ECB violations
120-128 East 34 Street, Manhattan • Block 00889 • Lot 0068
64 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Mar 10, 2022 | 35640900Z | RESOLVE | CLASS - 1 | UNLAWFULLY CONTINUED WORK WHILE ON NOTICE OF A STOP WORK ORDER.AT TIME OF INSPECTION OF 21 STORY ALT ON SWO FOR SUSPE... | $2,500 | $0 | Sep 1, 2022 |
| Feb 25, 2022 | 35639598Z | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE SIDEWALK SHED AS REQUIRED.NOTE AT TIME OF INSPECTION OF A 21 STORY BUILDING,I OBSERVED SUSPENDED S... | $0 | $0 | Nov 3, 2022 |
| Feb 25, 2022 | 35639599K | RESOLVE | CLASS - 2 | FAILURE TO NOTIFY DEPARTMENT PRIOR TO INSTALLATION OF SUSPENDED SCAFFOLD.NOTE AT TIME OF INSPECTION OF A 21 STORY BUI... | $1,250 | $0 | May 26, 2022 |
| Mar 17, 2021 | 39037760P | RESOLVE | CLASS - 2 | ATOI FOUND EXPOSED WIRING, CORRODED WATER COLUMN, DIRTY GLASS GAUGE, FRONT AND REAR BOILER DOORS NEED TO BE RESEALED,... | $0 | $0 | May 6, 2021 |
| Mar 17, 2021 | 39037761R | RESOLVE | CLASS - 2 | ATOI FOUND BOILER IN OPERABLE , EXPOSED WIRING, GUARDS MISSING ON COMPRESSOR, ALSO FOUND HOLES ON CEILING AND WALLS, ... | $312 | $0 | Jan 20, 2022 |
| Mar 17, 2021 | 39037759H | RESOLVE | CLASS - 2 | ATOI FOUND EXPOSED WIRING, CORRODED WATER COLUMN, CORRODED NIPPLE ON DRAIN VALVE, BELT GUARDS MISSING ON PUMP SET AND... | $0 | $0 | May 6, 2021 |
| Aug 5, 2015 | 35133289R | RESOLVE | CLASS - 2 | REMOVAL OF SIDEWALK SHEDS W/O DEPT'S APPROVAL. AS NOTED: AT TIME OF INSPECTION,BLDG FACADES WERE STILL DESIGNATED AS ... | $0 | $0 | Jan 14, 2016 |
| Apr 23, 2014 | 35034502N | ACTIVE | CLASS - 2 | OCCUPANCY CONTRARY TO THAT ALLOWED BY THE CERTIFICATE OF OCCUPANCY #102075585 ILLEGAL OCCUPANCY NOTED CELLAR OCCUPIED... | $1,200 | $0 | Nov 13, 2014 |
| Feb 25, 2014 | 35031968L | RESOLVE | CLASS - 1 | SEC. 3314.6.3;2314.10.9 STOP WORK ORDER ISSUED FOR EXPOSURE #2 - SUSPENDED SCAFFOLDS. TIEBACKS NOT STRAIGHT & GOING 3... | $1,600 | $0 | Apr 17, 2014 |
| Feb 25, 2014 | 35031967J | RESOLVE | CLASS - 1 | WORK DOES NOT CONFORM TO APPROVED CONSTR DOCUMENTS. NOTED: OUTRIGGERS BEAMS INSTALLATION AT EXPOSURE #2,MISSING U-BOL... | $1,000 | $0 | Apr 17, 2014 |
| Nov 9, 2013 | 35029044Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN. NOTED: NO DESIGNATED BICYCLE PARKING SIGN IN PLACE BUT CARS PARKED IN AREAS. REMEDY: COMPLY W/CODE. | $0 | $0 | Dec 26, 2013 |
| Oct 4, 2013 | 38228977L | RESOLVE | CLASS - 1 | 17D06,39O02,45O02,50M07,70O02,79E01. INFINITY ELEVATOR COMPANY LICENSE#495001 SUBMITTED A NOTARIZED STATEMENT TO BE U... | $0 | $0 | Feb 20, 2014 |
| Oct 4, 2013 | 38228899P | RESOLVE | CLASS - 1 | 17D06,39O02,45O02,50M07,70O02,79E01. RESPONDENT FILE A CERTIFICATE OF CORRECTION ON JULY 16,2013 FOR NOV#38226347H. A... | $0 | $0 | Feb 20, 2014 |
| Oct 4, 2013 | 38228886X | RESOLVE | CLASS - 2 | RC17D06,RC39O02,RC45O02,RC50M07,RC70O02,71X10,RC79E01,17H10,41M07. RECURRING CONDITIONS FROM NOV #38226347H.; 17D-VAR... | $0 | $0 | Nov 21, 2013 |
| Oct 4, 2013 | 38228975H | RESOLVE | CLASS - 2 | 17D06,39O02,45O02,50M07,70O02,79E01. FAILURE TO COMPLY WITH/COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION ... | $0 | $0 | Feb 20, 2014 |
| May 6, 2013 | 35016091Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN ADEQUATE HOUSEKEEPING PER SECTION REQUIREMENT. NOTED: 2 LARGE PILES OF BLOCK & BRICKS ON MAIN ROO... | $400 | $0 | Jul 25, 2013 |
| May 6, 2013 | 35016092K | RESOLVE | CLASS - 1 | FAILURE TO SAFEGUARD ALL PERSONS & PROPERTY AFFECTED BY CONSTRUCTION OPERATIONS - NOTED: WHILE WORKING ON REMOVING BR... | $2,400 | $0 | Jul 25, 2013 |
| May 6, 2013 | 35016090R | RESOLVE | CLASS - 1 | FAILURE TO HAVE SITE SAFETY MANAGER COORDINATOR PRESENT AS REQUIRED. NOTED: LAST ENTRY FOR S.S.M. ON P.W.2 4/22/19 OV... | $1,200 | $0 | Jul 25, 2013 |
| Apr 25, 2013 | 38226349L | RESOLVE | CLASS - 2 | 04D06,17D06,39O02,39Y02,40AA02,45O02,50M07,68B07,70O02. 17D-VARIOUS FLOORS; 50M-MG SET COVERS MISSING; 68B-PROVIDE UP... | $500 | $0 | Jun 13, 2013 |
| Apr 25, 2013 | 38226347H | RESOLVE | CLASS - 2 | 17D06,39O02,40AA02,45O02,50M07,68B07,70O02,79E01. 17D-VARIOUS FLOORS;50M-MG SET COVERS MISSING; 79-COMP CHAIN-ADJUST;... | $250 | $0 | Jun 13, 2013 |
| Apr 25, 2013 | 38226348J | RESOLVE | CLASS - 2 | 17D06,39O02,40AA02,45O02,45M07,50M07,68B07,70O02. 17D-VARIOUS FLOORS;45M-SEAL MISSING; 50M-MG SET COVERS MISSING; 68B... | $250 | $0 | Jun 13, 2013 |
| Apr 16, 2013 | 32073350X | RESOLVE | CLASS - 2 | 36,50B,50A. FULTON ST. BOILER,15HP,NB89041,GAS,FIRED,2001, 50A-REFERENCED HIGH PRESSURE STEAM BOILER WAS INSTALLED AS... | $500 | $0 | Jul 18, 2013 |
| Apr 11, 2013 | 34989924Z | RESOLVE | CLASS - 2 | FAILED TO NOTIFY DEPT/OBTAIN PERMIT PRIOR TO USE/INST. OFF OUTFIGGER BEAMS IN CONNECTION W/SUSPENDED SCAFFOLD - NOTED... | $400 | $0 | May 30, 2013 |
| Nov 13, 2012 | 38222041R | RESOLVE | CLASS - 2 | 40B07,56Y10,70O02. 1- PROVIDE SAFE AND CONVENIENT ACCESS TO MACHINE ROOM. 2- REPAIR OIL LEAK. 3- CLEAN PIT. | $500 | $0 | Mar 14, 2013 |
| Nov 13, 2012 | 38222040P | RESOLVE | CLASS - 2 | 45M07,40B07,70O02. 1- RETEST GOVERNOR, PROVIDE SEALS. 2- PROVIDE SAFE AND CONVENIENT ACCESS TO MACHINE ROOM. 3- CLEAN... | $500 | $0 | Mar 14, 2013 |
| Nov 13, 2012 | 38222039H | RESOLVE | CLASS - 2 | 40B16,56Y10,70O02. 1- PROVIDE SAFE CONVENIENT ACCESS TO MACHINE ROOM. 2- REPAIR OIL LEAK. 3- CLEAN PIT. | $500 | $0 | Mar 14, 2013 |
| Nov 15, 2011 | 34933774J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG NOTED : GARAGE DEFECTIVE EXIT SIGN, EMERGENCYLIGHTING THROUGHOUT ALSO INADEQUATE LIGHTING AT... | $0 | $0 | Jan 5, 2012 |
| Oct 9, 2010 | 34877580H | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH TTHE COMMISSIONER'S ORDER TO FILE A COFC WITH THE DOB FOR OPEN ECB VIOLATION#34852747J.REM:COM... | $800 | $0 | Dec 2, 2010 |
| Oct 9, 2010 | 34877579K | ACTIVE | CLASS - 1 | WORK DOES NOT CONFORM TO APPROVED CONSTRUCTION DOCUMENTS NOTED AT NORTH ELEVATION WEST CORNER AN EXHAUST DUCT IS APPX... | $1,250 | $0 | Mar 3, 2011 |
| Aug 14, 2010 | 34852747J | ACTIVE | CLASS - 1 | WORK DOES NOT CONFORM TO APPROVED CONSTRUCTION DOCUMENTS NOTED: @ FRONT OF PREMISES AN EXHAUST DUCT IS APPROX 3' FROM... | $500 | $0 | Nov 18, 2010 |
| Oct 28, 2009 | 34818185H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER NOTED CONCRETE CEILING HAS BECOME POROUS AND ALLOWING WATER INTO TH... | $250 | $0 | Aug 19, 2010 |
| Sep 29, 2008 | 34706508R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER INSTALLATION MAINTANENCE OF PLUMBING MATERIALS EQUIPMENT PER PC 102... | $250 | $0 | Jan 29, 2009 |
| Aug 28, 2008 | 34691312X | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE UNOBSTRUCTED PASSAGEWAY. NOTED: ALL EXIT DOORS OF PARKING GARAGE AT CELLAR & SUB CELLAR ARE OBSTRU... | $1,200 | $0 | Oct 23, 2008 |
| Mar 26, 2008 | 34610381M | RESOLVE | Non-Hazardous | FAILURE TO PROVIDE A SYSTEM OF AUTOMATIC SPRINKLERS WHERE REQUIRED UPON INSPECTION OF LAUNDRY ROOM IN CELLAR NO SPRIN... | $400 | $0 | Jul 22, 2010 |
| Oct 23, 2007 | 38169569P | RESOLVE | Non-Hazardous | 86BB05,17B07,51O02,38O02. 86- 2 YEAR TAG EXPIRED. 17 PROVIDE THE 2ND GIB ON FLR 13,4 & 18. 51- CLEAN OIL FROM HOIST R... | $0 | $0 | Dec 13, 2007 |
| Oct 17, 2007 | 34607401N | RESOLVE | Non-Hazardous | SEC-389 EXIT SIGNS THERE ARE NO EXIT SIGNS OVER EMERGENCY EGRESS DOORSREMEDY:INSTALL EXIT SIGNS | $0 | $0 | Dec 13, 2007 |
| Oct 17, 2007 | 34607400L | RESOLVE | Non-Hazardous | SEC-386 DIRECTIONAL SIGNS THERE ARE NO SIGNS LEADING TO ANY EMERGENCY EGRESS IN THE SUBCELLAR OR ON THE 1ST FL.REMEDY... | $0 | $0 | Dec 13, 2007 |
| Oct 16, 2007 | 38166933Z | RESOLVE | Non-Hazardous | 85BB05. | $0 | $0 | Dec 13, 2007 |
| Oct 16, 2007 | 38166934K | RESOLVE | Non-Hazardous | 85BB05. | $0 | $0 | Dec 13, 2007 |
| Oct 16, 2007 | 38166931P | RESOLVE | Non-Hazardous | 85BB05. | $0 | $0 | Dec 13, 2007 |
| Oct 16, 2007 | 38166932R | RESOLVE | Non-Hazardous | 85BB05. | $0 | $0 | Dec 13, 2007 |
| Mar 14, 2003 | 38136901R | RESOLVE | Non-Hazardous | 39O02,10L12,26B01. 390 TOO MUCH SOOT IN CONTROLLER PROPERLY CLEAN CONTROLLER. 10-REPLACE DEFECTIVE CAR DOOR GIBS 26-A... | $0 | $0 | May 1, 2003 |
| Jul 23, 2001 | 38117188R | RESOLVE | Non-Hazardous | 46B15-50F12-39H08-50O02-50Y14-74M07-55L11-57O02-74O02-74M07. 46-SHOCTEN CABLES FOR PROPER PIT OF COUNTERWEIGHT CLEARA... | $180 | $0 | Sep 6, 2001 |
| Sep 22, 1999 | 38090756Z | RESOLVE | Non-Hazardous | 50Y14,40O2,14M7,47D6,74L11,9M7. -50 SEAL OIL LEAK MAIN MACHINE, -14 PROVIDE CERTIFICATE OR INDICATE LOCATION OF SAME ... | $350 | $0 | Nov 4, 1999 |
| Sep 22, 1999 | 38090757K | RESOLVE | Non-Hazardous | 75U5,40O2,50Y14,39H8,74M7,74D6,15M7,10M6,44#11. -75 PERFORM 5 YR FULL LOAD SAFETY TEST AND FILE WITH THIS DEPT, -39 R... | $350 | $0 | Nov 4, 1999 |
| Sep 22, 1999 | 38090755R | RESOLVE | Non-Hazardous | 46M12,50Y14,57O2,40O2,14M6,39H8. -39 REGROOVE WORN TRACTION SHEAVE, -14 PROVIDE CERTIFICATE OR INDICATE LOCATION OF S... | $350 | $0 | Nov 4, 1999 |
| Sep 9, 1999 | 34222800N | RESOLVE | Non-Hazardous | OCCUPANCY CONTRARY TO THAT ALLOWED BY CERTIFICATE OF OCCUPANCY. NOTED:AT CELLAR PARKING GARAGE-45 CARS AT SUB CELLAR-... | $800 | $0 | Jan 20, 2000 |
| Aug 3, 1999 | 34222777Y | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN EXTERIOR BUILDING WALL. NOTED: AT 9TH FLOOR NORTH ELEVATION; EAST SIDE - WEST CORNER AT WINDOW LI... | $0 | $0 | Sep 23, 1999 |
| Aug 3, 1998 | 34178695P | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN TO MAINTAIN EXTERIOR BUIDLING WALLS. AT THE 14 AND15 STOP THERE ARE. LOOSE SECTIONS OF THE BRICK ... | $800 | $0 | Oct 22, 1998 |
| May 29, 1998 | 34152347N | RESOLVE | Non-Hazardous | USE OR INSTALLATION OF PLUMBING MATERIALS OR EQUIPMENT WHICH DO NOT COMPLY WITH RS-16. REMEDY: REMOVE NON COMPLYING M... | $0 | $0 | Jul 9, 1998 |