ECB violations
18 East 38 Street, Manhattan • Block 00867 • Lot 0018
45 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Oct 28, 2025 | 35717799X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING FACADE WALLS AND APPURTENANCES.NOTE:AT TIME OF INSPECTON I OBSERVED AT EX#1 EAST ELEVATI... | $0 | $0 | Jan 8, 2026 |
| Apr 11, 2024 | 37027665P | RESOLVE | CLASS - 2 | FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 9B REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WA... | $3,125 | $3,125 | May 22, 2025 |
| Feb 7, 2022 | 35568448H | RESOLVE | CLASS - 1 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION#39061735Y ISSUED ON 11/26/21 AND TO FI... | $0 | $0 | Aug 25, 2022 |
| Nov 26, 2021 | 39051735Y | RESOLVE | CLASS - 1 | WORK WITHOUT A PERMIT. AT TIME OF INSPECTION OBSERVED AT EXPOSURE #1 3RD FLOOR, LOT LINE WINDOWS APPROXIMATELY 4'X6' ... | $2,500 | $0 | May 12, 2022 |
| Nov 4, 2020 | 35542181M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN EXTERIOR BLDG FACADE AND APPURTENANCES.NOTE:OBSERVED 1)MULTIPLES CRACK ON THE PARAPET WALL AT EXP... | $620 | $0 | Jan 21, 2021 |
| Nov 15, 2019 | 37016823H | RESOLVE | CLASS - 2 | AC279291-FAILURE TO COMPLETE THE INSTALLATION OF A FULL SYSTEM OF AUTOMATIC SPRINKLERS AND FILE A FINAL SPRINKLER REP... | $0 | $0 | Feb 27, 2020 |
| Nov 15, 2019 | 37016375N | RESOLVE | CLASS - 2 | SEC. A.C.27-929.1,FAILURE TO COMPLETE THE INSTALLATION OF A FULL SYSTEM OF AUTOMATIC SPRINKLERS & FILE A FINAL SPRINK... | $0 | $0 | Nov 5, 2020 |
| Mar 19, 2019 | 32098682N | RESOLVE | CLASS - 2 | B254,50A,50B,50C. FULTON V.T. BLK 2; 10HP, NB60737, HPSTM GAS 1990 50A-HIGH AMBIENT TEMPERATUE IN THE BOILER ROOM, IN... | $0 | $0 | May 16, 2019 |
| Mar 19, 2019 | 32098681L | RESOLVE | CLASS - 2 | B254,50A,50B,50. FULTON V.T. BLK 1,15HP,MB79931, HP STEAM GAS FIRED, 1997 50A.-HIGH AMBIENT TEMPERATURE IN THE BOILER... | $312 | $0 | May 16, 2019 |
| Mar 19, 2019 | 32098683P | RESOLVE | CLASS - 2 | B254,50A,50B,50C. FULTON V.T. BLK#3; 15HP NB 106464,HP STM, GAS, 200850A-HIGH AMBIENT TEMPERATURE IN THE BOILER ROOM;... | $0 | $0 | May 16, 2019 |
| Nov 2, 2018 | 38266381H | RESOLVE | CLASS - 2 | 6R9,2M7-6R9)RELOCATE GATE SWITCH TO OUTSIDE OF CAR. 2M7)PHONE MISSING, PROVIDE. | $0 | $0 | Dec 27, 2018 |
| Nov 2, 2018 | 38266380X | RESOLVE | CLASS - 2 | 40O2,50Y13,1B10,71X10-40)CLEAN MOTOR ROOM. 56)HOIST MACHINE OIL LEAK. 1B10)ALARM BELL ON STOP SWITCH. 71)PIT LIGHT IN... | $0 | $0 | Dec 27, 2018 |
| Jun 13, 2018 | 32096609H | ACTIVE | CLASS - 1 | B154,3B,50A,51. FULTON V.T. BOILER #1, 15HP,NB79931, HP STM,GAS 1997 3B-REFERENCED BOILER #3 IN OPERATION WITH FLUE G... | $1,250 | $0 | Aug 2, 2018 |
| Jun 13, 2018 | 32096610P | ACTIVE | CLASS - 1 | B154,3B,50A,51. FULTON V.T. BOILER #2, 10HP,NB607374, HP STM,GAS 1990 3B-REFERENCED BOILER #3 IN OPERATION WITH FLUE ... | $1,250 | $0 | Aug 2, 2018 |
| Jun 13, 2018 | 32096611R | ACTIVE | CLASS - 1 | B154,3B,50A,51. FULTON V.T. BOILER #3, 15HP,NB105464, HP STM,GAS 2008 3B-REFERENCED BOILER #3 IN OPERATION WITH FLUE ... | $1,250 | $0 | Aug 2, 2018 |
| Mar 13, 2017 | 38253680P | RESOLVE | CLASS - 2 | 2X7 COMMUNICATION NOT WORKING INSIDE ELEVATOR PROVIDE (INSTALL PHONE SYSTEM). | $250 | $0 | Apr 27, 2017 |
| Mar 13, 2017 | 38253679H | RESOLVE | CLASS - 1 | 2X7,2X10. 2X7-ALARM BELL NTO WORKING; 2X10-COMMUNICATION NOT WORKING INOPERATIVE REPAIR. C/USE TAGGED ON MAINLINE. | $1,000 | -$250 | Apr 27, 2017 |
| Jan 21, 2017 | 35210334N | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN EXTERIOR BLDG FACADE AND APPURTENANCES *AMENDED REPORT FILE SAFE. NOTED: EAST ELEVATION EXP1:HORI... | $1,000 | $0 | Nov 30, 2017 |
| May 29, 2013 | 35004235K | RESOLVE | CLASS - 1 | FILED A C/C OR OTHER RELATED MATERIALS CONTAINING MATERIAL FALSE STATEMENT(S). NOTE: THERE ARE COMMERCIAL A/C UNITS T... | $0 | $0 | Nov 7, 2013 |
| Sep 11, 2012 | 34993169X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN A CODE-COMPLIANT MANNER. DEFECTS NOTED: ATTIME OF INSPECTION THERE ARE MULTIPLE EXHAUST D... | $0 | $0 | Nov 1, 2012 |
| Jul 10, 2012 | 38222601X | RESOLVE | CLASS - 2 | 70D06,71X10,10D06,56Y13,11P16. 11P: PROVIDE ACCESS TO 15TH FLOOR (CAR BUTTON). | $250 | $0 | Aug 30, 2012 |
| Jul 10, 2012 | 38222600Y | RESOLVE | CLASS - 2 | 05I10,08V01,10D06,56Y13,11P16.05I:ASTRAGAL FOR BIPAINTING CAR DOOR (ALSO REDUCE GAP TO CLOSE) FULLY. 11P:PROVIDE ACCE... | $250 | $0 | Aug 30, 2012 |
| Feb 14, 2012 | 38220765N | RESOLVE | CLASS - 1 | 97F10. 97F10-ELEVATOR SHAKES TOO MUCH DURING MOTION IN THE UP DIRECTION UPPER FLR-CEASE USE UNTIL REPAIRED- CALL DOB ... | $1,000 | $0 | Apr 5, 2012 |
| Jul 27, 2011 | 38217166Y | RESOLVE | CLASS - 2 | 10D06 98B07. 98-PROVIDE LEGIBLE 5-YR TAG (NO YEAR) STAMPED. | $0 | $0 | Sep 15, 2011 |
| Oct 17, 2009 | 32067046K | RESOLVE | CLASS - 3 | 50A,B,C,D,FULTON VT.BOILER 15HP,NB60727,GAS FIRED,1996 50A UPPER SECTION OF BOILER EXTERNAL CASING DEFECTIVE.PERFORM ... | $0 | $0 | Dec 10, 2009 |
| Feb 12, 2009 | 34744105J | RESOLVE | CLASS - 2 | LOCAL LAW REPORT FILED AS "UNSAFE" BY ARCHITECT/ENGINEER. NO AMENDED REPORT WAS FILED "UNSAFE CONDITIONS" REQUIRES SA... | $0 | $0 | Apr 9, 2009 |
| May 8, 2006 | 32050102P | ACTIVE | Non-Hazardous | 18A/50. FULTON VT BOILER,15 HP,NB 60727,GAS 1990. 18A-CORRODED HANDHOLES ON BOILER. REPAIR 50-STEAM PRESSURE GAUGE HA... | $180 | $0 | Oct 5, 2006 |
| May 8, 2006 | 32050100L | RESOLVE | Non-Hazardous | 50A/50B. FULTON V.T. BOILER,15 HP,NB 79931,GAS,1997. 50A-FLUE PIPE CLEAN OUT REPAIRS IN PROGRESS 50B-STEAM PRESSURE G... | $0 | $0 | Jun 22, 2006 |
| May 8, 2006 | 32050101N | RESOLVE | Non-Hazardous | 18A/B/50. FULTON V.T. BOILER,10 HP,NB 60737,GAS,1990. 18A/B-CORRODED &LEAKING HANDHOLES. REPAIR & REGASKET OPENINGS. ... | $0 | $0 | Jun 22, 2006 |
| Jun 4, 2004 | 32044912X | RESOLVE | Non-Hazardous | 48B,32A,6A,50.1997 FULTON 79931.50-REPLACE THE MISSING HANDLE ON THE TOP GLASS VALVE. | $0 | $0 | Jul 22, 2004 |
| Jun 4, 2004 | 32044913H | RESOLVE | Non-Hazardous | 6A,38.FULTON 1990 60737. | $0 | $0 | Sep 2, 2004 |
| Jun 4, 2004 | 32044914J | ACTIVE | Non-Hazardous | 51.CEASE USE.1990 FULTON 60727-HIGH CARBON MONOXIDE.51-SEALED BOILER-341 P.P.M OUT OF CASING AROUND TOP HAND HOLE. | $400 | $0 | Sep 2, 2004 |
| Jun 6, 2001 | 34285428Y | RESOLVE | Non-Hazardous | WORK WITHOUT PERMIT NOTED:AT SECOND FLOOR RESTAURANT REPLACED BY ISNTALLATION OF PARTITIONS TO CREATE OFFICE SPACE AL... | $0 | $0 | Dec 6, 2001 |
| May 14, 1999 | 34211932L | RESOLVE | Non-Hazardous | WORK WITHOUT PERMIT. NOTED: AT 2ND FLOOR - RESTAURANT REPLACED BY IN- STALLATION OF PARTITIONS TO CREATE OFFICE SPACE... | $250 | $0 | Jul 8, 1999 |
| Apr 10, 1996 | 38056379N | RESOLVE | Non-Hazardous | 50L,8V,. | $0 | $0 | Jul 18, 1996 |
| Apr 9, 1996 | 38056378L | RESOLVE | Non-Hazardous | 8V,. | $0 | $0 | Jul 18, 1996 |
| May 26, 1995 | 34122863M | RESOLVE | Non-Hazardous | FAILURE TO PROVIDE EMERGENCY POWER EXIT LIGHTS ON VARIOUS FLOORS THROUGHOUT BLDG.IE 2,3,4,6,7,8,11.ETC. | $200 | $0 | Jul 13, 1995 |
| May 24, 1993 | 34091738Y | RESOLVE | Non-Hazardous | WORK WITHOUT A PERMIT NOTED ALTERED ENTIRE FLOOR FROM A EATING 7 DRINKING ESTABLISHMENT TO A OFFICE SPACE LOCATION 2N... | $350 | $0 | Jul 8, 1993 |
| May 8, 1992 | 34073302Y | RESOLVE | Non-Hazardous | WORK WITHOUT A PERMIT NOTED:ALTERED ENTIRE FLOOR FROM A EATING & DRINKING ESTABLISHMENT TO A OFFICE SPACE.LOCATION 2N... | $285 | $0 | Jul 16, 1992 |
| May 3, 1990 | 34042414R | RESOLVE | Non-Hazardous | OPERATION OF PLACE OF ASSEMBLY CONTRARY TO THE C OF O WHEN THE CURRENTC OF O ALLOWS FOR THE OPERATION OF THE P.A. NOW... | $0 | $0 | Jun 14, 1990 |
| Jan 18, 1990 | 34038004M | RESOLVE | Non-Hazardous | WORK WITHOUT A PERMIT. ALTERED ENTIRE FLOOR FROM A EATING AND DRINK- ING ESTABLISHMENT TO A OFFICE SPACE. LOCATE IN 2... | $250 | $0 | Mar 1, 1990 |
| Jan 18, 1990 | 34038005Y | RESOLVE | Non-Hazardous | OCCUPANCY CONTRARY TO BUILDING DEPARTMENT RECORDS. LEGAL OCCUPANCY WAS EATING AND DRINKING ESTABLISHMENT IN ENTIRE SE... | $250 | $0 | Mar 1, 1990 |
| Jun 8, 1989 | 34025261K | RESOLVE | Non-Hazardous | ALTERED PREMISES LEGAL OCCUPANCY WAS EATING AND DRINKING . REMEDY: FILE TO REMOVE +DISCONTINUE PA AND OBTAIN A NEW C ... | $0 | $0 | Aug 17, 1989 |
| Apr 5, 1989 | 34018630L | RESOLVE | Non-Hazardous | ALTERED PREMISES LEGAL OCCUPANCY WAS EATING & DRINKING EST. CHANGED TO ART STUDIO & GENERAL OFFICE SPACE. REMEDY FILE... | $0 | $0 | May 18, 1989 |
| May 31, 1988 | 34005832R | RESOLVE | Non-Hazardous | ALTERED PREMISES: LEGAL OCCUPANCY WAS EASTING, DRINKING ESTABLISHMENTCHANGED TO EXECUTIVE & GENERAL OFFICE AND DESIGN... | $0 | $0 | Sep 29, 1988 |