ECB violations
27-31 East 29 Street, Manhattan • Block 00859 • Lot 0026
117 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Aug 5, 2025 | 39156103R | RESOLVE | CLASS - 1 | CEASE USE ITEM: DOOR ZONE RESTRICTOR AND IN-CAR EMERGENCY STOP SWITCH INOPERATIVE. THIS IS A SAFETY FEATURE WHICH ENS... | $1,250 | $0 | Oct 9, 2025 |
| Aug 5, 2025 | 39156105K | RESOLVE | CLASS - 1 | CEASE USE ITEM: DOOR ZONE RESTRICTOR INOPERATIVE. THIS IS A SAFETY FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY: TO... | $1,250 | $1,250 | Oct 9, 2025 |
| Aug 5, 2025 | 39156104Z | RESOLVE | CLASS - 2 | CLASS 2 ITEMS; HOIST ROPES SHOWING SIGNS OF ROUGE. CLEAN ENTIRE PIT AREA. | $0 | $0 | Oct 9, 2025 |
| Aug 5, 2025 | 39156102P | RESOLVE | CLASS - 2 | CLASS 2 ITEM: PROVIDE AN AUDIBLE ALARM WHEN CAR IS ACCENDING AND DECENDING. | $0 | $0 | Oct 9, 2025 |
| Jul 30, 2025 | 39155518Y | RESOLVE | CLASS - 2 | OBSERVED STANDPIPE CAPS THROUGHOUT THE BUILDING ARE PLASTIC. MISSING SPRINKLER HEAD CAPS THROUGHOUT THE BUILDING. IN ... | $0 | $0 | Oct 9, 2025 |
| Jul 30, 2025 | 39155517M | RESOLVE | CLASS - 1 | OBSERVED ON THE ROOF NO APPLIANCE VALVE NEXT TO CEILING HEATER UNIT AND ROOFTOP UNIT. FUTURE ON GAS LINE. BOILER MISS... | $2,500 | $0 | Oct 9, 2025 |
| Aug 29, 2024 | 39123410X | RESOLVE | CLASS - 2 | OBSERVED IN BASEMENT FIRE PUMP LEAKING WATER ONTO THE FLOOR. ALSO FIRE ALARM PANEL INDICATING THAT THERE IS A PROBLEM... | $0 | $0 | Nov 7, 2024 |
| Jul 29, 2024 | 39120152Z | RESOLVE | CLASS - 1 | I OBSERVED IN THE CELLAR LAUNDRY ROOM THE WIRING SUPPLYING POWER TO THE DRYER IMPROPERLY FUSED., PROVIDE PROTECTION A... | $4,800 | $0 | Dec 5, 2024 |
| Jul 29, 2024 | 39120163Y | RESOLVE | CLASS - 2 | IMPROPER STORAGE UNDERNEATH STAIRCASE LOCATED AT STAIRCASE 3B, (B-STAIRCASE 3RD FLOOR)., PROVIDE PROPER CORRIDOR WIDTH | $0 | $0 | Oct 3, 2024 |
| Jul 29, 2024 | 39120151R | RESOLVE | CLASS - 1 | I OBSERVED ON ALL FLOORS THE FAILURE TO MAINTAIN/INSTALL TAMPER RESISTANT OUTLETS IN THE COMMON HALLWAYS AS PER LL39/... | $2,500 | $0 | Jul 3, 2025 |
| Jul 29, 2024 | 39120140L | RESOLVE | CLASS - 2 | OBSERVED IN THE BOILER ROOM ON THE ROOM LEVEL EXCESSIVE COMBUSTIBLE STORAGE. NO STORAGE SHALL BE KEPT IN THE BOILER R... | $0 | $0 | Oct 3, 2024 |
| Jul 29, 2024 | 39120161K | RESOLVE | CLASS - 2 | NO EMERGENCY LIGHTING IN THE BUILDING CORRIDOR/HALLWAYS., REPAIR AND/OR REPLACE LIGHTING | $0 | $0 | Oct 3, 2024 |
| Jul 29, 2024 | 39120159L | RESOLVE | CLASS - 2 | ILLEGAL HARDWARE, (PUSH BOTTON LOCKS, HOOKS, SLIDING LATCH LOCKS) LOCATED THROUGHOUT BUILDING., PROVIDE LEGAL HARDWARE | $0 | $0 | Oct 3, 2024 |
| Jul 29, 2024 | 39120154M | RESOLVE | CLASS - 1 | I OBSERVED IN THE ROOFTOP BOILER ROOM AND THE ELECTRICAL CLOSETS THE FAILURE TO PROVIDE LIGHTING AT THE ENTRANCE.; EC... | $1,600 | $0 | Dec 5, 2024 |
| Jul 29, 2024 | 39120158J | RESOLVE | CLASS - 1 | IMPROPER STORAGE OF COMBUSTIBLE MATERIAL, (LARGE PROPANE TANK) LOCATED AT BALL ROOM OFFICE AREA, GROUND FLOOR. ALL CO... | $2,500 | $0 | Jul 10, 2025 |
| Jul 29, 2024 | 39120160Z | RESOLVE | CLASS - 1 | PATH OF EGRESS/EMERGENCY EXIT, (STAIRCASE E) HAS BEEN ALTERED, EXTENDED, AND OR CHANGED TO RE-ENTER BUILDING. ALSO WA... | $0 | $0 | Jan 30, 2025 |
| Jul 29, 2024 | 39120153K | RESOLVE | CLASS - 1 | I OBSERVED THROUGHOUT THE ROOFTOP AREA, DISCONNECT SWITCHES, ELECTRICAL EQUIPMENT (GENERATOR) CONDUITS AND FITTINGS I... | $1,600 | $0 | Jul 3, 2025 |
| Jul 29, 2024 | 39120162M | RESOLVE | CLASS - 2 | HOLE PENETRATIONS WITH ILLEGAL FOAM, NO FIRE-STOPPING, AND OR PIPES RUNNING THROUGH WITHOUT PROPER FIRE-STOPPING LOCA... | $0 | $0 | Oct 3, 2024 |
| Jul 29, 2024 | 39120142P | RESOLVE | CLASS - 2 | OBSERVED A LARGE LAUNDRY BIN IN THE GAS METER ROOM LOCATED IN THE BASEMENT/CELLAR. AS PER E 3 OF THE FGC, GAS METER R... | $0 | $0 | Oct 3, 2024 |
| Jul 29, 2024 | 39120157H | RESOLVE | CLASS - 2 | ROOF TOP MECHANICAL BOILER ROOM DOUBLE DOORS DO NOT SELF-CLOSE AND HAVE ILLEGAL SLIDING LATCH LOCKS INSTALLED., REPAI... | $0 | $0 | Oct 3, 2024 |
| Jul 29, 2024 | 39120150P | RESOLVE | CLASS - 1 | I OBSERVED IN THE ROOFTOP BOILER ROOM, THE ELECTRICAL CLOSETS ON ALL FLOORS AND THE MAIN ELECTRICAL ROOMS IN THE CELL... | $1,200 | $0 | Jul 3, 2025 |
| Jul 29, 2024 | 39120148X | RESOLVE | CLASS - 2 | OBSERVED IN THE BASEMENT/CELLAR WATER LEAK ON THE ELECTRIC WATER HEATER. AS PER PC 102.3 MAINTENANCE. INSTALLATIONS, ... | $0 | $0 | Oct 3, 2024 |
| Jul 29, 2024 | 39120139Y | RESOLVE | CLASS - 1 | OBSERVED FLAMMABLE EQUIPMENT CABINET IS BEING STORED IN THE FIRE PUMP ROOM. AS PER 404.3 OF THE FGC, GAS PIPING, GAS ... | $1,250 | $0 | Jul 3, 2025 |
| Jul 29, 2024 | 39120141N | RESOLVE | CLASS - 2 | OBSERVED GAS PIPING ON ROOF AND ALSO IN THE BASEMENT/CELLAR NOT PAINTED OR MARKED. AS PER FGC 401.5 GAS PIPING MUST B... | $0 | $0 | Oct 3, 2024 |
| Jul 29, 2024 | 39120121X | RESOLVE | CLASS - 1 | CLASS 1 CEASE USE ITEM: RELACE WORN COUNTER WEIGHT GUIDE ROLLER. CLASS 2 ITEM: PRO VIDE MAIN LINE DISCONNECT TO WORK ... | $1,250 | $0 | Sep 11, 2025 |
| Jul 29, 2024 | 39120122H | RESOLVE | CLASS - 1 | CEASE USE CLASS 1 ITEMS: BRAKE PAD ON LEFT SHOE WORN. F4 3AMP FUSE IN CONTROLLER BYPASSED. CLASS 2 ITEMS: CLEAN AND R... | $1,250 | $0 | Sep 11, 2025 |
| Jan 16, 2024 | 37026054L | RESOLVE | CLASS - 2 | FAILURE TO FILE ACCEPTABLE AMENDED CYCLE 8A & 9A REPORT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCIBED IN INITIA... | $1,250 | $0 | Sep 17, 2024 |
| Jan 5, 2024 | 39524563Y | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH CODES 3307.6.5.6. SIDEWALK SHED ERECTED AT EXPOSURES WERE MISSING PROTECTION FOR SOME BOLTS AN... | $2,430 | $0 | Mar 14, 2024 |
| Dec 27, 2023 | 39524332R | RESOLVE | CLASS - 2 | AT TIME OF INSPECTION I OBSERVED SIDEWALK SHED INSTALLED ON EXPOSURE #1 WITH INOPERABLE LIGHT BULBS AT UNDERSIDE THE ... | $2,430 | $0 | Mar 7, 2024 |
| Nov 6, 2023 | 35675309L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN EXTERIOR WALL AND APPURTENANCE. AT THE ROOF LEVEL ON EAST ELEVATION OBSERVED CRACKED MASONRY AND ... | $500 | $0 | May 17, 2024 |
| Aug 25, 2023 | 39093462N | RESOLVE | CLASS - 2 | CLASS 2, 52/Y/13 HOIST MOTOR OIL LEAK SEAL,13/L/10 EMERGENCY LIGHT IS NOT WORKING DEFECTIVE REPAIR, | $655 | $0 | Jul 11, 2024 |
| Jan 14, 2023 | 39511679N | RESOLVE | CLASS - 2 | SWS NOTTIGHT TO FACADE MORE THAN AN INCH GAP NO SEALMENT PER 3307.6.4.5,MISSING C-CLAMPS CONNECTION HEADER TO JUNIORB... | $0 | $0 | Mar 23, 2023 |
| Jun 1, 2022 | 39063245J | RESOLVE | CLASS - 1 | OUT OF SERVICE | $1,250 | $0 | Jul 21, 2022 |
| Feb 8, 2022 | 39055724R | RESOLVE | CLASS - 1 | CLASS 1 R T S. THE ELEVATOR IN BUILDING OUT OF SERVICE , UPON INSPECTION THE DEVICE IS FOUND TO BE OUT OF SERVICE, RE... | $1,250 | $0 | Sep 8, 2022 |
| Jan 10, 2022 | 35538235R | RESOLVE | CLASS - 2 | REMOVAL OF PUBLIC PROTECTION FROM UNSAFE FACADE W/O APPROVAL FROM DEPT.NOTE:ALTHO AMENDED SWARMP WAS FILED BY QEWI ON... | $1,250 | $0 | Nov 3, 2022 |
| Jan 10, 2022 | 35538232L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING WALLS AND APPURTENANCES. OBSERVED:CRACKEDMASONRY LINTELS ON 5TH FL&10TH FL AT SOUTH END,... | $1,250 | $0 | Nov 3, 2022 |
| Oct 8, 2021 | 37022098P | RESOLVE | CLASS - 2 | FAILURE TO FILE ACCEPTABLE AMENDED CYCLE8A REPORT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRIBED IN INITIAL FAC... | $0 | $0 | Feb 24, 2022 |
| Sep 18, 2020 | 38272158X | RESOLVE | CLASS - 1 | CEASE USE, 97X17, 5L10: 97-X-17 ENTIRE DEVICE IS INOPERATIVE REPAIR DOOR AND RESTORE TO SERVICE 5-L-10 DOORS IS DAMAG... | $312 | $0 | Apr 29, 2021 |
| Jun 11, 2020 | 39023851N | RESOLVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF K3 2014 NYCBC. THIS IS A CONTROLLER FE... | $0 | $0 | Jul 30, 2020 |
| Aug 1, 2018 | 37012272M | RESOLVE | CLASS - 2 | FAILURE TO FILE ACCEPTABLE AMENDED CYCLE 8A REPORT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRIBED IN INITIAL FA... | $1,250 | $0 | Jan 31, 2019 |
| Jul 23, 2018 | 38264400P | RESOLVE | CLASS - 1 | 52H11 WORN HOIST ROPES, UNDERSIZED AND ROUGED. REPLACE AND CALL FOR REINSPECTION. | $1,250 | -$1,250 | Oct 25, 2018 |
| Jun 20, 2017 | 37002471X | RESOLVE | CLASS - 2 | FAILURE TO FILE ANNUAL CERTIFICATION THAT COOLING TOWER 1000001639 HASBEEN INSPECTED,TESTED AND DISINFECTED AND THAT ... | $2,000 | $0 | Apr 5, 2018 |
| Jun 8, 2017 | 35126018J | RESOLVE | CLASS - 1 | FILED A CERTIFICATE,FORM,APPLICATION,ETC,CONTAINING A MATERIAL FALSE STATEMENT. NOTED: FALSE STATEMENT FILED UNDER AP... | $0 | $0 | Oct 19, 2017 |
| Jun 8, 2017 | 35126017H | RESOLVE | CLASS - 1 | FILED A CERTIFICATE,FORM,APPLICATION,ETC CONTAINING A MATERIAL FALSE STATEMENT FILED UNDER APPL#123057565 ITEM#26 CHE... | $0 | $0 | Oct 19, 2017 |
| Jun 8, 2017 | 35126015Y | RESOLVE | CLASS - 1 | FILED A CERTIFICATE,FORM,APPLICATION,ETC CONTAINING A MATERIAL FALSE STATEMENT. NOTED: FALSE STATEMENT FILED UNDER AP... | $0 | $0 | Oct 19, 2017 |
| Jun 8, 2017 | 35126016X | RESOLVE | CLASS - 1 | FILED A CERTIFICATE,FORM,APPLICATION ETC. CONTAINIG A MATERIAL FALSE STATEMENT. NOTED: FALSE STATEMENT FILED UNDER AP... | $0 | $0 | Oct 19, 2017 |
| Jun 8, 2017 | 35126019L | RESOLVE | CLASS - 1 | FILED A CERTIFICATE,FORM,APPLICATION,ETC CONTAINING A MATERIAL FALSE STATEMENT. NOTED: FALSE STATEMENT FILED UNDER AP... | $0 | $0 | Oct 19, 2017 |
| Apr 4, 2016 | 38241030P | RESOLVE | CLASS - 2 | 59-U-07,68-B-07,17-L-11,25-M-07:(59-U-07)PROVIDE BREAK MAINTENANCE TAG(68-B-07)UPDATE MAINTENANCE LOG TO SHOW SHOW BR... | $250 | $0 | May 19, 2016 |
| May 7, 2015 | 35133154J | RESOLVE | CLASS - 2 | REMOVAL OF SHED/ PROTECTIVE MEASURE WITHOUT DEPARTMENT APPROVAL.NOTE: BLDG FACADES WERE SILL DESIGNATED AS "UNSAFE".A... | $800 | $0 | Sep 10, 2015 |
| Nov 28, 2014 | 36026529J | RESOLVE | CLASS - 2 | FAILURE TO FILE AN ACCEPTABLE AMENDED CYCLE 7 REPORT TO THIS DEPT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRIBE... | $800 | -$30 | Jun 25, 2015 |