ECB violations
722 10 Avenue, Manhattan • Block 01059 • Lot 0004
121 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Aug 5, 2026 | 39199321P | ACTIVE | CLASS - 2 | FAILURE TO PROVIDE/MAINTAIN SUFFICIENT ACCESS/WORK SPACE ABOUT ELECTRICAL EQUIPMENT. OBSERVED IN THE BASEMENT THE MAI... | $500 | $500 | Oct 15, 2026 |
| Aug 5, 2026 | 39199322R | ACTIVE | CLASS - 1 | FAILURE TO INSTALL GROUNDING ELECTRODE CONDUCTOR. OBSERVED IN THE BASEMENT THE MAIN ELECTRICAL SERVICE HAS NO ELECTRO... | $4,800 | $4,800 | Oct 15, 2026 |
| Mar 11, 2026 | 39180030P | ACTIVE | CLASS - 1 | AT TIME OF INSPECTION INSIDE UNIT 3B ONGOING PLUMBING WAS OBSERVED BEING DONE WITHOUT ANY PERMITS ON FILE FOR THE SCO... | $2,500 | $2,500 | Oct 1, 2026 |
| Jan 30, 2026 | 39175555L | ACTIVE | CLASS - 2 | AT TIME OF INSPECTION OBSERVED FAILURE TO MAINTAIN IN APT 3A GAS LINE FOR STOVE AND WATER LINE IN THE KITCHEN NOT CAP... | $6,250 | $6,250 | Apr 9, 2026 |
| Jan 30, 2026 | 39175554J | ACTIVE | CLASS - 2 | PSWO ISSUED FOR WORK WITHOUT A PERMIT IN APT 3A AT TIME OF INSPECTION OBSERVED ELECTRICAL BX WIRING HANGING DOWN FROM... | $6,250 | $6,250 | Apr 9, 2026 |
| Dec 19, 2025 | 39171004R | ACTIVE | CLASS - 2 | FAILURE TO SUBMIT CERTIFICATE OF CORRECTION FOR VIOLATION #35679418Z ISSUED ON 07/15/2024 #35679319N ISSUED ON 07/25/... | $6,250 | $6,250 | May 7, 2026 |
| Dec 19, 2025 | 39171002N | ACTIVE | CLASS - 2 | 722 10 AVE FAILURE TO SUBMIT CERTIFICATE OF CORRECTION FOR VIOLATION #35679317J ISSUED ON 07/25/2024 FOR PERMANENT DW... | $6,250 | $6,250 | May 7, 2026 |
| Dec 19, 2025 | 39171001L | ACTIVE | CLASS - 2 | FAILURE TO SUBMIT CERTIFICATE OF CORRECTION FOR VIOLATION #35679417R ISSUED ON 07/15/2024 #35679318L ISSUED ON 07/25/... | $6,250 | $6,250 | May 7, 2026 |
| Dec 19, 2025 | 39171003P | ACTIVE | CLASS - 2 | FAILURE TO SUBMIT CERTIFICATE OF CORRECTION FOR VIOLATION #35679419K ISSUED ON 07/15/2024 #35679320K ISSUED ON 07/25/... | $6,250 | $6,250 | May 7, 2026 |
| Jul 25, 2024 | 35679319N | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN A CODE-COMPLIANT MANNER. LACK OF A SYSTEM OF AUTOMATIC SPRINKLERS WHERE REQUIRED AS P... | $3,125 | $3,125 | Dec 1, 2025 |
| Jul 25, 2024 | 35679320K | ACTIVE | CLASS - 1 | BC907.7.8. FAILURE TO PROVIDE THE REQUIRED FIRE ALARM SYSTEM FOR TRANSIENT USE AT APT. 2B. PREVIOUS VIO #35679419K. R... | $6,250 | $6,250 | Dec 1, 2025 |
| Jul 25, 2024 | 35679318L | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN A CODE-COMPLIANT MANNER. FAILURE TO PROVIDE THE REQUIRED NUMBER OF MEANS OF EGRESS FO... | $6,250 | $6,250 | Dec 1, 2025 |
| Jul 25, 2024 | 35679317J | ACTIVE | CLASS - 1 | PERMANENT DWELLING USED/CONVERTED FOR OTHER THAN PERMANENT RESIDENTIALPURPOSES DEPT. OF BUILDINGS RECORDS INDICATES P... | $22,000 | $22,000 | Dec 1, 2025 |
| Jul 15, 2024 | 35679417R | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.LACK OF REQUIREDNUMBER OF MEANS OF EGRESS FOR EVERY FLOOR PER B... | $2,500 | $2,500 | Dec 1, 2025 |
| Jul 15, 2024 | 35679416P | RESOLVE | CLASS - 2 | PERMANENT DWELLING USED/CONVERTED FOR OTHERS THAN PERMANENT-RESIDENTIAL PURPOSES,DEPT OF BUILDINGS RECORDS INDICATES ... | $2,500 | $2,500 | Dec 1, 2025 |
| Jul 15, 2024 | 35679419K | ACTIVE | CLASS - 1 | BC 907.2.8 FAILURE TO PROVIDE FIRE ALARM SYSTEM FOR TRANSIENT USE AT APT 2B.REM:DISCONTINUE ILLEGAL OCCUPANCY. | $2,500 | $2,500 | Dec 1, 2025 |
| Jul 15, 2024 | 35679418Z | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.LACK OF SYSTEM OF AUTOMATIC SPRINKLER WHERE IS REQUIRED PER BC ... | $1,250 | $1,250 | Dec 1, 2025 |
| Apr 14, 2023 | 39083816M | ACTIVE | CLASS - 2 | I OBSERVED IN BASEMENT AREA ALL GAS METERS AND SOME GAS PIPING FOR HOUSE SIDE REMOVED AND THE ONLY PERMIT ON FILE WAS... | $1,250 | $0 | Aug 10, 2023 |
| Dec 8, 2022 | 39075380K | RESOLVE | CLASS - 2 | AT THE TIME OF MY INSPECTION I OBSERVED IN THE BASEMENT INSTALLATION OF NEW REFRIGERATION COMPRESSOR IN THE BASEMENT ... | $0 | $0 | Oct 26, 2023 |
| Dec 8, 2022 | 35658546K | ACTIVE | CLASS - 2 | ELECTRICAL WORK W/O PERMIT.OBSERVED IN BASEMENT INSTALLATION OF NEW REFRIGERATION COMPRESSOR FOR FRIDGE IN STORE WITH... | $800 | $800 | Sep 7, 2023 |
| Jul 20, 2021 | 39044682Y | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLAINT MANNER I OBSERVED IN CELLAR FOR APARTMENT 1B GAS LINE HAVING SLIGHT CO... | $625 | $0 | May 19, 2022 |
| Jul 17, 2020 | 39025648R | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDINGS ... | $3,125 | $0 | Feb 11, 2021 |
| Dec 19, 2019 | 35465665M | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE A SYSTEM OF AUTOMATIC SPRINKLERS WHERE REQUIRED PERBC903.2 AND 27-954 FOR TRANSIENT USE BUT APARTM... | $0 | $0 | Dec 17, 2020 |
| Dec 19, 2019 | 35465667X | RESOLVE | CLASS - 1 | FAILUER TO PROVIDE THE REQUIRED NUMBER OF MEANS OF EGRESS FOR EVERY FLOOR PER BC1018.1(2008);BC1021.1(2014)AND 27-366... | $0 | $0 | Dec 17, 2020 |
| Dec 19, 2019 | 35465666Y | RESOLVE | CLASS - 1 | BC90728-FAILURE TO PROVIDE THE REQUIRED FIRE ALARM SYSTEM FOR TRANSIENT USE AT APARTMENT#4A.PREVIOUS VIO#35298717J,35... | $0 | $0 | Dec 17, 2020 |
| Dec 19, 2019 | 35465664K | RESOLVE | CLASS - 1 | PERMANENT DWELLING USED/CONVERTED FOR OTHER THAN PERMANENT RESIDENTIALPURPOSES.DOB RECORDS INDICATES PREMISES TO BE L... | $0 | $0 | Dec 17, 2020 |
| Nov 1, 2019 | 35461107J | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIOENRS ORDER TO FILE A CERTIFICATE OF CORRETCION WITH TEH DEPT OF BUILDING FOR VIOL... | $1,250 | $0 | Apr 30, 2020 |
| Nov 1, 2019 | 35461108L | RESOLVE | CLASS - 1 | TO COMPLY WITH AN ORDER OF THE COMMISSIONER FOR #35335193H ISSUED ON 6-6-18 COMPLY W/ COMMISSIONER ORDER | $3,125 | $0 | Apr 30, 2020 |
| Nov 1, 2019 | 35461109N | RESOLVE | CLASS - 1 | UNLAWFUL ACTS FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER FOR VIOLATION #35372687K ISSUED ON 0124-18 COMPLY W... | $0 | $0 | Apr 30, 2020 |
| Sep 18, 2019 | 35414866Z | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CTO FILE A CERT OF CORRECTION W/DOB'S FOR VIO#35335292X ISSUED ON 6-6-18. REMEDY... | $0 | $0 | Mar 5, 2020 |
| Jul 10, 2019 | 35393331M | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35414729M ISSUED ON 04-27-19 & TO FILE A C OF C PURSUAN... | $0 | $0 | Nov 26, 2019 |
| Jul 10, 2019 | 35393330K | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35335192X ISSUED ON 06-06-18 & TO FILE A C OF C PURSUAN... | $3,125 | $0 | Nov 21, 2019 |
| Jun 18, 2019 | 37015251R | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION #35344298Z ISSUED ON 08-28-2018 AND TO FILE... | $1,250 | $0 | Dec 12, 2019 |
| May 14, 2019 | 35417741Z | ACTIVE | CLASS - 1 | BC907.2.8 FAILURE TO PROVIDE A FIRE ALARM SYSTEM FOR TRANSIENT USE INAPT 3D. PREVIOUS VIOLATION 35383291H, 35383465Z.... | $6,250 | $0 | Sep 3, 2020 |
| May 14, 2019 | 35417743M | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER LACK OF REQUIREDNUMBER OF MEANS OF EGRESS FOR EVERY FLOOR PER B... | $6,250 | $0 | Sep 3, 2020 |
| May 14, 2019 | 35417740R | RESOLVE | CLASS - 1 | PERMANENT DWELLING USED/CONVERTED FOR OTHER THAN PERMANENT RESIDENTIALPURPOSES BY DOB PREMISES TO BE LEGALLY APPROVED... | $15,000 | $0 | Sep 3, 2020 |
| May 14, 2019 | 35417742K | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. LACK OF A SYSTEM OF AUTOMATIC SPRINKLER WHERE REQUIRED PER BC ... | $3,125 | $0 | Sep 3, 2020 |
| May 5, 2019 | 35398741H | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUM/VIO #35372688M ISSUED ON 01/24/18 &/OR TO FILE A C O... | $3,125 | $0 | Sep 19, 2019 |
| May 4, 2019 | 35398707Y | RESOLVE | CLASS - 1 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUM/VIO #35335193H ISSUED ON 06/06/18 &/OR TO FILE A C O... | $6,250 | $0 | Sep 19, 2019 |
| May 4, 2019 | 35398706M | RESOLVE | CLASS - 1 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUM/VIO #35372687K ISSUED ON 01/24/18 &/OR TO FILE A C O... | $6,250 | $0 | Sep 19, 2019 |
| Apr 27, 2019 | 35414729M | RESOLVE | CLASS - 1 | REMOVED OR DEFACED A WRITTEN POSTED VACATE ORDER. AT TIME OF INSPECTION NOTED: VACATE ORDER#480462-496109 ISSUED ON 6... | $0 | $0 | Sep 5, 2019 |
| Apr 27, 2019 | 35398256Y | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35335192X ISSUED ON 06-06-18 & TO FILE A C OF C PURSUAN... | $3,125 | $0 | Sep 5, 2019 |
| Mar 6, 2019 | 35383472R | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER TO FILE A CCERT OF CORRECTION W/THE DOB FOR THE ECB VIO#35373688R. REMEDY: FILE ... | $1,250 | $0 | Oct 31, 2019 |
| Mar 6, 2019 | 35383470N | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER TO FILE A CERT OF CORRECTION W/THE DOB'S FOR THE VIO#35373686N ISSUED ON 12-21-1... | $1,250 | $0 | Oct 31, 2019 |
| Mar 6, 2019 | 35383469X | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER TO FILE A CERT OF CORRECTION W/THE DOB FOR THE VIO#35373685L ISSUED ON 12-21-18.... | $1,250 | $0 | Oct 31, 2019 |
| Mar 6, 2019 | 35383467M | ACTIVE | CLASS - 2 | WORK W/O A PERMIT. WORK NOTED: AT APT#4C & 3D ERECTED FULL HEIGHT PARTITION WALLS TO SUBDIVIDE THE LIVING AREA-LIVING... | $1,250 | $0 | Oct 31, 2019 |
| Mar 6, 2019 | 35383465Z | RESOLVE | CLASS - 1 | SEC. 907.2.8 FAILURE TO PROVIDE FIRE ALARM SYSTEM FOR TRANSIENT USE ATAPT#3D & 4C CLASS'J'. PREVIOUS VIO#35373688R. R... | $2,500 | $0 | Oct 31, 2019 |
| Mar 6, 2019 | 35383464R | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLAINT MANNER. LACK OF A SYSTEM OFAUTOMATIC SPRINKLER WHERE US REMOVED AS PER BC ... | $1,250 | $0 | Oct 31, 2019 |
| Mar 6, 2019 | 35383462N | RESOLVE | CLASS - 1 | PERMANENT DWELLING USED/CONVERTED FOR OTHER THAN PERMANENT-RESIDENTIALPURPOSES. DOB'S RECORDS INDICATES PREMISES TO B... | $6,000 | $0 | Oct 31, 2019 |
| Mar 6, 2019 | 35383463P | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLAINT MANNER. LACK OF REQUIRED # OF MEANS OF EGRESS FOR EVERY FLOOR PER BC 1018.... | $2,500 | $0 | Oct 31, 2019 |