ECB violations
Environmental Studies Hs, Manhattan • Block 01065 • Lot 0001
147 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Apr 29, 2014 | 35094286M | RESOLVE | CLASS - 1 | RE-ISSUE # 34921702M. NO 2ND MEANS OF EGRESS PER BC 1018.1; 27-366. AT 6TH FLOOR AUDITORIUM, 2 SETS OF DOUBLE EXIT DO... | $0 | $0 | Jun 19, 2014 |
| Apr 29, 2014 | 35094285K | RESOLVE | CLASS - 2 | RE-ISSUE # 35015675H. SPALLING - MISSING PLASTER. AT SHOP AREA 1ST FLOOR, SPALLING & MISSING PLASTER & MASONRY FIRE R... | $0 | $0 | Jun 19, 2014 |
| Apr 29, 2014 | 35094293K | RESOLVE | CLASS - 2 | MISSING FIRE STOPPING. AT BASEMENT ELECTRIC METER ROOM, PENETRATIONS IN TERRACOTTA WALL & CEILING WITH CONDUITS & OPE... | $0 | $0 | Jun 19, 2014 |
| Apr 29, 2014 | 35094291R | RESOLVE | CLASS - 2 | BC 903.6.3. UNPAINTED SPRINKLER/STANDPIPE PER LOCAL LAW 58/2009; BC 903.6.3 RETROACTIVE. THE COMBINATION SPRINKLER & ... | $0 | $0 | Jun 19, 2014 |
| Apr 29, 2014 | 35094289H | RESOLVE | CLASS - 3 | SPALLING PLASTER. IN 5TH FLOOR STAIR "D", SPALLING & MISSING PLASTER WALL SURFACES. REMEDY: REPAIR WALL PLASTER SURFACE. | $0 | $0 | Jun 19, 2014 |
| Apr 29, 2014 | 35094294M | RESOLVE | CLASS - 2 | MISSING FIRE STOPPING. AT 6TH FLOOR PUMP ROOM BEHIND AUDITORIUM, PENETRATIONS & HOLES IN RISER CHASE WALLS & CEILING ... | $0 | $0 | Jun 19, 2014 |
| Apr 29, 2014 | 35094288X | RESOLVE | CLASS - 2 | INOPERATIVE PANIC HARDWARE PER 27-371(K). AT 1ST FLOOR CAFETERIA, BROKEN & DEFECTIVE PANIC BAR ASSEMBLY TO CORRIDOR -... | $0 | $0 | Jun 19, 2014 |
| Apr 29, 2014 | 35094287Y | RESOLVE | CLASS - 2 | DEFECTIVE DOOR FRAME. AT 3RD FLOOR STAIR E, THE METAL DOOR FRAME HAS BROKEN AT TOP PROVIDING NO HINGE ANCHORAGE. REME... | $0 | $0 | Jun 19, 2014 |
| Apr 29, 2014 | 35094290P | RESOLVE | CLASS - 3 | CRACKED MASONRY WALLS. AT BULKHEADS "D" & "E", HORIZONTAL & VERTICAL CRACKS IN MASONRY WALLS. REMEDY: REPAIR ALL MASO... | $0 | $0 | Jun 19, 2014 |
| Apr 2, 2013 | 35015675H | RESOLVE | CLASS - 2 | REISSUE 34921700Z. SPALLING PLASTER ON SHOP ROOM CEILING AND AROUND I-BEAMS. REMEDY: MAINTAIN BLDG. | $0 | $0 | May 16, 2013 |
| Apr 2, 2013 | 35015676J | RESOLVE | CLASS - 2 | ROOFTOP SHAFTWAY ROOM LOCATED IN CENTER OF ROOM LOCATED IN CENTER OF ROOM WHERE ELEVATION CHANGES FROM 6 FLR TO 4 FLR... | $0 | $0 | May 16, 2013 |
| Nov 28, 2012 | 38223670Y | RESOLVE | CLASS - 2 | 97X10 - ENTIRE DEVICE INOPERATIVE MUST REPAIR AND BRING BACK TO SVC. | $2,500 | $0 | Jan 17, 2013 |
| May 30, 2012 | 38221978L | RESOLVE | CLASS - 1 | 28-116.4.1: 97R07;NEW TRACTION SHEAVE INSTALLED. OPERATING DEVICE WITHOUT THE CERT OF COMPLIANCE. NO REPORT OF INSPEC... | $0 | $0 | Jul 30, 2015 |
| May 3, 2012 | 34953839J | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG NOTED AT 10 AVE SIDE CONCRETE SPALLING ABOVE DECORATIVE CORNICE SECTION OF CONCRETE LOOSE W/... | $5,000 | $0 | Jun 21, 2012 |
| May 3, 2012 | 34953840R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG NOTED AT REAR ROOF SHAFTWAY,CONCRETE SPALLING/MISSING ALSO WATER PENETRATION INTO FOUNDATION... | $1,250 | -$1,250 | Jun 21, 2012 |
| Jul 21, 2011 | 34921704X | RESOLVE | CLASS - 3 | ELECTRIC ROOM STORAGE. ELECTRIC ROOM W/STORAGE OF VARIOUS PERSONAL ITEMS. REMEDY: REMOVE ALL ITEMS, MAINTAIN STORAGE ... | $0 | $0 | Sep 15, 2011 |
| Jul 21, 2011 | 34921702M | RESOLVE | CLASS - 1 | NO 2ND MEANS OF EGRESS PER BC 1018.1 & 27-366. AT 6TH FLR AUDITORIUM, 2 CONNECTED SETS OF DOUBLE DOORS. EXIT TO 6TH F... | $0 | $0 | Sep 15, 2011 |
| Jul 21, 2011 | 34921703Y | RESOLVE | CLASS - 2 | NO FIRE STOP. AT ELECTRIC ROOM, HOLE IN WALL ABOVE DOOR ON RIGHT. REMEDY: SEAL ALL WALL OPENINGS, MAINTAIN FIRE STOP. | $0 | $0 | Sep 15, 2011 |
| Jul 21, 2011 | 34921700Z | RESOLVE | CLASS - 2 | REISSUE #34847770L SPALLING CONCRETE CEILING. AT 1ST FLR SHOP AREA & GENERATOR ROOM, SPALLING CONCRETE AROUND CEILING... | $0 | $0 | Sep 15, 2011 |
| Jul 21, 2011 | 34921701K | RESOLVE | CLASS - 1 | PLACE OF ASSEMBLY W/O C/O. AT 6TH FLR, AUDITORIUM W/FIXED SEATING FOR 190 AND NO PA C/O ISSUED. REMEDY: OBTAIN PA C/O. | $0 | $0 | Sep 15, 2011 |
| Dec 10, 2010 | 34883207K | RESOLVE | CLASS - 2 | — | $0 | $0 | Feb 3, 2011 |
| Apr 15, 2010 | 34847770L | RESOLVE | CLASS - 2 | REISSUE 34793508P FAILURE TO MAINTAIN OBSERVED AT SHOP AREA ON 1 FL SPALLING CEMENT ON CEILING EXPOSED I-BEAM REM: MA... | $0 | $0 | Jul 15, 2010 |
| Apr 15, 2010 | 34847769Y | RESOLVE | CLASS - 2 | REISSUE 34793506L FAILURE TO MAINTAIN OBSERVED TO EASTSIDE PARAPET GYM ABOVE AC UNIT SPALLING CRACKED BRICK FACADE RE... | $0 | $0 | Jul 15, 2010 |
| Jul 9, 2009 | 34793507N | RESOLVE | CLASS - 2 | THE PLASTER IS SPALLING OFF THE WALL LOCATED AT STAIRWAY "E" BETWEEN 5TH & 6TH FLR. REMEDY: REPAIR/REPLACE PLASTER ON... | $0 | $0 | Nov 19, 2009 |
| Jul 9, 2009 | 34793505J | RESOLVE | CLASS - 2 | THE EXTERIOR BRICK FACADE IS CRACKED AT ROOF LEVEL ABOVE THE GYMNASIUMON THE EASTERN SIDE. (CRACK IS VISIBLE FROM ROO... | $0 | $0 | Nov 19, 2009 |
| Jul 9, 2009 | 34793508P | RESOLVE | CLASS - 2 | THE CONCRETE IS SPALLING OFF THE CEILING LOCATED IN THE SHOP AREA ON THE 1ST FLR LEVEL. REMEDY: REPAIR/REPLACE CONCRETE. | $0 | $0 | Nov 19, 2009 |
| Jul 9, 2009 | 34793506L | RESOLVE | CLASS - 2 | THE GAS METER ROOM IS LACKING FIRE STOPPING AT THE 1ST FLR LEVEL. REMEDY: PROVIDE/MAINTAIN FIRE STOPPING IN GAS METER... | $0 | $0 | Nov 19, 2009 |
| Dec 8, 2008 | 38201237X | RESOLVE | CLASS - 2 | 52O02.56Y13.42D06.62O02.53O02.60Q03.01L10.02L10.17H11.10H11.76O02.77O02.29O02.52.53.76O CLEAN FOR PROPER INSPECTION 4... | $500 | $0 | Apr 22, 2010 |
| Aug 1, 2008 | 34697755M | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG. ON INSPECTION (TAR) IS LEAKING THRU DROP CEILING IN BOY'S BATHROOM & IN ROOM 6024 (SERIOUS)... | $0 | $0 | Sep 11, 2008 |
| Aug 1, 2008 | 34697754K | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF CLOSING RE ISSUE 34577958X. 6TH FLOOR ELEC CLOSET #6089 RACKED, 3RD FLOOR GYMNASIUM REAR STAIRWELL... | $0 | $0 | Sep 11, 2008 |
| Jun 20, 2008 | 38185797R | RESOLVE | Non-Hazardous | 55Y10,13.85M05.43H08.59Q03.41R08,11. 55Y HOIST MACHINE OILED REPAIR SEAL & CLEAN 85M 5YR TAG MISSING PERFORM & FILE T... | $350 | $0 | Oct 9, 2008 |
| Jun 20, 2008 | 38185796P | RESOLVE | Non-Hazardous | 16B07.21I10.83O02. 16B STENCIL FL'S ON HOISTWAY DOORS 21I REPAIR DOOR LOCK ARM DAMAGED 83O OVERHAUL & CLEAN DEVICE TO... | $350 | $0 | Oct 9, 2008 |
| Jun 20, 2008 | 38185798Z | RESOLVE | Non-Hazardous | 41R09,11.86M05.55Y10,13.56B10.02.51O02. 41R F1 FUSE HAS JUMPER REMOVE & REPLACE 86M 2YR MISSING PERFORM & FILE TEST W... | $350 | $0 | Oct 9, 2008 |
| Feb 29, 2008 | 38182261P | RESOLVE | Hazardous | 51Q03.84H11.08V01.66O02. 51Q03 PROVIDE ROPE GUARD IN MACHINE RM 84H11 REPLACE WORN MO ROLLERS ON 2,3,4 FLS 08V01 ADJU... | $0 | $0 | Apr 24, 2008 |
| Feb 29, 2008 | 38182260N | RESOLVE | Hazardous | 16B01.03R09.84M07. 16B01 ADJUST HALL DOOR ECCENTRIES AT LOBBY LEVEL (STREET SIDE) 03R09 REMOVE ALL ITEMS IN ELEVATOR ... | $0 | $0 | Apr 24, 2008 |
| Jul 12, 2007 | 34577959H | RESOLVE | Hazardous | FAILURE TO MAINTAIN- INTERIOR. STAIRWAY E BULKHEAD WALLS AND CEILINGS DAMAGED DUE TO WATER PENETRATION. PLASTER ON WA... | $0 | $0 | Sep 13, 2007 |
| Jul 11, 2007 | 34577958X | RESOLVE | Hazardous | EXIT DOOR NOT SELF CLOSING. LOCATIONS OF DOORS THAT ARE RACKED IN THE FRAME AND CANNOT OPEN AND CLOSE PROPERLY. 6TH F... | $0 | $0 | Sep 13, 2007 |
| Feb 13, 2007 | 38162842P | RESOLVE | Non-Hazardous | 03B07.03/B-PROVIDE INSIDE CAR AREA TO MATCH CAR CAPACITY.(INSIDE AREA 67.29 SQ FT CAPACITY PLATE READS 2,000 LBS) | $0 | $0 | Apr 12, 2007 |
| Apr 20, 2006 | 34519329H | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN.DEFECT NOTED:6TH FL WATER DAMAGE AT CEILING RM 6024 RACKED, STAIR DOOR D RACKED,6001 AUDITORIUM D... | $0 | $0 | Jul 20, 2006 |
| Apr 20, 2006 | 34519330P | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN.DEFECT NOTED:2ND FL STAIR D 444 SIDE RACKED.1ST FL. STAIR E DOOR RACKED,1023 DOOR MISSING,1013A D... | $0 | $0 | Jul 20, 2006 |
| Dec 1, 2005 | 38156396N | RESOLVE | Non-Hazardous | 83L10. (83-L-10)ELEVATOR NOT WORKING, REPAIR/RESTORE TO SERVICE SO THAT A PROPER INSPECTION MAY BE PERFORMED BY D.O.B... | $0 | $0 | Mar 9, 2006 |
| Dec 1, 2005 | 38156395L | RESOLVE | Non-Hazardous | 02L10/83O02/84L10. (02-L-10)ALARM SYSTEM NOT WORKING, REPAIR. (84-L-10)COMMUNICATION DEVICE IN SIDE CAR, REPAIR. | $0 | $0 | Mar 9, 2006 |
| Dec 1, 2005 | 38156397P | RESOLVE | Non-Hazardous | 02L10/83O02/84L10 (02-L-10) ALARM SYSTEM NOT WORKING, REPAIR (84-L-10)COMMUNICATION DEVICE IN CAR NOT WORKING, REPAIR. | $0 | $0 | Jan 19, 2006 |
| Sep 14, 2005 | 32048491P | RESOLVE | Non-Hazardous | 50A/50B. 50A-PROVIDE A PEMENANT LADDER FOR ACCESS TO THE TOP FOR THE BOILER. 50B-NO CHAINS ON SAFETY VALVES TO PERMIT... | $0 | $0 | Nov 3, 2005 |
| Sep 14, 2005 | 32048492R | RESOLVE | Non-Hazardous | 50A/50B. 50A-PROVIDE A PEMANENT LADDER FOR ACCESS TO THE TOP OF THE BOILER. 50B-PROVIDE A CHAIN FOR OPENING & CLOSING... | $0 | $0 | Nov 3, 2005 |
| Jul 20, 2005 | 38153935J | RESOLVE | Non-Hazardous | #D06/40T07 #-FIRE EXTINGUISHER IN ELEVATOR MACHINE ROOM IS NOT SECUREDTO ELEVATOR MACHINE ROOM WALL.40-ELEVATOR MACHI... | $0 | $0 | Sep 8, 2005 |
| Apr 22, 2005 | 34476907N | RESOLVE | Hazardous | FAILURE TO MAINTAIN EXTERIOR BUILDING WALL HAZARDOUS DEFECT NOTED AT BULKHEAD ROOF DEFECTIVE ROOFING MEMBRANCE GUTTER... | $2,500 | $0 | Jun 9, 2005 |
| Oct 15, 2004 | 38149017Z | RESOLVE | Non-Hazardous | 85BB05/ 44H10/ 55Y13/ 57Q03/ 60T15/ 16P07/ 17H11/ 84H11/ 10H11/ 38O02/33O02/ 66O02/ 67O02/ 68O02/ 71O02/ 57=INSTALL C... | $180 | $0 | Jan 18, 2005 |
| Oct 15, 2004 | 38149016R | RESOLVE | Non-Hazardous | 15I10/ 84B11/ 47H13/ 34Q03/ 84BB05/ 60T15/ 28B01/ 27H11/ 17H11/ 47O02/38O02/ 33O02/ 66O02/ 67O02/ 68O02/ 71O02/ 84=RE... | $180 | $0 | Jan 18, 2005 |
| Oct 6, 2004 | 38149013L | RESOLVE | Non-Hazardous | 85BB5/55Y13/60T15/71K11/33O2/38O2/39O2/66O2/67O2/68O2 60 COMPANY NAME ON MAIN LINE. 71 UNDERSIDE PLATFORM RUSTED BAD. | $350 | $0 | Nov 18, 2004 |