Skip to content

ECB violations

100-102 West 96 Street, Manhattan • Block 01226 • Lot 0029

18 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Aug 7, 2026 39199632M ACTIVE CLASS - 2 CLASS 2 ITEMS: CAR SHOES ARE SCRAPING AGAINST THE GUIDE RAILS DURING ELEVATOR TRAVEL. ADJUST OR REPLACE WORN/DAMAGED ... $625 $625 Oct 15, 2026
May 2, 2019 38269453L RESOLVE CLASS - 2 16I11, 16H10, 41B7, 68B7. 16-I-11, 6,2 + LOBBY FLOOR HOIST WAY DOOR RELEASE ROLLERS DAMAGED, REPLACE/16-H-10 CAR DOOR... $625 $0 Jun 27, 2019
Mar 20, 2009 32066391R RESOLVE CLASS - 2 18B.50A.48B.50B.50C.50D.50E.50A SPILL AW. DISCONNECTED 50B DRAFT INDUCER MOTOR NOT WORKING 50C INSTALL DRAIN LINE ON ... $250 $0 May 14, 2009
Apr 2, 2008 34418741R RESOLVE Hazardous 27-129(D)(I)(A) LOCAL LAW REPORT FILED AS "UNSAFE"; UNSAFE CONDITION EXISTED & NO MEASURES TAKEN TO SECURE SAFETY OF ... $0 $0 Sep 4, 2008
Mar 25, 2008 34635354H RESOLVE Non-Hazardous "STOP ALL WORK".FAILURE TO PROVIDE CONTRACTORS SIGN. $250 $0 May 28, 2009
Mar 25, 2008 34635353X RESOLVE Non-Hazardous SIDEWALK SHED DOES NOT MEET BUILDING CODE SPECIFICATION 1 NO VANDAL PROOF LIGHT FIXTURES. $2,000 $0 Oct 31, 2008
Mar 12, 2008 34635184Y RESOLVE Hazardous FAILURE TO PROVIDE ADEQUATE PROTECTION FOR SIDEWALKS DURING CONSTRUCTION OPERATIONS THE OUTER SIDE AND ENDS SHALL BE ... $2,000 $0 Jul 10, 2008
Dec 19, 2007 34617994R RESOLVE Hazardous WORK W/O A PERMIT WORK NOTED:THE DEMOLITIAN OF INTERIOR PARTITION WALLS THRU-OUT NOTED LOCATION PENTHOUSE LEVEL EAST ... $500 $0 Feb 14, 2008
Nov 21, 2007 34606060J RESOLVE Hazardous USING HOISTING EQUIPMENT W/O A SPECIAL RIGGER LICENSE - MATERIAL HOIST/ELECTRIC. OPERATION OF HOISTING EQUIPMENT IN U... $5,250 $0 Dec 4, 2008
Aug 22, 2007 32052300P RESOLVE Non-Hazardous 18B,40. $180 $0 Mar 27, 2008
May 26, 2004 32044842J RESOLVE Non-Hazardous BQ9/6B/36/50 BQ9-BOILR IS A RUDO WITH A H STAMP 6B) PIPE SIZE FROM BOILER TO SAFTEY RELIEF VALVE WITHOUT THE REDUCING... $0 $0 Jul 15, 2004
May 26, 2004 32044841H RESOLVE Non-Hazardous 50A/50B/50C 1988 FULTON 56127 50A)REVERSE THE VALVES SO THAT THE QUICKCLOSING VALVE ON THE BOTTOM BLOWDOWN LINE IS CL... $180 -$180 Jul 15, 2004
Dec 18, 2001 32026343X RESOLVE Non-Hazardous 16/49. LEFT SIDE OF THE BOILER NOT ACCESSIBLE FOR INSPECTION. THE PIPE UNDER SIZE FOR LOW PRESSURRE BOILER AND HIGH P... $0 $0 Jan 23, 2003
Jan 22, 1999 38083711J RESOLVE Non-Hazardous 60J 60 PROVIDE PROPER CONTERWEIGHT CLEARENCE BETWEEN BUFFER $0 $0 Mar 11, 1999
Oct 10, 1997 38065754K RESOLVE Non-Hazardous 37A35O23U #37-JUMPERS. $0 $0 Dec 4, 1997
Oct 10, 1997 38065755M RESOLVE Non-Hazardous 35O23U74M18Q22D34I #74 DUST COVERS 1 FL #34 REMOVE OLD TRAVELLING CABLE. $0 $0 Dec 4, 1997
Oct 29, 1996 38057532P RESOLVE Non-Hazardous 46K,46K. RENEW OR REPLACE(EXCESSIVE)CABLE ROUGE REMEDY: OR REPLACE CABLES. $0 $0 Dec 19, 1996
Jan 26, 1993 32009649Y RESOLVE Non-Hazardous 64A,46B. REPLACE HANDLES ON SIGHTGLASS VALUES ; SIGHTGLASS LEAKING ON STEAM END. CLEAN OR REPLACE SIGHTGLASS. $50 $0 Apr 15, 1993