| Mar 14, 2014 | 35038819J | RESOLVE | CLASS - 2 | FAILURE TO INSTALL GROUND FAULT CIRCUIT INTERRUPTER (GFCI) PROTECTION AS REQUIRED.REM:INSTALL GFCI PROTECTION. | $0 | $0 | Aug 7, 2014 |
| Mar 14, 2014 | 35038821Z | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE EFFECTIVE CONTINUITY FOR METAL RACEWAYS ENCLOSURES CABLE ARMOR.EXPOSE WIRES IN SIDEWALK SHED.REM:P... | $0 | $0 | Jul 24, 2014 |
| Mar 14, 2014 | 35038820R | RESOLVE | CLASS - 2 | PVC USED IN SIDE WALK SHED.SUCH LIGHTING SHALL BE INSTALLED IN A METALRACEWAY APPROVED FOR OUTDOOR USE.REM:COMPLY W/ ... | $0 | $0 | Jul 24, 2014 |
| Dec 30, 2013 | 38229641M | RESOLVE | CLASS - 2 | 56O02,40O02,42M07,99BB07. 40O-REMOVE GARBAGE PARTS AND PAPER (PRINTS)ALL OVER M/ROOM-SECURE; 42M-PROVIDE MISSING TROU... | $1,250 | $0 | Oct 30, 2014 |
| Nov 22, 2013 | 35084124K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG: NO FIRE STOPPING: PER BC712.3;27-345. NOTED:AT GARAGE,PENETRATION IN CMU BLOCK FIRE WALL IN... | $0 | $0 | Jan 9, 2014 |
| Nov 13, 2013 | 35031208Z | RESOLVE | CLASS - 1 | SUPPORTED SCAFFOLD AT ROOF LEVEL DOES NOT MEET DOB CODE SPECIFICATIONS. NOTED: TOE BOARDS NOT INSTALLED. PICTURES FIL... | $1,000 | $0 | Jan 2, 2014 |
| Nov 13, 2013 | 35031207R | RESOLVE | CLASS - 1 | UNLAWFULLY CONTINUED WORK WHILE ON A SWO. SUSPENDED SCAFFOLDING EQUIPMENT (OUTRIGGERS BEAMS) W/O RESCINDING REMOVAL S... | $4,800 | $0 | May 1, 2014 |
| Oct 16, 2013 | 35010172N | RESOLVE | CLASS - 2 | FAILED TO NOTIFY DEPT PRIOR TO INSTALLATION OF C-HOOKS OR OUTRIGGERS BEAMS IN CONNECTION W/SUSPENDED SCAFFOLDS. NOTED... | $830 | $0 | Jan 2, 2014 |
| Jun 21, 2013 | 38227533X | RESOLVE | CLASS - 2 | 42D10 40M11 02L10. 42D10-PROPERLY SECURE P.C BOARD IN CONTROLLER. 40M11-REPLACE ALL MISSING COVERS ON CONTROLLER,TROU... | $0 | $0 | Aug 8, 2013 |
| Jun 21, 2013 | 38227532Y | RESOLVE | CLASS - 2 | 44M11 40M11 40O02. 44M11-REPLACE GUARD FOR SHEAVE (CABLES). 40M11- REPLACE ALL MISSING COVERS (CONTROLLER, TROTH). 40... | $0 | $0 | Aug 8, 2013 |
| Jun 19, 2013 | 35009707M | RESOLVE | CLASS - 2 | MISSLEADING JOB SITE SIGN. NOTED: JOB SITE SIGN W/O PERMIT # & EXPIRATION DATE. PICTURES FILED. REMEDY: COMPLY W/DOB ... | $0 | $0 | Aug 8, 2013 |
| Mar 26, 2013 | 35012629N | RESOLVE | CLASS - 2 | EMERGENCY EXIT LIGHTING INOPERATIVE IN BOILER ROOM REISSUE:34953863J REMEDY: MAINTAIN BUILDING PER CODE. | $0 | $0 | May 16, 2013 |
| Mar 26, 2013 | 35012628L | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN REISSUE 34953862H OBSERVED: AT 2ND FLR STAIR B, STAIRWELL EXIT DORRS RACKED,BIND AT TOP AGAINST J... | $0 | $0 | May 16, 2013 |
| Feb 19, 2013 | 38225929N | RESOLVE | CLASS - 2 | 40O02,52M07,56Q03,05M07,29D06,67X10,34J01,17H11,17D06,14M07,70O02,71X10. 40O-CLEAN DEBRIS; 52M-SHACKLES MISSING SPRIN... | $0 | $0 | Apr 4, 2013 |
| Feb 19, 2013 | 38225930K | RESOLVE | CLASS - 1 | 34H11,34J01,01L10,02X10,52M07,17H11,17D06,05X10,52Q03,61J01,12X10,14J01,70O02,76Q03,52B14. CEASE USE ITEMS. 34HJ-EXTR... | $0 | $0 | Apr 4, 2013 |
| Feb 19, 2013 | 38225928L | RESOLVE | CLASS - 2 | 05I10,05L11,05X10,29D06,34J01,17H11,17D06,61J01,14M07,70O02. 5I,L-REPAIR DAMAGE TO DOOR AND REPLACE ASTRIGAL; 5X-ZONE... | $0 | $0 | Apr 4, 2013 |
| Dec 28, 2012 | 38221474H | RESOLVE | CLASS - 2 | 97X10 - RESTORE TO SERVICE. | $250 | $0 | Feb 14, 2013 |
| Dec 4, 2012 | 38224653R | RESOLVE | CLASS - 2 | 67B07- CAR INTERCOM TO FRONT DESK DOES NOT WORK. ALARM BELL CAN'T BE HEARD AT FRONT DESK DUE TO DISTANCE AND GLASS EN... | $0 | $0 | Jan 24, 2013 |
| Nov 20, 2012 | 38223663X | RESOLVE | CLASS - 2 | 251:67L10,70O02,71I11.67L10:COMMUNICATION INSIDE CAB IS DEFECTIVE;MUST REPAIR.70O02:MUST CLEAN PIT.71I11:MUST PROVIDE... | $500 | $0 | Jan 10, 2013 |
| Nov 20, 2012 | 38223664H | RESOLVE | CLASS - 2 | 251:67L10,70O02,30B10.67L10:COMMUNICATIN INSIDE CAB IS DEFECTIVE;MUST REPAIR.70O02:MUST CLEAN PIT.30B10:REPAIR THE NO... | $500 | $0 | Jan 10, 2013 |
| Nov 20, 2012 | 38223665J | RESOLVE | CLASS - 2 | 251:67L10,70O02,05I11.67L10:COMMUNICATION INSIDE CAB IS DEFECTIVE;MUST REPAIR.70O02:CLEAN PIT.05I11:CAR DOOR IS DAMAG... | $500 | $0 | Jan 10, 2013 |
| Sep 24, 2012 | 38223676P | RESOLVE | CLASS - 2 | 98BB05,99BB05. | $250 | $0 | Dec 13, 2012 |
| Aug 28, 2012 | 38223183R | RESOLVE | CLASS - 2 | 68M07,98M05,99M05. | $250 | $0 | Oct 18, 2012 |
| Aug 28, 2012 | 38223182P | RESOLVE | CLASS - 2 | 68M07,98M05,99M05. | $250 | $0 | Oct 18, 2012 |
| Aug 28, 2012 | 38223181N | RESOLVE | CLASS - 2 | 68M07,98M05,99M05. | $625 | $0 | Oct 18, 2012 |
| Aug 8, 2012 | 34980770Y | RESOLVE | CLASS - 2 | EXPIRED PERMIT - AT TIME OF INSPECTION. OBSERVED PERMIT #120328528-01 FOR SIDEWALK SHED, EXPIRED ON 7.15.12. REMEDY: ... | $0 | $0 | Sep 27, 2012 |
| Jul 11, 2012 | 38221538H | RESOLVE | CLASS - 2 | 68M07,98BB05,99M07. | $500 | $0 | Nov 15, 2012 |
| Apr 26, 2012 | 34953863J | RESOLVE | CLASS - 2 | DEFECTIVE EMERGENCY LIGHTING THROUGHOUT ENTIRE BLDG CORRIDORS,GYM,ETC.TOO MANY TO LIST.REM:REPAIR/REPLACE EMERGENCY L... | $0 | $0 | Jun 14, 2012 |
| Apr 26, 2012 | 34953864L | RESOLVE | CLASS - 2 | EXIT PASSANGERS PARTIAL OBSTRUCTED @ 2FL CORRIDOR 6FT LONG SECURITY DESK IN PLACE.ALSO AUDITORIUM REAR STAGE DESK & C... | $0 | $0 | Jun 14, 2012 |
| Mar 30, 2012 | 38220699Y | RESOLVE | CLASS - 2 | 98BB05,99BB05,67X10,68M07,39O02,79B14,70O02,17H11. | $0 | $0 | May 17, 2012 |
| Mar 30, 2012 | 38221275P | RESOLVE | CLASS - 2 | 98U05,99U05,68M07. | $0 | $0 | May 17, 2012 |
| Dec 29, 2011 | 36018151R | RESOLVE | CLASS - 2 | FAILURE TO FILE AN AMENDED 6TH ROUND REPORT ACCEPTABLE TO THIS DEPT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRI... | $800 | $0 | May 17, 2012 |
| Dec 26, 2011 | 38219935Z | RESOLVE | CLASS - 2 | 52O02.59O02.42G07.42L10.68M07.69B07.99BB05.32H10/11.14M07.40O02. (52)CLEAN HOIST ROPES (59)CLEAN BRAKE CORE & ARMS (4... | $0 | $0 | Mar 1, 2012 |
| Dec 26, 2011 | 38219934R | RESOLVE | CLASS - 1 | CU.52J01.42N10. 52O02.59O02.42G07.68M07.69B07.99M05.42D03.57M07.32L10/11.40O02. CEASE USE ITEMS (52)HOIST ROPES HAVE ... | $0 | $0 | Mar 1, 2012 |
| Dec 26, 2011 | 38219933P | RESOLVE | CLASS - 2 | 52O02.59O02.42G11.42L10.68M07.69B07.99BB05.40O02.32H10/11.14M07.05I10/11.29E01.40O02. (52)CLEAN HOIST ROPES (59)CLEAN... | $0 | $0 | Mar 1, 2012 |
| Dec 20, 2011 | 38219682J | RESOLVE | CLASS - 2 | 05M07,03B10. 05- BIPARTING CAR DOORS - ASTRAGA/RUBBER STRIP - MISSING.03B- ELEVATOR SCRAPING FASCIA COVERS ON VARIOUS... | $0 | $0 | Feb 9, 2012 |
| Nov 10, 2011 | 34925689P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN EXTERIOR BLDG.SOUTH ELEV.,EXP.#2OBSERVE VERTICAL CRACKS & DISPLACEMENT IN CORNER FACADE BETWEEN 1... | $500 | $0 | Dec 29, 2011 |
| Aug 4, 2011 | 34926775X | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN PARKING GARAGE @ NORTH EAST CORNER BETWEEN COLUMN LINES B-12 TO B-13(@ ENTRANCE FLR)THE AREA TO B... | $0 | $0 | Oct 28, 2011 |
| Aug 4, 2011 | 34926776H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN-PARKING GARAGE-NO PARKING LINES,NUMBERS FOR PARKING SPACES,NO CURB STOPS,NO AISLES FOR NYCFD EGRE... | $0 | $0 | Oct 28, 2011 |
| Jul 22, 2011 | 34921707L | RESOLVE | CLASS - 2 | SEC. 27-371(B). PLEXI VISION PANELS. AT VARIOUS ROOMS THROUGHOUT 2ND &3RD FLR, INSTALLED PLEXI VISION PANELS. REMEDY:... | $0 | $0 | Sep 15, 2011 |
| Jul 22, 2011 | 34921706J | RESOLVE | CLASS - 3 | BROKEN PANIC HARDWARE. AT AUDITORIUM EXIT DOOR MARKED G 57, BROKEN PANIC BAR W/INTERNAL PARTS EXPOSED. REMEDY: REPAIR... | $0 | $0 | Sep 15, 2011 |
| Jul 22, 2011 | 34921705H | RESOLVE | CLASS - 2 | RACKED DOORS. THE FIRE PROOF SELF-CLOSING ARE RACKED TO FRAME & NOT OPERATING PROPERLY AT 1ST FLR STWY B, 2ND FLR SMO... | $2,500 | $0 | Sep 15, 2011 |
| Jul 14, 2011 | 34923133K | RESOLVE | CLASS - 2 | FAIL TO MAINTAIN BLDG IN CODE COMPLIANT MANNER-GARAGE VACATED AREA. 1)@ COLUMN LINE 3-10 VACATE BARRIES NOT MAINTAINE... | $0 | $0 | Sep 8, 2011 |
| Mar 31, 2011 | 34892741P | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN PREMISE/BLDG IN CODE COMPLIANT MANNER.LOCATION:AMTRACK TUNNEL BETWWEEN WEST 50 ST & WEST 51ST BEL... | $0 | $0 | Sep 9, 2011 |
| Mar 1, 2011 | 38210684M | RESOLVE | CLASS - 2 | 03E10 40O02 41B07 03-RUBBING SCRAPING NOISE COMING FROM UP & DOWN TRAVEL REPAIR 41B-PROVIDE W/ APPROVE LOCK | $0 | $0 | Apr 21, 2011 |
| Mar 1, 2011 | 38210685Y | RESOLVE | CLASS - 2 | 50M07 60L10 50M-MG SET COVER MISSING FOR SPLICE BOX | $0 | $0 | Apr 21, 2011 |
| Jan 11, 2011 | 34892293K | RESOLVE | CLASS - 2 | SEC. 27-357(D);1105.1. PEOPLE W/PHSICAL DISABILITIES: PRIMARY ENTRANCE/RAMPS INACCESSIBLE. NOTED: PUBLIC SIDEWALK AT ... | $4,000 | $0 | Sep 8, 2011 |
| Jan 11, 2011 | 34892291R | RESOLVE | CLASS - 2 | SEC. 27-292.17;1109.9. PEOPLE W/DISABILITIES: INADEQUATE TACTILE WARNING SYSTEM. NOTED: PREMISES FRONTAGE RUNS ENTIRE... | $0 | $0 | Sep 8, 2011 |
| Jan 11, 2011 | 34892289H | RESOLVE | CLASS - 2 | SEC. 27-292;1105.1. PEOPLE W/DISABILITIES: PUBLIC SPACES NOT ACCESSIBLE. NOTED: NO USABLE ENTRY WAY FOR PEOPLE W/DISA... | $0 | $0 | Sep 8, 2011 |
| Jan 11, 2011 | 34892292Z | RESOLVE | CLASS - 2 | SEC. 27-292.18;1110.1. PEOPLE W/PHSICAL DISABILITIES: INADEQUATE SIGNAGE. NOTED: NO VISIBLE SIGNAGE PRESENT TO DIRECT... | $0 | $0 | Sep 8, 2011 |