ECB violations
519-521 West 49 Street, Manhattan • Block 01078 • Lot 0020
36 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Mar 19, 2026 | 39181146L | RESOLVE | CLASS - 1 | OBSERVED ON 10TH FLOOR SPRINKLER HEADS OBSTRUCTED. PIPE PENETRATIONS ARE ON 9TH, 8TH AND BASEMENT FLOOR WITH NO FIRE ... | $2,530 | $30 | Jul 2, 2026 |
| Nov 14, 2024 | 39130520M | RESOLVE | CLASS - 1 | I OBSERVED IN DOB RECORDS THE SUBMISSION OF A C OF C FOR THE USE OF FLEXIBLE CORDS IN THE REAR COURTYARD A.C UNITS AN... | $0 | $0 | Jan 23, 2025 |
| Nov 14, 2024 | 39130513Y | RESOLVE | CLASS - 1 | I OBSERVED ON THE 11TH FLOOR ROOF , THE REAR COURTYARD THE USE OF FLEXIBLE WIRING USED AS PERMANENT WIRING FROM THE A... | $1,600 | $0 | Jan 23, 2025 |
| Nov 14, 2024 | 39130516J | RESOLVE | CLASS - 1 | I OBSERVED IN DOB RECORDS THE PERMIT #M00914191 FOR THE INSTALLATION OF 5 HVAC SYSTEMS, THE SCOPE OF WORK IN THE REAR... | $1,000 | $0 | Jan 23, 2025 |
| Nov 14, 2024 | 39130517L | RESOLVE | CLASS - 2 | I OBSERVED IN THE ROOFTOP GENERATOR ROOM THE UNPERMITTED USE OF EMT THROUGH THE CONCRETE WALL WITHOUT PROTECTION FROM... | $0 | $0 | Jun 30, 2025 |
| Nov 14, 2024 | 39130512M | RESOLVE | CLASS - 2 | I OBSERVED IN THE ROOFTOP GENERATOR ROOM AND THE BASEMENT WATER METER ROOM THE INSTALLATION OF CONDUIT RACEWAYS , BRA... | $400 | -$400 | Jun 30, 2025 |
| Nov 14, 2024 | 39130518N | RESOLVE | CLASS - 2 | I OBSERVED IN THE BASEMENT WATER METER ROOM THE WATER METER JUMPER DETACHED FROM THE WATER SERVICE PIPE, THIS AN ESSE... | $600 | $0 | Jun 30, 2025 |
| Nov 14, 2024 | 39130515H | RESOLVE | CLASS - 2 | I OBSERVED ON THE ROOF TOP THE FAILURE TO SUPPORT THE LFMC (SEALTITE) AS REQUIRED, ALSO NOTED THAT THE LENGTH IN USE ... | $400 | $0 | Jun 30, 2025 |
| Nov 14, 2024 | 39130519P | RESOLVE | CLASS - 2 | I OBSERVED IN THE GAS METER ROOM THE IMPROPER TERMINATION OF RACEWAYS AND CONDUCTORS. THE CABLE AND THE WIRING WERE H... | $0 | -$800 | Jun 30, 2025 |
| Nov 14, 2024 | 39130514X | RESOLVE | CLASS - 3 | I OBSERVED THROUGHOUT THE BUILDING THE ELECTRICAL PANEL BRANCH CIRCUITS NOT OR IMPROPERLY IDENTIFIED AS PER CODE., PR... | $0 | $0 | Jun 30, 2025 |
| Nov 14, 2024 | 39130511K | RESOLVE | CLASS - 1 | I OBSERVED IN DOB RECORDS THE FILING OF A CERTIFICATE OF CORRECTIONS #0251356 ON 07/25/2023 BY VICENTE MOLDELO STATIN... | $0 | $0 | Jul 10, 2025 |
| Nov 13, 2024 | 39130140K | RESOLVE | CLASS - 1 | OBSERVED MISSING FIRE STOPPING IN THE MECHANICAL ROOM LOCATED ON THE 15TH FLOOR. THIS IS A HAZARDOUS BECAUSE IT IS GI... | $2,500 | $0 | Sep 4, 2025 |
| Nov 13, 2024 | 39130141M | RESOLVE | CLASS - 2 | OBSERVED PAINTED SPRINKLER CAPS ON THE 14TH AND 13TH FLOORS. AS PER 102.3 OF THE PLUMBING CODE INSTALLATIONS, BOTH EX... | $0 | $0 | Jan 23, 2025 |
| Aug 1, 2023 | 39520062H | RESOLVE | CLASS - 1 | UPON REACHING THE UPPER FLOORS WHERE THE CREW WERE WORKING, I ASKED TO SPEAK WITH THE PERSON IN CHARGE, , JOSE L ISID... | $2,500 | $0 | Jan 4, 2024 |
| Aug 1, 2023 | 39520064L | RESOLVE | CLASS - 2 | AT TIME OF INSPECTION I OBSERVED THE SITE WAS CONTRARY TO THE S.S.P DUE TO SUSPENDED SCAFF. @EXP.#1(SUPP. SCAFF. SHOW... | $625 | $0 | Apr 25, 2024 |
| Jul 27, 2023 | 39091369J | RESOLVE | CLASS - 2 | VERIZON ELECTRICAL BOXES AND WIRING MOUNTED/INSTALLED IN STAIRCASE LOCATED AT CELLAR LEVEL, NEXT TO STANDPIPE., REPAI... | $0 | $0 | Oct 5, 2023 |
| Jun 6, 2023 | 39087884M | RESOLVE | CLASS - 1 | I OBSERVED THE UNPERMITTED USE OF FLEXIBLE WIRING AT THEN ENTRANCE SUPPLYING POWER TO THE SIDEWALK SHED, THE INTERCON... | $1,600 | $0 | Oct 10, 2024 |
| Jun 6, 2023 | 39087875K | RESOLVE | CLASS - 2 | OBSERVED SPRINKLER FLOW SWITCH ON THE SECOND AND THIRD FLOORS ARE NOT READILY ACCESSIBLE FOR NORMAL OR EMERGENCY MAIN... | $312 | $0 | Aug 10, 2023 |
| Jun 6, 2023 | 39087883K | RESOLVE | CLASS - 2 | I OBSERVED THE FAILURE TO PROVIDE GFCI PROTECTION AS REQUIRED FOR OUTDOOR LIGHTING OF THE SIDEWALK SHED AND IN THE BO... | $2,400 | $0 | Aug 10, 2023 |
| Jun 6, 2023 | 39087886X | RESOLVE | CLASS - 2 | I OBSERVED IN THE REAR COURTYARD THE IMPROPER IDENTIFICATION OF A NEUTRAL CONDUCTOR, I NOTED A GREEN COLORED WIRE CON... | $400 | $0 | Aug 10, 2023 |
| Jun 6, 2023 | 39087885Y | RESOLVE | CLASS - 1 | I OBSERVED FROM THE ROOF AREA BOILER ROOM THE TEMPORARY WIRING FOR THE MOTORIZED SCAFFOLDS PASSING THROUGH DOORWAYS, ... | $1,600 | $0 | Jan 11, 2024 |
| Jun 6, 2023 | 39087887H | RESOLVE | CLASS - 1 | I OBSERVED THE MAIN ELECTRICAL ROOM THE FAILURE TO GROUND THE 400 AMP SERVICE DISCONNECT SWITCH. I NOTED THE SWITCH B... | $4,800 | $0 | Aug 10, 2023 |
| Jun 6, 2023 | 39087888J | RESOLVE | CLASS - 2 | I OBSERVED IN THE REAR YARD THE INSTALLATION OF RACEWAYS, BRANCH CIRCUIT WIRING, OVERCURRENT DEVICES, AND DISCONNECT ... | $400 | $0 | Aug 10, 2023 |
| Nov 7, 2022 | 39073612L | RESOLVE | CLASS - 1 | FAILURE TO HAVE NEW OR ALTERED PLUMBING SYSTEM TESTED I OBSERVED IN THE BASEMENT INSTALLED NEW GAS PIPING BY THE GAS ... | $1,250 | $0 | Jan 26, 2023 |
| Nov 7, 2022 | 39073611J | RESOLVE | CLASS - 1 | GAS BEING SUPPLIED TO BUILDING WITHOUT INSPECTION AND CERTIFICATION BY DOB I OBSERVED IN THE BASEMENT NEW GAS PIPING ... | $2,500 | $0 | Jan 26, 2023 |
| Feb 13, 2018 | 35265151Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING EXTERIOR WALLS/FACADES AND APPURTENANCES.*SOUTH ELEVATION, EXP 1: ERODED MORTIS JOINTS *... | $530 | $0 | Apr 5, 2018 |
| Oct 7, 2016 | 35173933P | RESOLVE | CLASS - 1 | FAILURE TO TAKE A PROVIDE SAFETY MEASURES WHERE REQUIRED TO PROTECT AND SECURE PUBLIC SAFETY FROM UNSAFE FACADE AS PE... | $2,400 | $0 | Dec 29, 2016 |
| Oct 20, 2011 | 34925634H | RESOLVE | CLASS - 2 | 28-302.5 FAIL TO PROVIDE SAFETY MEASURE (SIDEWALK SHED) TO PROTECT PUBLIC FROM HAZARDOUS CONDITION-UNSAFE FLSP TECHNI... | $400 | $0 | Dec 8, 2011 |
| Jul 29, 2011 | 36016463R | RESOLVE | CLASS - 2 | FAILURE TO FILE AN AMENDED 6TH ROUND REPORT ACCEPTABLE TO THIS DEPT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRI... | $400 | $0 | Dec 15, 2011 |
| May 22, 2009 | 36009232Y | RESOLVE | CLASS - 2 | FAILURE TO FILE AN AMENDED SIXTH ROUND REPORT ACCEPTABLE TO THIS DEPARTMETN INDICATING CORRECTION OF UNSAFE CONDITION... | $0 | $0 | Aug 20, 2009 |
| Jan 9, 2009 | 36007339P | RESOLVE | CLASS - 2 | FAILURE TO FILE AN AMENDED SIXTH ROUND REPORT ACCEPTABLE TO THIS DEPARTMENT INDICATING CORRECTION OF UNSAFE CONDITION... | $800 | $0 | Jun 25, 2009 |
| Sep 17, 2002 | 38125609X | RESOLVE | Non-Hazardous | 75U05,08V01,28L12,57O02, 75-PERFORM & FILE 5 YRS TEST 08-ADJUST LEVELLING OF FLOORS- 28- CHANGE IDEEFECTIVE ROLLER GU... | $0 | $0 | Nov 7, 2002 |
| Sep 17, 2002 | 38125610N | RESOLVE | Non-Hazardous | 75U05,57O02, 75- PERFORM 5 YRS TEST ,AND TAG DEVICE 75- CLEAN PIT. | $0 | $0 | Nov 7, 2002 |
| Jul 5, 2002 | 34314962Y | RESOLVE | Hazardous | FAILURE TO FILE AN AMENDED ROUND FIVE REPROT ACCEPTALBE TO THIS DEPARTMENT PURSUANT TO RULE R.C.N.Y. 32-03B (5), INDI... | $400 | $0 | Sep 5, 2002 |
| May 3, 2002 | 34314533X | RESOLVE | Hazardous | FAILURE TO FILE AN AMENDED ROUND FIVE REPORT ACCEPTABLE TO THIS DEPARTMENT PURSUANT TO RULE R.C.N.Y. 32-03B(5), INDIC... | $400 | $0 | Aug 22, 2002 |
| Feb 15, 1989 | 34020766N | RESOLVE | Non-Hazardous | NEW BLDG.#67/84 PERMIT#003188/88 HAS BEEN REVOKED.DUE TO NON COMP- LIENCE WITH OBJECTIONS CHECKLIST FOR NEW BLDGS.AND... | $500 | $0 | Aug 9, 1990 |