAFETY VALVE.50B-IMPROPER ARRANGEMEN... | $0 | $0 | Aug 12, 2004 |
| Jun 23, 2004 | 32045011N | RESOLVE | Non-Hazardous | 32A,34B,50A,32B,38.1991 FULTON NATL BO 61794.50A-ADD A BLOW OPENING VALVE TO THE BOTTOM BLOW DOWN LINE. | $0 | $0 | Aug 12, 2004 |
| Jun 23, 2004 | 32044856K | RESOLVE | Non-Hazardous | 44C,50.FULTON VERT. TBLS. BLR.,15HP,NB82750,GAS-FIRED,1998.50-IMPROPER ARRANGEMENT OF BLOWDOWN VALVES ON THE REFERENC... | $0 | $0 | Aug 12, 2004 |
| Jun 23, 2004 | 32044861P | RESOLVE | Non-Hazardous | 48A,B.50.FULTON V.T. BOILER,10HP,NB73511,GAS FIRED,1995.48A,B- DIRTY AND LEAKING GAUGE GLASS.50-IMPROPER ARRANGEMENT ... | $180 | $0 | Aug 12, 2004 |
| Jun 23, 2004 | 32044860N | RESOLVE | Non-Hazardous | 50.FULTON V.T. BOILER,10HP,NB65253,GAS-FIRED,1992.50-IMPROPER ARRANGEMENT OF BLOWNDOWN VALVES.INSPEC. SCREW -TYPE ANG... | $0 | $0 | Aug 12, 2004 |
| Jun 23, 2004 | 32045010L | RESOLVE | Non-Hazardous | 50A,50B,50C,50D,32A,38,BQ9,36.1994 FULTON N.BO 69201.50A-THREADED ENDS ON SAFETY VALVE PIPE DOWN.50B-HOLE IN WALL ABO... | $430 | $0 | Aug 12, 2004 |
| Jun 23, 2004 | 32044855Z | RESOLVE | Non-Hazardous | FULTON V.T. BOILER,15HP,NB73659,GAS-FIRED,1995.50A-IMPROPER ARRANGEMENT OF BLOWDOWN VALVES ON THE REFERENCED BOILER.I... | $0 | $0 | Aug 12, 2004 |
| Jun 23, 2004 | 32044858Y | RESOLVE | Non-Hazardous | 5OA,50B.FULTON V.T. BOILER,20HP,NB68930,GAS-FIRED,1999.50A-FRESH AIR INTAKE DUCT TO BURNING RESTING ON THE GAS FUEL T... | $0 | $0 | Aug 12, 2004 |
| Jun 23, 2004 | 32045012P | RESOLVE | Non-Hazardous | 1984 FULTON NATL. BD 45294 11A> ADD A SLOW OPENING VALVE ON THE BOTTOMBLOWDOWN 50A WIRE A MANUAL RESET CONTROL IN FOR... | $2,500 | $0 | Oct 28, 2004 |
| Jun 23, 2004 | 32045013R | RESOLVE | Non-Hazardous | BQ9,32A,11A,36,48B,50.REIMOR MINIATURE NATL BO 3659.50-PROVIDE A BALL COCK VALVE ON THE PRESSURE GAUGE. | $5,000 | $0 | Aug 12, 2004 |