506-514 West 43 Street, Manhattan • Block 01071 • Lot 0023
51 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Oct 14, 2025 | 39163514R | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED SECURITY CHAIRS OBSTRUCTING PASSAGEWAYS/HALLWAYS. LOC... | $1,280 | $1,280 | Jul 23, 2026 |
| Nov 18, 2024 | 39130599Y | RESOLVE | CLASS - 2 | I OBSERVED IN THE 6TH FLOOR BATHROOM, THE ELEVATOR MOTOR ROOM AND THE MAIN ELECTRICAL ROOM THE FAILURE TO PROVIDE GFC... | $1,200 | $0 | Feb 20, 2025 |
| Nov 18, 2024 | 39130601Y | RESOLVE | CLASS - 1 | I OBSERVED IN THE KITCHEN/PANTRY IN THE REAR BUILDING A DEFECTIVE EXTENSION CORD IN USE AND AN EXTENSION PASSING ACRO... | $400 | $0 | Feb 20, 2025 |
| Nov 18, 2024 | 39130600M | RESOLVE | CLASS - 1 | I OBSERVED ON THE 6TH FLOOR IN THE BATHROOM NEXT TO THE "B" STAIRS THE ELECTRICAL PANELS OPEN WITH EXPOSED AND ENERGI... | $1,600 | $0 | Feb 20, 2025 |
| Nov 18, 2024 | 39130589K | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $2,500 | $0 | Feb 20, 2025 |
| Nov 18, 2024 | 39130582H | RESOLVE | CLASS - 2 | OBSERVED AT BASEMENT FERNCO COUPLING AND JIM CAP INSTALLED ON 2 INCH WASTE PIPE ALSO 2 INCH PIPE BEING SUPPORTED WITH... | $0 | $0 | Feb 20, 2025 |
| Nov 18, 2024 | 39130588Z | RESOLVE | CLASS - 2 | OBSERVED AT 8TH FLOOR ROOF LEVEL, SHEET METAL COVERING TO STAND PIPE VALVE POSING A RISK OF A SEVERE LACERATION., REP... | $0 | $0 | Feb 20, 2025 |
| Nov 18, 2024 | 39130590H | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING. OBSERVED NON SELF CLOSING DOORS THROUGHOUT BUILDING. INCASE OF FIRE THIS IS A HAZARD CONI... | $0 | $0 | Feb 20, 2025 |
| Nov 16, 2023 | 39099508R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED AT EXP#3 (WEST 43RD ST SIDE) FACADE WITH MISSING BRICKS ... | $0 | $0 | Jan 25, 2024 |
| Nov 16, 2023 | 39099507P | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED THROUGHOUT PARKING GARAGE 1ST & 2ND LEVELS, SEVERAL AREA... | $1,250 | $0 | Feb 22, 2024 |
| Aug 2, 2023 | 39091682X | RESOLVE | CLASS - 2 | NO EMERGENCY LIGHTING FROM 2ND FL TO 7TH FL, CORRIDORS OF BOTH BUILDINGS. (EMERGENCY LIGHTING IS REQUIRED TO ILLUMINA... | $0 | -$1,250 | Oct 12, 2023 |
| Jan 13, 2023 | 39077737N | RESOLVE | CLASS - 2 | OBSERVED RESIDENTIAL GAS FLEX INSTALLED ON COMMERCIAL DRYERS. AS PER FGC 411 1. RIGID METALLIC PIPE AND FITTINGS. SPA... | $312 | $0 | Mar 23, 2023 |
| Jan 11, 2023 | 39077590H | RESOLVE | CLASS - 1 | I OBSERVED IN THE BASEMENT AREA OF THE REAR BUILDING THE INSTALLATION OF A TEMPORARY BLOWER FAN TO THE BOILER DISCONN... | $800 | $0 | Aug 10, 2023 |
| Jan 11, 2023 | 39077566H | RESOLVE | CLASS - 2 | OBSERVED: FROM 2ND FL TO 7TH FL, CORRIDORS AND STAIR CASE A,B,C & D, EMERGENCY LIGHTING ARE REQUIRED TO ILLUMINATE AN... | $625 | $0 | Aug 10, 2023 |
| Jan 11, 2023 | 39077593N | RESOLVE | CLASS - 1 | I OBSERVED TEMPORARY WIRING INSTALLED THROUGH THE OPENED COVER OF AN 3PHASEDISCONNECT, THIS FAILS TO PROTECT THE WIRI... | $1,600 | $0 | Aug 10, 2023 |
| Jan 11, 2023 | 39077565X | RESOLVE | CLASS - 2 | OBSERVED. AT CELLAR LEVEL,ELECTRICAL RM, STORAGE RMS NEAR GAS METER, GAS METER AREA, ALSO STORAGE CLOSET THROUGH THE ... | $3,125 | $0 | Mar 23, 2023 |
| Jan 11, 2023 | 39077564Y | RESOLVE | CLASS - 2 | OBSERVED: AT CELLAR LEVEL, CORRIDOR, FIRE PROOF WALLS/ STORAGE ROOMS AND WATER HEATER ROOM, SEVERAL CRACKS ,MISSING B... | $0 | $0 | Mar 23, 2023 |
| Jan 11, 2023 | 39077592L | RESOLVE | CLASS - 1 | I OBSERVED IN THE 6TH FLOOR "C SIDE" LINEN CLOSET IN IMPROPER INSTALLATION OF A TEMPORARY LIGHT SOCKET, ALSO NOTED IN... | $1,600 | $0 | Aug 10, 2023 |
| Jan 11, 2023 | 39077589K | RESOLVE | CLASS - 2 | I OBSERVED ON THE ROOF LEVEL OF THE 1ST BUILDING THE UNPERMITTED USE OF EMT THROUGH CONCRETE WALL SUPPLYING POWER TO ... | $250 | $0 | Aug 10, 2023 |
| Jan 11, 2023 | 39077591J | RESOLVE | CLASS - 1 | I OBSERVED IN THE POOL AREA THE USE OF FLEXIBLE CORDS THROUGH A GLASS AND METAL FRAME WALL TO SUPPLY POWER TO APPLIAN... | $1,600 | $0 | Aug 10, 2023 |
| Apr 13, 2022 | 39060194P | RESOLVE | CLASS - 1 | ROPE GRIPPER DEFECTIVE WILL NOT CLOSE AFTER GOVERNOR SWITCH OPEN OR PULLING THE MAIN LINE IN THE OFF POSITION. MUST P... | $1,250 | $0 | Sep 15, 2022 |
| Aug 23, 2021 | 39046435X | RESOLVE | CLASS - 2 | - OBSERVED: SELF-CLOSING FIREPROOF ON STAIRS A, B, C & D 90% OF DOORS DO NOT CLOSE AUTOMATICALLY DUE TO DOOR LEAVES O... | $0 | $0 | Oct 7, 2021 |
| Aug 23, 2021 | 39046433M | RESOLVE | CLASS - 2 | OBSERVED. AT THE BASEMENT LEVEL, MECHANICAL ROOMS, SEVERAL HOLES IN THE CONCRETE SLAB, BLOCK WALLS DUE TO THE PENETRA... | $0 | $0 | Oct 7, 2021 |
| Aug 23, 2021 | 39046436H | RESOLVE | CLASS - 2 | -OBSERVED. AT THE BASEMENT LEVEL, MECHANICAL ROOMS, EMERGENCY EXIT CORRIDORS, SEVERAL CRACKS BETWEEN 6-7 FEET, OPENIN... | $0 | $0 | Feb 10, 2022 |
| Aug 23, 2021 | 39046427X | RESOLVE | CLASS - 2 | I OBSERVED IN THE ELEVATOR MOTOR ROOM THE IMPROPER FUSING OF THE ELEVATOR MOTORS THE LOAD SIDE WAS FUSED AT 100 AMPS ... | $1,200 | $0 | Feb 10, 2022 |
| Aug 23, 2021 | 39046425M | RESOLVE | CLASS - 2 | I OBSERVED IN THE CORRIDORS ON ALL FLOORS CONVENIENCE RECEPTACLES NOT OF THE TAMPER-RESISTANT TYPE NOR TAMPER-PROOFED... | $0 | $0 | Oct 7, 2021 |
| Aug 23, 2021 | 39046426Y | RESOLVE | CLASS - 2 | I OBSERVED IN THE ELECTRICAL / JANITOR'S CLOSET CONVENIENCE RECEPTACLES NOT OF THE GFCI TYPE NOR GFCI PROTECTED. PHOT... | $1,200 | $0 | Feb 10, 2022 |
| Aug 23, 2021 | 39046434Y | RESOLVE | CLASS - 2 | - OBSERVE: AT ROOF LEVEL, EXPOSURE # 2, LOSS OF FLASHING, APPROXIMATE LENGTH OF 90 FEET, DRAINS NOT WORKING DUE TO ER... | $0 | $0 | Oct 7, 2021 |
| Aug 23, 2021 | 39046423Z | RESOLVE | CLASS - 2 | I OBSERVED IN BASEMENT/ CELLAR SANITARY PIPING SEVERELY CORRODED CAUSING PIPING TO START FLAKING AND CHIPPING., REPAI... | $0 | $0 | Oct 7, 2021 |
| Jul 3, 2018 | 32097262M | RESOLVE | CLASS - 2 | B254,32A,50A,50B,50C. AS PER CLASS 2 (B254) 28.301.1 FAILURE TO MAIN TAIN: 32A=EXPOSED ELECTRICAL WIRING; 50A-"U" RAT... | $0 | $0 | Aug 23, 2018 |
| Nov 21, 2017 | 38259780J | RESOLVE | CLASS - 2 | 59BB15,68B7. 59BB15 BRAKE MAINTENANCE TAG EXPIRED.68B7 BRAKE MAINTENANCE NOT LOGGED AS PER A17.1 2003 & APPENDIX K3 8... | $0 | $0 | Jan 11, 2018 |
| Nov 21, 2017 | 38259781L | RESOLVE | CLASS - 2 | 60X10,59BB15,68B7,39X10,100L10,70O2. 60 MOTOR ROOM LIGHTS INOPERATIVE.59 BRAKE MAINT TAG EXPIRED.68 BRAKE MAINTENANCE... | $0 | $0 | Jan 11, 2018 |
| Nov 16, 2017 | 38259553J | RESOLVE | CLASS - 1 | DOOR MONITORING SYSTEM IS INOPERATIVE-REPAIR;ROPE GRIPPER WAS DISASSEMBLED-REPAIR;TOP OF CAR HAS OIL-CLEAN;HOIST MOTO... | $1,000 | $0 | Jan 4, 2018 |
| Nov 16, 2017 | 38259552H | RESOLVE | CLASS - 1 | 6B10:26Y2;56Y2:DOOR RESTRICTOR MONITORING SYSTEM IS INOPERATIVE,REPAIRTOJP OF CAR HAS OIL-CLEAN;HOIST MACHINE/MOTOR I... | $1,000 | $0 | Jan 4, 2018 |
| Oct 18, 2013 | 38228989Z | RESOLVE | CLASS - 2 | 40B10- CHECKING MAIN LINE DISCONNECT (FUSES) ONCE PULLED ROPE GRIPPER SETS & STAYS SET WHEN MAIN LINE DISCONNECT IS P... | $0 | $0 | Dec 5, 2013 |
| Nov 30, 2012 | 38224382Y | RESOLVE | CLASS - 2 | 56B10:VIBRATION, NOISE COMING FROM MACHINE. | $0 | $0 | Jan 17, 2013 |
| Nov 5, 2012 | 38223695K | RESOLVE | CLASS - 2 | 40O02,40D06,40B10,52O02. 40D-PROVIDE MISSING FLUORESCENT BULBS AND COVERS. 40B-PATCH, REPAIR FLOORS, REMOVE EXISTING ... | $0 | $0 | Dec 20, 2012 |
| Nov 5, 2012 | 38223694Z | RESOLVE | CLASS - 2 | 52K02,61G11,40D06,40O02. 2K-CABLES HAVE RUST(ROUGE) CLEAN & MONITOR ROPES.40D-SECURE GFCI OUTLET, PROVIDE COVERS ON F... | $0 | $0 | Dec 20, 2012 |
| Jan 27, 2010 | 36011918L | RESOLVE | CLASS - 2 | FAILURE TO FILE AN ARCHITECT/ENGINEER REPORT CERTIFYING EXIT/DIRECTIONAL SIGNS ARE CONNECTED TO EMERGENCY POWER SOURC... | $0 | $0 | Nov 18, 2010 |
| May 22, 2009 | 36009231M | RESOLVE | CLASS - 2 | FAILURE TO FILE AN AMENDED SIXTH ROUND REPORT ACCEPTABLE TO THIS DEPARTMETN INDICATING CORRECTION OF UNSAFE CONDITION... | $0 | $0 | Jan 6, 2010 |
| Jan 9, 2009 | 36007328J | RESOLVE | CLASS - 2 | FAILURE TO FILE AN AMENDED SIXTH ROUND REPORT ACCEPTABLE TO THIS DEPARTMENT INDICATING CORRECTION OF UNSAFE CONDITION... | $0 | $0 | Sep 9, 2011 |
| Mar 22, 2007 | 38165428N | RESOLVE | Non-Hazardous | 38O02,55Y13,59Q3,17H07.38-CLEAN CAR TOP.55-CLEAN & SEAL MACHINE.59-MISSING GUARDS ON LIGHTS.07-HALL GABS WORN-PROVIDE. | $0 | $0 | May 17, 2007 |
| Mar 22, 2007 | 38165427L | RESOLVE | Non-Hazardous | 38O02,55Y13,59Q3,17H07.38-CLEAN CAR TOP.55-CLEAN & SEAL MACHINE.59-MISSING GUARDS ONLIGHTS.17-HALL GIBS. | $0 | $0 | May 17, 2007 |
| May 9, 2000 | 32018851M | RESOLVE | Non-Hazardous | 36. 36- AO SMITH WATER BOILER (MODEL NUMBE BC 420 780) NOT REGISTERED WITH NUC DEPT OF BUILDINGS. | $350 | $0 | Jun 29, 2000 |
| May 9, 2000 | 32018425J | RESOLVE | Non-Hazardous | 36. 36- AO SMITH LP BOILER (MODEL NUMBER HW 420 892) NOT REGISTERED WITH NYC DEPT OF BUILDINGS. | $350 | $0 | Jun 29, 2000 |
| Aug 18, 1998 | 34176709H | RESOLVE | Non-Hazardous | FAILURE TO SUBMIT A FOURTH ROUND TECHNICAL ROUND TECHNICAL REPORT: PERIODIC INSPECTION OF EXTERIOR WALLS AND APPURTEN... | $0 | $0 | Feb 12, 1999 |
| May 28, 1998 | 34176479L | RESOLVE | Hazardous | FAILURE TO SUBMIT A 4TH ROUND TECHNICAL REPORT: PERIODIC INSPECTION OFEXTERIOR WALLS & APPURTENANCES AS REQUIRED BY L... | $0 | $0 | Feb 11, 1999 |
| Mar 30, 1995 | 38048056Z | RESOLVE | Non-Hazardous | 28H,46K,40U. | $0 | $0 | Jun 13, 1995 |
| Jul 20, 1993 | 38035180N | RESOLVE | Non-Hazardous | 50Y, 74 COMPLY WITH A.C. 27-1004. 74 ALUMINATE MACHINE ROOM AS YEAR CODE. | $0 | $0 | Mar 18, 1994 |
| Jul 20, 1993 | 38035181P | RESOLVE | Non-Hazardous | 50Y, 74A COMPLY WITH A.C.27-1004. 74 ALUMINATE MACHINE ROOM AS YSER CODE. | $1,000 | -$40 | Aug 25, 1994 |