ECB violations
544-550 West 43 Street, Manhattan • Block 01071 • Lot 0054
42 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Sep 23, 2022 | 39070688Y | RESOLVE | CLASS - 1 | CAR CEASE USE CLASS1 DOOR ZONE RESTRICTOR NOT WORKING TAMPERED WITH OR DISABLED. | $0 | $0 | Nov 10, 2022 |
| Mar 26, 2020 | 39020469Z | ACTIVE | CLASS - 1 | EXPIRED FIRE EXTINGUISHER IN MOTOR ROOM, PHONE NOT WORKING,NO DOOR LOCK MONITORING INSTALLED IN CONTROLLER AS MANDATE... | $1,250 | $1,250 | Apr 15, 2021 |
| Mar 26, 2020 | 39020470X | ACTIVE | CLASS - 1 | EXPIRED FIRST EXTINGUISHER, PHONE NOT WORKING,NO DOOR LOCK MONITORING INSTALLED IN CONTROLLER AS MANDATED IN 3.10.12 ... | $1,250 | $1,250 | Apr 15, 2021 |
| Mar 26, 2020 | 39020471H | ACTIVE | CLASS - 1 | INSUFFICIENT FIRE EXTINGUISHER IN MOTOR ROOM, PHONE NOT WORKING, NO DOOR LOCK MONITORING INSTALLED IN CONTROLLER AS M... | $6,250 | $6,250 | Jan 7, 2021 |
| May 17, 2002 | 34278000H | RESOLVE | Non-Hazardous | WORK W/O PERMIT UPON INSPECTION AT THE ABOVE PROPERTY PIPE SCAFFOLD WAS INSTALLED IS NO PERMIT ISSUED STOP ALL WORK O... | $800 | $0 | Jul 3, 2003 |
| May 17, 2002 | 34277999H | RESOLVE | Non-Hazardous | NO DESIGN FRAWING UPON INSPECTION AT THE ABOVE PROPERTY SACFFOLD WAS INSTALLED UP TO 19TH FLOOR AND THERE IS NO DESIG... | $500 | $0 | Jul 3, 2003 |
| Feb 26, 2002 | 34314223K | RESOLVE | Hazardous | APPROVED PLANS NOT AVAILABLE FOR INSPECTION AT TIME OF INSPECTION CONTINUOS WINDOW FOR EAST SIDE 21 TO 22ND FL WAS BE... | $500 | $0 | Jul 3, 2003 |
| Feb 8, 2002 | 34288225H | RESOLVE | Hazardous | INSUFFICIENT CONTAINERS PROVIDED FOR THE STORAGE OF GARBAGE AND DEBRIS AT TIME OF INSPECTION DEBRIS UN COMBUSTIBLE MA... | $500 | $0 | Jul 3, 2003 |
| Aug 7, 2001 | 34298528Y | RESOLVE | Hazardous | FAILURE TO SAFEGUARD PUBLIC & PROPERTY AT TIME OF INSPECTION BRICK WORK IN PROGRESS ON FLOOR BRICKERS HANGING SCAFFOL... | $5,000 | $0 | Nov 1, 2001 |
| Jul 10, 2001 | 34263232P | RESOLVE | Non-Hazardous | FAILURE TO CARRY OUT PERMITTED WORK IN ACCORDANCE WITH APPLICABLE LAWS & REGULATIONS IN THE CONSTRUCTION ACTIVITIES A... | $0 | $0 | Nov 1, 2001 |
| May 11, 2001 | 34288588R | RESOLVE | Hazardous | HORIZONTAL NETS NOT INSTALLED AS PER MANUFACTURES RECOMEDATION UPON INSPECTION OF SITE AT ABOVE ADDRESS HORIZONTAL SA... | $1,250 | $0 | Jul 3, 2003 |
| May 11, 2001 | 34288587P | RESOLVE | Hazardous | RESHORES WITHIN 10 FT OF FACADE AT TIME OF INSPECTION RESHORES @ 20TH FLOOR WERE NOT SECURED REMEDY: SECURES RESHORES... | $500 | $0 | Jul 3, 2003 |
| May 11, 2001 | 34288589Z | RESOLVE | Hazardous | HORIZONTAL NETS NOT INSTAALED AS PER MANUFACTURES RECOMMENDATION: UPON INSPECTION OF SITE AT ABOVE ADDRESS HORIZONTAL... | $1,250 | $0 | Jul 3, 2003 |
| May 8, 2001 | 34277546P | RESOLVE | Hazardous | HORIZONTAL SAFETY NETTING NOT PROVIDED.UPON INSPECTION OF ABOVE ADDRESS WORK STRIPPING OF CONCRETE FORMS WAS IN PROGR... | $1,250 | $0 | Jul 3, 2003 |
| May 1, 2001 | 34277494M | RESOLVE | Hazardous | FAILURE TO PROVIDE EMERGNECY LIGHTING OR DEFECTIVE OR MISSING; UPON INSPECTION AT ABOVE PROPERTY,LIGHTING WAS DEFECTI... | $0 | $0 | Jul 3, 2003 |
| Apr 20, 2001 | 34277486M | RESOLVE | Hazardous | CONCRETE FORMS NOT JOINED PROPERLY AS PER DRAWING.UPON INSPECT. AT SITE AT ABOVE ADDRESS A CONCRETE FORM BLOW-OUT OCC... | $500 | $0 | Jul 3, 2003 |
| Apr 20, 2001 | 34277487Y | RESOLVE | Hazardous | HORIZONTAL SAFETY NETTING NOT PROVIDED.UPON INSPECTION AT THE ABOVE PROPERTY.HORIZONTAL NETS WERE NOT PROVIDED ON THE... | $500 | $0 | Jul 3, 2003 |
| Apr 3, 2001 | 34277684N | RESOLVE | Hazardous | SAFETY NETTING DAMAGED/OR BROKEN UPON INSPECTION PREMISES,VERTICAL OR PERIMETER SAFETY NETTING IS NOT SECURED TO THE ... | $2,500 | $0 | Jun 21, 2001 |
| Mar 13, 2001 | 34277183P | RESOLVE | Non-Hazardous | WORK WITHOUT PERMIT UPON INSPECTION OF ABOVE PREMISES STANDPIPE SYSTEM WAS BEING INSTALLED FROM 1ST TO 12TH FL DEPT R... | $500 | $0 | Jul 3, 2003 |
| Feb 20, 2001 | 34277677P | RESOLVE | Hazardous | VERTICAL SAFETY NETTING NOT PROVIDED.AT TIME OF INSEPCTION AT THE ABOVE ADDRESS,VERTICAL NETTING AT 8FL,WAS NOT TIED ... | $1,250 | $0 | Jul 3, 2003 |
| Feb 20, 2001 | 34277676N | RESOLVE | Hazardous | WEDGES USED IN RESHORES WITHIN 10FT OF FACADE:AT TIME OF INSPECTION AT ABOVE PROPERTY WEDGES USED IN RESHORES ON FL 6... | $500 | $0 | Jul 3, 2003 |
| Feb 20, 2001 | 34277678R | RESOLVE | Hazardous | NO SIDEWALK SHED OVERHEAD PROTECTION GOING INTO BLDG AT TIME OF INSPECTION THE 12FL WAS BEING FRAMED AND NO OVERHEAD ... | $2,000 | $0 | Jul 3, 2003 |
| Feb 6, 2001 | 34269097Z | RESOLVE | Hazardous | WEDGES USED IN RESHORES WITHIN 10 FEET OF FACADE AT TIME OF INSPECTION AT ABOVE PREMESIS THERE WAS A TOTAL OF 15 WEDG... | $500 | $0 | Jul 3, 2003 |
| Feb 6, 2001 | 34269096R | RESOLVE | Hazardous | FAILURE TO PROVIDE HANDRAILS ON STAIRWELL UPON INSPECTION AY ABOVE PREMISES. THERE WAS NO HANDRAILS ON STAIRS FROM FI... | $1,250 | $0 | Jul 3, 2003 |
| Feb 6, 2001 | 34269098K | RESOLVE | Hazardous | HORIZONTAL SAFETY NETTING NOT PROVIDED , AT TIME OF INSPECTION THERE WAS NO HORIZONTAL SAFETY NETTING BUILDING HAS RE... | $2,500 | $0 | Jul 3, 2003 |
| Jan 8, 2001 | 34262906H | RESOLVE | Non-Hazardous | FAILURE TO CARRY OUT PERMITTED WORK IN ACCORDANCE WITH APPLICABLE LAWS AND REGULATIONS IN THAT CONSTRUCTION ACTIVITIE... | $0 | $0 | Aug 7, 2003 |
| Jun 1, 2000 | 34234072M | RESOLVE | Non-Hazardous | FAILURE TO HAVE SITE SAFETY MANAGER PRESENT AT SITE AT TIME OF INSPECTION.THERE IS NO SITE SAFETY MANAGER PRESENT.POS... | $5,000 | $0 | Jul 27, 2000 |
| May 10, 2000 | 34234059H | RESOLVE | Non-Hazardous | FAILURE TO COMPLY W/SITE SAFETY PLAN&PROGRAM:@TIME OF INSPECTION CONST.WORK WAS IN PROGRESS THERE WAS NO SITE SAFETY ... | $1,000 | $0 | Jul 27, 2000 |
| May 10, 2000 | 34234057Y | RESOLVE | Hazardous | NO SITE SAFETY MANAGER:UPON INSPECTION@ABOVE PREMISES.THERE WAS NO SITE SAFETY MANAGER@SITE.REMEDY:PROVIDE SITE SAFET... | $2,000 | $0 | Jul 27, 2000 |
| Aug 13, 1999 | 34211504P | RESOLVE | Hazardous | NO 18 GAGE STEEL WIRE AROUND THE SCAFFOLD AT FLOOR NO 5,4,3X2 AND FACADE OF THESE FLOORS WAS COMPLETLY REMOVED. WORKM... | $750 | $0 | Jun 8, 2000 |
| Aug 13, 1999 | 34211503N | RESOLVE | Hazardous | MECHANCIAL DEMOLITION WITHOUT PERMIT AT TIME OF INSPECTION DEMOLITION BEING DONE BY MEANS OF MECHANCIAL WITH A BOBCAT... | $800 | $0 | Jun 8, 2000 |
| Aug 12, 1999 | 34211501J | RESOLVE | Hazardous | FAILURE TO CARRY OUT DEMOLATION OPERATION IN A SAFE AND PROPER MANNER IN THAT THE BUILDING WAS NOT TAKEN DOWN IN A SY... | $2,000 | $0 | Jun 8, 2000 |
| Jul 30, 1999 | 34211842H | RESOLVE | Hazardous | FAILURE TO GIVE 24 HRS NOTICES PRIOR TO COMMUNCEMENT OF DEMO REMEDY PROVIDE 24 HRS NOTICE TO THIS DEPT PRIOR TO COMMS... | $2,500 | $0 | Dec 30, 1999 |
| Jul 30, 1999 | 34211841X | RESOLVE | Hazardous | FAILURE TO REMOVECX GLASS PRIOR THE COMMENCEMNET OF DEMOLITION REMEDY REMOVED ALL GLASS PRIOR THE START OF DEMOLITION... | $2,500 | $0 | Dec 30, 1999 |
| Jul 30, 1999 | 34211845N | RESOLVE | Hazardous | WORK WITHOUT A PERMIT UPON INSPECTION AT ABOVE PREMISES DEMOLITION WORK WAS IN PRIGRESS WITHOUT OBTAINING A PERMIT DE... | $2,500 | $0 | Dec 30, 1999 |
| Jul 30, 1999 | 34211843J | RESOLVE | Hazardous | FAILURE TO PROVIDE 24 HOURS NOTICE PRIOR TO START OF DEMOLITION AT TIME OF INSPECTION DEMOLITION WORK WAS IN PROGRESS... | $2,500 | $0 | Dec 30, 1999 |
| Jul 30, 1999 | 34211844L | RESOLVE | Hazardous | FAILURE TO REMOVE GLASS PROIR TO TH ECOMMUNCEMENT DEMO UPON INSPECTION DEMO WAS IN PROGRESS AND GLASS WAS NOT REMOVED... | $2,500 | $0 | Dec 30, 1999 |
| Nov 10, 1997 | 34166786M | RESOLVE | Hazardous | FAILURE TO MAINTAIN EXTERIOR BLDG WALL. NOTED: PARAPET WALL AT FRONT FACADE OF BLDG IS LEANING INWARD OUT OF PLUMB AP... | $2,000 | $0 | Jan 15, 1998 |
| Jul 2, 1997 | 34154578J | RESOLVE | Hazardous | FAILURE TO MAINTAIN EXTERIOR BUILDING WALL. IN THAT PARAPET WALL AT ROOF IS LEANING AND OUT OF PLUMB AND CRACKED. REM... | $2,000 | $0 | Aug 21, 1997 |
| Jun 5, 1996 | 34137772Z | RESOLVE | Hazardous | FAILURE TO MAINTAIN EXTERIOR BLDG WALL.HAZ.PARAPET WALL AT ROOF AT FRONT OF BLDG IS LEANING INWARD OUT OF PLUMB.BRICK... | $800 | $0 | Sep 19, 1996 |
| May 19, 1992 | 34073007L | RESOLVE | Hazardous | FAILURE TO FILE A REPORT OF COMPLIANCE WITH LOCAL LAW 16/84-CERTIFYING TO THE INSTALLATION OF REQUIRED FIER PROTECTIO... | $0 | $0 | Jul 2, 1992 |
| May 19, 1992 | 34073012X | RESOLVE | Non-Hazardous | FAILURE TO PROVIDE ELEVATOR LANDING SIGNS. FAILURE TO PROVIDE FLOOR NUMBERING SIGNS. FAILURE TO PROVIDE STAIR IDENTIF... | $0 | $0 | Jul 2, 1992 |