ECB violations
243 West 55 Street, Manhattan • Block 01027 • Lot 0009
74 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Jan 18, 2000 | 34228086M | RESOLVE | Non-Hazardous | SPRINKLER SYSTEM NOT PROPERTY TESTED. BUILDING WAS CONVERTED FROM RESIDENTIAL TO HOTEL. A NEW SPRINKLER SYSTEMHAS BEE... | $400 | $0 | Mar 8, 2001 |
| Jan 18, 2000 | 34228087Y | RESOLVE | Hazardous | PLUMBING WORK WITHOUT A PERMIT. STAND PIPE WAS EXTENDED OR INSTALLED NEW TO COVER. TWO NEW FLOORS THAT WERE ADDED TO ... | $1,000 | $0 | Mar 9, 2000 |
| Jan 18, 2000 | 34228089H | RESOLVE | Hazardous | PERFORMING WORK REQUIRED TO BE PERFORMED BY A LISENCED MASTER PLUMBERLISENCED SPRINKLER CONTROLLER WITHOUT HAIVING OB... | $400 | $0 | Mar 8, 2001 |
| Nov 12, 1999 | 34217371H | RESOLVE | Non-Hazardous | INSUFFICENT HEIGHT OF GRAVITY TANK ABOVE HIGHEST HOSE OR SPRINKLER OUTLET. REMEDY: PROVIDE SUFFICEN HEIGHT FOPR GRAVI... | $2,500 | $0 | Mar 9, 2000 |
| Nov 12, 1999 | 34217370X | RESOLVE | Hazardous | FAILURE TO MAINTAIN PLUMBING AND OR APPURTENCES HAZARDOUS. NO WATER IN STANDPIPE, SPRINKLER RESERVE ROOF TANK NO COVE... | $2,500 | $0 | Mar 9, 2000 |
| Nov 12, 1999 | 34217372J | RESOLVE | Non-Hazardous | FAILURE TO PROPERLY PROTECT STANDPIPE SYSTEM FROM FREEZING STANDPIPE AT THE BOTTOM OF ROOF TANK IS NOT ADEQUATELY PRO... | $2,500 | $0 | Mar 9, 2000 |
| Aug 12, 1999 | 34217358N | RESOLVE | Non-Hazardous | INSUFFICIENT HEIGHT OF GRAVITY TANK ABOVE HIGHEST SPRINKLER HEAD OR HOSE OUTLET HAZARDOUS BOTTOM OF ROOF TANK IS LESS... | $0 | $0 | Sep 30, 1999 |
| Aug 12, 1999 | 34217359P | RESOLVE | Hazardous | FAILURE TO MAINTAIN PLUMBING AND/OR APPURTENANCES HAZARDOUS NO WATER IN ROOF TANK USED AS RESERVE FOR STANDPIPE AND S... | $0 | $0 | Sep 30, 1999 |
| Aug 12, 1999 | 34217357L | RESOLVE | Non-Hazardous | FAILURE TO PROPERLY PROTECT STANDPIPE SYSTEM FROM FREEZING HAZARDOUS 4" STANDPIPE AND WATER SUPPLY TO ROOF TANK ARE N... | $0 | $0 | Sep 30, 1999 |
| Apr 28, 1999 | 34191041M | RESOLVE | Non-Hazardous | INSUFFICIENT HEIGHT OF GRAVITY TANK ABOVE HIGHEST SPRINKLER HEAD OR HOSE OUTLET. BOTTOM OF ROOF TANK IS LESS THAN 25 ... | $0 | $0 | Sep 9, 1999 |
| Apr 28, 1999 | 34191040K | RESOLVE | Non-Hazardous | FAILURE TO PROPERLY PROTECT STANDPIPE SYSTEM FROM FREEZING. 4" STAND- PIPE AND WATER SUPPLY TO ROOF TANK ARE NOT ADEQ... | $0 | $0 | Sep 9, 1999 |
| Apr 28, 1999 | 34191042Y | RESOLVE | Hazardous | FAILURE TO MAINTAIN PLUMBING AND/OR APPURTENANCES. HAZARDOUS. NO WATERIN ROOF TANK USED AS RESERVE FOR STANDPIPE AND ... | $0 | $0 | Sep 9, 1999 |
| Dec 31, 1998 | 34191030R | RESOLVE | Non-Hazardous | INSTALLATION OF UNDERSIZED STANDPIPE RISER. RISER IS 4" & CONTRARY TOSECTION 8-1.2.1 OF PLUMBING/SPRINKLER CODE WHICH... | $0 | $0 | Aug 12, 1999 |
| Dec 31, 1998 | 34191029J | RESOLVE | Hazardous | FAILURE TO MAINTAIN PLUMBING &/OR APPURTENANCES. HAZARDOUS. NO WATERIN THE ROOF TANK USED AS RESERVE FOR STANDPIPE, S... | $0 | $0 | Aug 12, 1999 |
| Dec 30, 1998 | 34191027X | RESOLVE | Non-Hazardous | FAILURE TO PROPERLY PROTECT STANDPIPE SYSTEM FROM FREEZING. 4" STAND-PIPE & WATER SUPPLY TO ROOF TANK HAVE NO INSULAT... | $0 | $0 | Aug 12, 1999 |
| Dec 30, 1998 | 34191028H | RESOLVE | Non-Hazardous | INSUFFICIENT HEIGHT OF GRAVITY TANK ABOVE HIGHEST HOSE (SPRINKLER) OUTLET. BOTTOM OF ROOF TANK IS LESS THAN 25' ABOVE... | $0 | $0 | Aug 12, 1999 |
| Oct 19, 1998 | 38080249P | RESOLVE | Hazardous | 73R#. -73 OPERATING DEVICE WITHOUT EQUIPMENT USE PERMIT (CERTIFICATE) CALL 212-312-8745 FOR REMEDY. OFFENSE APT. 18 {... | $0 | $0 | Jan 21, 1999 |
| Oct 9, 1998 | 38080240Z | RESOLVE | Non-Hazardous | 73M DEVICE WAS REMOVED WITHOUT A PERMIT | $250 | $0 | Jan 21, 1999 |
| Oct 8, 1998 | 38080239L | RESOLVE | Non-Hazardous | 73# 73 PERFORMING DEVICE WITHOUT AB EQUIPMENT USE PERFORM CALL 312 8245 FIT ADOERMENT TO TEST SERVICE | $0 | $0 | Jul 6, 1999 |
| Jul 11, 1997 | 34157664J | RESOLVE | Non-Hazardous | WORK WITHOUT A PERMIT IN THAT A SIDEWALK SHED HAS BEEN ERECTED AT FRONT OF BUILDING. REMEDY: OBTIAN PERMIT FORM THIS ... | $0 | $0 | Dec 11, 1997 |
| Mar 11, 1997 | 34136790H | RESOLVE | Hazardous | FAILURE TO POSTED DOT PERMIT FOR COMTAINER ON STREER IN FRONT OF 243 WEST 55 STREET REMEDY POST DOT PERMIT AS PER CODE | $0 | $0 | Nov 6, 1997 |
| Mar 11, 1997 | 34136788Z | RESOLVE | Non-Hazardous | WORK WITHOUT PERMIT UPON INSPECTION AT SAID PREMISES ELECTRICAL WORK HAS BEEN DONE AND INCOMPLETE CONSIST NEW BX WIRI... | $0 | $0 | Nov 6, 1997 |
| Mar 11, 1997 | 34136789K | RESOLVE | Non-Hazardous | FAILURE TO PROVIDE CONTRACTORS SIGN NO CONTRACTORS SIGN WAS POSTED AT THE TIME OF INSPECTION REMEDY PROVIDE CONTRACTO... | $0 | $0 | Nov 6, 1997 |
| Mar 11, 1997 | 34136787R | RESOLVE | Non-Hazardous | WORK WITHOUT PERMIT UPON INSPECTION AT ABOVE PREMISES PLUMBING WORK WAS OCCURRING CONSIT OF NEW COPPER SUPLY ANDRETUR... | $0 | $0 | Nov 6, 1997 |