ECB violations
West End Secondary School, Manhattan • Block 01154 • Lot 0108
96 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Apr 11, 2025 | 35717109J | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING PROPERLY. AT THE TIME OF INSPECTION AT 2ND FLOOR NEAR RM-NO 212 ONE EXIT DOOR AT 1ST FLOOR... | $625 | $0 | May 19, 2025 |
| Nov 13, 2024 | 39130142Y | ACTIVE | CLASS - 2 | OBSERVED IN WEST END SECONDARY SCHOOL ON THE SECOND FLOOR IN THE STAFF TOILET ROOM 231 SINK NOT WORKING NO WATER COMI... | $3,125 | $3,125 | Jan 23, 2025 |
| Mar 8, 2021 | 35548203L | RESOLVE | CLASS - 2 | REISSUE 35491026P FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER:LACK OF EMERGENCY LIGHTING FOR EXITS,EXIT DISCHAR... | $1,250 | $0 | Jun 10, 2021 |
| Apr 14, 2020 | 35491025N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER NO FIRE STOPPINGPER BC712.3/27-345.NOTED:AT CELLAR GAS AND ELEC... | $1,250 | $0 | Aug 13, 2020 |
| Apr 14, 2020 | 35491026P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.LACK OF EMERGENCY LIGHTING FOR EXITS,EXIT DISHCARGES AND PUBLIC... | $1,250 | $0 | Aug 13, 2020 |
| Apr 14, 2020 | 35490674Z | RESOLVE | CLASS - 2 | FAILUER TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:AT(2ND FL)GYM AND (1ST FL)CAFETERIA DOORS IN DISREPAIR/CR... | $625 | $0 | Aug 13, 2020 |
| Oct 7, 2019 | 35454682K | RESOLVE | CLASS - 2 | REISSUE#35317156J.FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NO FIRE STOPPING.PER BC712.3,27.345 AT CELLAR... | $3,125 | $0 | Jan 9, 2020 |
| Feb 13, 2018 | 35317154X | RESOLVE | CLASS - 2 | REISSUE #35235929N FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.AT CELLAR GAS METER ROOM,STORAGE OF SCHOOL M... | $0 | $0 | May 3, 2018 |
| Feb 13, 2018 | 35317155H | RESOLVE | CLASS - 2 | 28-301.1 REISSUE #35235928L AT CELLAR GAS METER ROOM NO VENTILATION FOR GAS METER ROOM. RMDY: COMPLY WITH NOTICE OF V... | $0 | $0 | May 3, 2018 |
| Feb 13, 2018 | 35317156J | RESOLVE | CLASS - 2 | REISSUE 352359275 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER NO FIRE STOPPING PER BC 712. 3.27.345 AT CELL... | $0 | $0 | May 3, 2018 |
| Mar 31, 2017 | 35235929N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: STORAGE CONSISTING OF PAINTS, SEVERAL CANS & GALLONS WAS OB... | $0 | $0 | May 4, 2017 |
| Mar 31, 2017 | 35235925X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:NOTED:WATER PENETRATION THROUGHOUT ROOF WAS OBSERVED AT 3 FLR I... | $500 | $0 | Jul 6, 2017 |
| Mar 31, 2017 | 35235928L | RESOLVE | CLASS - 2 | B-206,2. 28-31.1. RE-ISSUED VIO # 34779613X FOR FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P115.6(1968 CODE... | $0 | $0 | May 4, 2017 |
| Mar 31, 2017 | 35235927J | RESOLVE | CLASS - 2 | RE-ISSUED VIO # 35147653L FOR FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NO FIRE STOPPING PER BC 712.3' 27-34... | $0 | $0 | May 4, 2017 |
| Sep 15, 2016 | 35200865N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG: MISSING FIRE STOPPING. NOTED: MISSING FIRE STOPPING FROM WALL OF ELECTRICAL ROOM B-42 & ON ... | $1,250 | $0 | Nov 3, 2016 |
| Sep 16, 2015 | 35147655P | RESOLVE | CLASS - 2 | RE-ISSUED ECB #35093860N.FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES EXTERIOR.FAILURE TO MAINTAIN BUILDING ... | $500 | $0 | Jan 7, 2016 |
| Sep 16, 2015 | 35147652J | RESOLVE | CLASS - 2 | REISSUED ECB 35093858Y ALTERED/CHANGED BUILDING OCCUPIED W/O A VALID CERT OF OCCUPANCY. REISSUED ECB #35019150N ALTER... | $0 | $0 | Oct 29, 2015 |
| Sep 16, 2015 | 35147654N | RESOLVE | CLASS - 2 | 27-776 REISSUED ECB 35093857M FRESH AIR IN GAS METER ROOM RS 16P115.4 AND GTPPN 1 OF 1964. 27-776 REISSUE ECB #350194... | $0 | $0 | Oct 29, 2015 |
| Sep 16, 2015 | 35147653L | RESOLVE | CLASS - 2 | REISSUED ECB #35093858Y FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANTMANNER NO FIRE STOPPING PER BC 7123; 27-345. RE... | $0 | $0 | Oct 29, 2015 |
| Apr 2, 2014 | 35093860N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. ROOF LEAKING ATSEVERAL AREAS INTO 3RD FL HALLWAY & CLASSROOM. ... | $500 | $0 | May 22, 2014 |
| Apr 2, 2014 | 35093859X | RESOLVE | CLASS - 2 | RE-ISSUE ECB #35019150N ALTERED/CHANGED BLDG OCCUPIED W/O A VALID CERT OF OCCUPANCY BLDG ALTERED UNDER JOB #102278269... | $0 | $0 | Jun 5, 2014 |
| Apr 2, 2014 | 35093858Y | RESOLVE | CLASS - 2 | RE-ISSUE ECB #35019453K FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER NO FIRE STOPPING PER BC712.3; 27-345 INSIDE... | $0 | $0 | Jun 5, 2014 |
| Apr 2, 2014 | 35093857M | RESOLVE | CLASS - 2 | 27-776 REISSUE ECB #35019455Y FRESH AIR IN GAS METER RM NO FRESH AIR IN GAS METER ROOM IN BASEMENT. REMEDY: PROVIDE F... | $0 | $0 | Jun 5, 2014 |
| May 6, 2013 | 35019150N | RESOLVE | CLASS - 2 | REISSUE: 34941403K. ALTERED BLDG OCCUPIED W/O A VALID C/O REQUIRED BY JOB #102278269. REMEDY: OBTAIN C/O. | $0 | $0 | Jul 18, 2013 |
| May 6, 2013 | 35019456X | RESOLVE | CLASS - 2 | THE CORRIDOR/HALLWAY FLR IS RISING CAUSING A TRIPPING HAZARD LOCATED ADJACENT TO ROOM B-48. REMEDY: REPAIR/REPLACE FLR. | $0 | $0 | Jul 18, 2013 |
| May 6, 2013 | 35019453K | RESOLVE | CLASS - 2 | REISSUE: 34941404M. THE ELECTRICAL ROOM IS LACKING FIRE STOPPING ABOVETHE ENTRY DOOR AT THE BASEMENT LEVEL. REMEDY: P... | $0 | $0 | Jul 18, 2013 |
| May 6, 2013 | 35019455Y | RESOLVE | CLASS - 2 | REISSUE: 34941402Z. THE GAS METER ROOM IS LACKING FRESH AIR VENTILATION AT THE BASEMENT LEVEL. REMEDY: PROVIDE/MAINTA... | $0 | $0 | Jul 18, 2013 |
| Mar 6, 2012 | 34941401R | RESOLVE | CLASS - 2 | REISSUE # 34921718R. GAS METER ROOM & ELECTRICAL ROOM ARE BEING USED FOR STORAGE OF MAINTENANCE & CONSTRUCTION MATERI... | $0 | $0 | May 17, 2012 |
| Mar 6, 2012 | 34941402Z | RESOLVE | CLASS - 2 | 27-766. REISSUE # 34921715L. NO FRESH AIR VENT IN GAS METER ROOM. REMEDY: PROVIDE FRESH AIR VENT. | $0 | $0 | May 17, 2012 |
| Mar 6, 2012 | 34941403K | RESOLVE | CLASS - 2 | REISSUE # 34921714J. BLDG ALTERED UNDER JOB # 102278269 & NO NEW C/O ISSUED. BASEMENT IS BEING OCCUPIED WITHOUT A VAL... | $0 | $0 | May 17, 2012 |
| Mar 6, 2012 | 34941404M | RESOLVE | CLASS - 2 | HOLES IN WALL OF ELECTRICAL ROOM ABOVE DOOR AT PIPE PENETRATION. REMEDY: PROVIDE/MAINTAIN FIRE STOPPING. | $0 | $0 | May 17, 2012 |
| Nov 3, 2011 | 34897794L | RESOLVE | CLASS - 1 | 3314 SUPPORTERD SCAFFOLD DOES NOT MEET DOB SPECIFICATIONS MISSING TOE BOARDS MISSING NETTING DO NOT REMOVE EQUIPMENT ... | $0 | $0 | Dec 22, 2011 |
| Jul 26, 2011 | 34921717P | RESOLVE | CLASS - 2 | PARTIAL OBSTRUCTION AT 1FL ENTRY PARTIAL CORRIDOR OBSTRUCTION W/ FURNITURE TABLES CHAIRS BOXES REM; REMOVE ALL ITEMS ... | $0 | $0 | Sep 15, 2011 |
| Jul 26, 2011 | 34921716N | RESOLVE | CLASS - 2 | REISSUE #34195102P NO PLACE OF ASSEMBLY CERTIFICATE OF OPERATION. NO P/A ISSUED FOR GYM #153,DRAMA STUDIO #157,CAFETE... | $0 | $0 | Oct 20, 2011 |
| Jul 26, 2011 | 34921715L | RESOLVE | CLASS - 2 | 27-766 REISSUE #34779613X NO FRESH AIR VENT AT GAS METER ROOM AT BSMT LVL GAS METER ROOM NO FRESH AIR VENTILATION REM... | $0 | $0 | Sep 15, 2011 |
| Jul 26, 2011 | 34921714J | RESOLVE | CLASS - 2 | REISSUE #34779614H ALTERED BLDG OCCUPIED W/O VALID C/O BSMT ALTERED UNDER JOB#102278269 ALT1 OCCUPIED W/O A VALID CER... | $0 | $0 | Sep 15, 2011 |
| Jul 26, 2011 | 34921718R | RESOLVE | CLASS - 2 | GAS METER ROOM SERVICE AT BSMT LVL GAS METER ROOM W/ STORAGE OF VARIOUS MAINTENANCE AND CONSTRUCTION MATERIAL REM; RE... | $0 | $0 | Sep 15, 2011 |
| Jun 14, 2011 | 34852240K | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER. DEFECTS NOTED: 3RD FLR WATER DAMAGE CEILING TILES AT VARIOUS LOCAT... | $0 | $0 | Aug 4, 2011 |
| Jan 20, 2011 | 34892551Y | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/ COMMISSIONERS ORDER TO FILE A CERT OF CORRECTION FOR NOV#34878547R.REM:FILE CERT OF CORRECTION. | $0 | $0 | May 12, 2011 |
| Jan 20, 2011 | 34892550M | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/ COMMISSIONERS ORDER TO FILE A CERT OF CORRECTION FOR NOV#34879257R.REM:FILE CERT OF CORRECTION. | $0 | $0 | May 12, 2011 |
| Nov 12, 2010 | 34879257R | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY.DEFECT NOTED:@ TIME OF INSPECTION @ 3STORY STAIRWELL THERE IS BAGS OF... | $1,200 | $0 | Apr 21, 2011 |
| Nov 12, 2010 | 34879256P | RESOLVE | CLASS - 1 | FAILURE TO SAFEGUARD ALL PERSONS & PROPERTY AFFECTED BY CONSTRUCTION OPERATIONS.DEFECTS NOTED:@ TIME OF INSPECTION ME... | $2,400 | $0 | Apr 21, 2011 |
| Oct 6, 2010 | 34879133P | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG WALL(S) OR APPURTENANCES. DEFECTS NOTED: AT TIME OF INSPECTION THERE IS SPALLING BRICK AT EX... | $1,000 | $0 | Feb 10, 2011 |
| Aug 17, 2010 | 34872067Y | ACTIVE | CLASS - 1 | OPERATION OF PLACE OF ASSEMBLY W/O A CURRENT P.A. PERMIT APPL#1046355441 GYM DISAPPROVED APPROX 150 PERSONS.REM:OBTAI... | $1,600 | $0 | May 19, 2011 |
| Aug 17, 2010 | 34872066M | ACTIVE | CLASS - 1 | OPERATION OF PLACE OF ASSEMBLY W/O A CURRRENT P.A. PERMIT APPL#1046355450 DRAMA STUDIO DISAPPROVED AAPROX 100 PERSON ... | $1,600 | $0 | May 19, 2011 |
| Aug 17, 2010 | 34872065K | ACTIVE | CLASS - 1 | OPERATION OF PLACE OF ASSEMBLY W/O A CURRENT P.A. PERMIT.APPL#104635469 CAFETERIA DISAPPROVED. APPROX 170 PERSON SEAT... | $1,600 | $0 | May 19, 2011 |
| Aug 17, 2010 | 34872069H | ACTIVE | CLASS - 2 | MISSING FRESH AIR INTAKE INSIDE GAS METER ROOM.REM:INSTALL F.A.I | $500 | $0 | May 19, 2011 |
| Aug 17, 2010 | 34872068X | ACTIVE | CLASS - 2 | ALTERED BLDG OCCUPIED W/O A CURRENT COFO 102278269 EXP 8-11-2004 NOTED:BLDG OCCUPIED AS PUBLIC SCHOOL.BSMT LEVEL# OF ... | $500 | $0 | May 19, 2011 |
| May 20, 2009 | 34779618P | RESOLVE | CLASS - 2 | ELECTRICAL ROOM AT BASEMENT IS BEING USED TO STORE BOXS,CHAIRS LIGHTING,ECT. REMEDY: REMOVE STORAGE FROM ELECTRICAL R... | $0 | $0 | Jul 9, 2009 |
| May 20, 2009 | 34779610K | RESOLVE | CLASS - 2 | REISSUE: 34195102P OPERATION OF A PLACE OF ASSEMBLY W/O A CURRENT CERTIFICATE OF OPERATION. NOTE: GYM,DRAMA STUDIO & ... | $0 | $0 | Jul 9, 2009 |