ECB violations
106 West 83 Street, Manhattan • Block 01213 • Lot 0038
31 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Jan 20, 2026 | 39174428Y | ACTIVE | CLASS - 2 | FAILURE TO SUBMIT CERTIFICATE OF CORRECTION FOR VIOLATION #39154033L ISSUED ON 07/17/2025 FOR WORK WITHOUT A PERMIT(M... | $1,250 | $1,250 | Oct 15, 2026 |
| Jul 17, 2025 | 39154033L | RESOLVE | CLASS - 1 | METAL STRUCTURE AT REAR OF ABOVE BUILDING BUILT ON LOTLINE APPROX 30' X15' AND 20' HIGH;NO PERMIT ON FILE FOR THIS WO... | $1,250 | $1,250 | Apr 2, 2026 |
| Oct 17, 2023 | 39097230M | RESOLVE | CLASS - 2 | AS PER ONE ROCKMILLS MP-40. STEAM HEATING BOILER; NO PRV ON PIPING FOR DOMESTIC HOT WATER COIL-THERMOMETER FOR DOMEST... | $312 | $312 | Jan 2, 2025 |
| Sep 22, 2021 | 39047891Y | RESOLVE | CLASS - 2 | CORRODED PIPE TO BOILER LEFT SIDE/GAS PIOLIT REGULATOR AND TUBING INCORRECT/COLD WATER THERMO LOOP MISSING FROM HW MI... | $0 | $0 | Nov 18, 2021 |
| Oct 15, 2019 | 39011246R | RESOLVE | CLASS - 1 | I OBSERVED IN THE BASEMENT AT THE THE ELECTRICAL SERVICE EQUIPMENT THE SERVICE ENTRANCE CONDUCTORS INSTALLED IN A HOL... | $0 | $0 | Mar 12, 2020 |
| Oct 15, 2019 | 39011245P | RESOLVE | CLASS - 1 | I OBSERVED INSIDE THE 100 AMP SERVICE SWITCH THE NEUTRAL NOT BONDED TO THE ENCLOSURE (MISSING MAIN BONDING JUMPER) VI... | $1,500 | $0 | Mar 12, 2020 |
| Oct 15, 2019 | 39011244N | RESOLVE | CLASS - 2 | I OBSERVED OUTSIDE UNDERNEATH THE FRONT STAIRS AT THE UTILITY ENDLINE BOX THE USE OF EMT PIPE AS A SERVICE RACEWAY IN... | $800 | $0 | Mar 12, 2020 |
| Jan 14, 2019 | 35390713Y | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION #35372491Z ISSUED ON 11/19/18 AND TO FI... | $1,250 | $0 | May 23, 2019 |
| Nov 19, 2018 | 35372491Z | RESOLVE | CLASS - 1 | OCCUPANCY CONTRARY TO THAT ALLOWED BY THE CERTIFICATE OF OCCUPANCY OR BUILDINGS DEPT RECORDS NOTED: COFO #121840259 I... | $6,250 | $0 | May 23, 2019 |
| Oct 1, 2018 | 35361390X | RESOLVE | CLASS - 1 | OCCUPANCY CONTRARY TO THAT ALLOWED BY THE CERTIFICATE OF OCCUPANCY OR BUILDING DEPARTMENT RECORDS. C OF O #121840259 ... | $2,500 | $0 | Mar 21, 2019 |
| Oct 1, 2018 | 35361389Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. NOTED: AT EXP# 2, 3 AND 4. AT PARAPET WALLS MORTAR CRACKED AND... | $1,250 | $0 | Jan 17, 2019 |
| Jul 17, 2018 | 32097272X | RESOLVE | CLASS - 2 | B254,50A,50B,50C,50D,50E,50F,50G,50H. AS PER CLASS 2 (B254) 28.301.1 FAILURE TO MAINTAIN 50A-FLUE PIPING NOT SUPPORTE... | $625 | $0 | Nov 1, 2018 |
| May 1, 2018 | 32096378J | RESOLVE | CLASS - 2 | B254:5B,6,15,32A:AS PER CLASS 2 B254 28-301.1.VIOLATING CONDITIONS:MISSING DISCHARGE PIPE;MISSING DOMESTIC RELIEF VAL... | $625 | $0 | Aug 23, 2018 |
| Mar 13, 2018 | 35324826P | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.OBSERVED ON 03/13/18 AT ABOVE ADDRESS IMPORPER VENTILATION USED... | $312 | $0 | Nov 1, 2018 |
| Feb 16, 2018 | 35284107P | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION #35311452R ISSUED 01/10/18 AND TO FILE... | $400 | $0 | Jun 14, 2018 |
| Jan 10, 2018 | 35311452R | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. AT BASEMENT LEVEL, THE TWO SEPARATE GAS METER ROOMS, DO NOT HA... | $1,000 | $0 | May 10, 2018 |
| Dec 12, 2017 | 35274340M | RESOLVE | CLASS - 1 | AN UNLAWFUL ACT. FAILURE TO COMPLY W/AN ORDER OF THE COMMISSIONER. FAILURE TO CORRECT & CERTIFY ECB#35290398P ISSUED ... | $2,400 | $0 | Apr 19, 2018 |
| Nov 24, 2017 | 35297608X | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED: AT TIME OF INSPECTION THERE WERE NO FRESH AIR VENTS TO E... | $2,500 | $0 | Jun 21, 2018 |
| Oct 13, 2017 | 35294475H | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. AT TIME OF INSPECTION NEITHER OF THE 2 GAS METER ROOMS IN CELLAR,H... | $1,000 | $0 | May 10, 2018 |
| Sep 6, 2017 | 35290366K | RESOLVE | CLASS - 3 | OCCUPANCY CONTRARY TO THAT ALLOWED BY THE C OF O OR BLDG DEPT RECORDS.TCO#121840259 INDICATES 1ST STY AS 9 SRO ROOMS,... | $500 | $0 | Mar 29, 2018 |
| Sep 6, 2017 | 35290398P | RESOLVE | CLASS - 1 | FAILURE TO GROUND ELECTRICAL SYSTEMS. OBSERVED CONDUCT W/GROUNDING CONDUCTOR BROKEN & LAYING ON FLOOR OF SPRINKLER CO... | $4,800 | $0 | Mar 29, 2018 |
| Sep 6, 2017 | 35290545X | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER.OBSERVED ON 09/06/2017 @ABOVE ADDRESS IN CELLAR NO FRESH AIR IN TAK... | $1,000 | $0 | Mar 29, 2018 |
| Sep 6, 2017 | 35290397N | RESOLVE | CLASS - 2 | ELECTRICAL WORK W/O A PERMIT. NO ELECTRICAL APPLICATION ON FILE FOR ANY EXISTING OF NEW WORK PERTAINING TI ELECTRICAL... | $800 | $0 | Mar 29, 2018 |
| Feb 24, 2016 | 35171555H | RESOLVE | CLASS - 3 | OCCUPANCY CONTRARY TO THAT ALLOWED BY THE C OF O OR BLDG DEPT RECORDS.C OF O #121840259T003 INDICATES 1ST FL TO BE 9 ... | $400 | $0 | Apr 14, 2016 |
| Feb 24, 2016 | 35171556J | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF CLOSING. THE FOLLOWING DOORS NOT SELF CLOSING: 3RD FL WEST SIDE EXIT DOOR,2ND FL WEST & EAST DOORS... | $0 | $0 | Apr 14, 2016 |
| Jan 23, 2014 | 35034184R | RESOLVE | CLASS - 1 | SEC. 715. FAILURE TO COMPLY W/OPENING PROTECTIVES. NOTED: EXIT DOORS LEADING TO STAIRCASE ARE LOCKED IN OPEN POSITION... | $400 | $0 | Sep 18, 2014 |
| Jan 23, 2014 | 35034182N | RESOLVE | CLASS - 1 | OCCUPANCY CONTRARY TO THAT ALLOWED BY C/O #94927 ILLEGAL OCCUPANCY NOTED: 1)CELLAR OCCUPIED AS A CAFETERIA & OFFICES.... | $1,200 | $0 | Sep 18, 2014 |
| Jan 23, 2014 | 35034183P | RESOLVE | CLASS - 2 | WORK W/O PERMIT. WORK NOTED: CREATE CONCIERGE DECK & GLASS LOBBY ENTRANCE. REMEDY: STOP ALL WORK. OBTAIN PERMIT. | $800 | $0 | Sep 18, 2014 |
| Jan 15, 2003 | 34372786J | RESOLVE | Non-Hazardous | WORK WITHOUT PERMITK WORK NOTED GUT DEMO NOTED THROUGHOUT BLDF FROM 1 FLOOR THRU 5 FL GUT DEMO APPROX 40% COMPLETED N... | $0 | $0 | Mar 4, 2004 |
| Jan 12, 2000 | 34155342H | RESOLVE | Non-Hazardous | WORK WITHOUT A PERMIT.WORK NOTED PARTITION WALL REMOVED BETWEEN ROOMS 5F AND 5E AT 5 STORY REAR SECTION.STOP ALL WORK... | $2,500 | $0 | Mar 16, 2000 |
| Aug 3, 1988 | 34011206K | RESOLVE | Non-Hazardous | OCCUPANCY CONTRARY TO THAT ALLOWED BY THE C OF O. REMEDY: FILE PLANS TO OBTAIN APPROVALS. | $250 | $0 | Feb 2, 1989 |