ECB violations
201 West 87 Street, Manhattan • Block 01235 • Lot 0029
76 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Feb 17, 2011 | 34838485H | RESOLVE | CLASS - 1 | SEC. 1003.3.1. FAILURE TO COMPLY W/HEADROOM REQUIREMENTS. NOTED: HAVING CHIMNNEY INSTALLED IN EXIT PASSAGEWAY BETWEEN... | $1,600 | $0 | Apr 7, 2011 |
| Feb 17, 2011 | 34838489P | RESOLVE | CLASS - 1 | SEC. 1008.4.3. FAILURE TO MEET EGRESS EXIT & EXIT DISCHARGE REQUIREMENTS LOCATED ON 2-5 FLRS DOUBLE HUNG WINDOWS ARE ... | $0 | $0 | Aug 1, 2011 |
| Feb 17, 2011 | 34838490M | RESOLVE | CLASS - 2 | OCCUPANCY CONTRARY TO THAT ALLOWED BY BLDG DEPT RECORDS. ILLEGAL OCCUPANCY. NOTED: HAVING COMMERCIAL LAUNDRY AT GROUN... | $0 | $0 | Aug 1, 2011 |
| Feb 17, 2011 | 34838486J | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY. NOTED: 1) EXIT PASSAGGEWAY FROM REAR FIRE ESCAPE OBSTRUCTED BY GARBA... | $1,200 | $0 | Apr 7, 2011 |
| Feb 17, 2011 | 34838492X | RESOLVE | CLASS - 2 | ZR32-653. HAVING ILLUMINATED AWNING SIGNAGE (DELI) W/SURFACE AREA EXCEEDING 12 SQ FT, W/LETTERS HIGHER THAN 12", NOT ... | $0 | $0 | Apr 7, 2011 |
| Feb 17, 2011 | 34838493H | RESOLVE | CLASS - 2 | ZR32-652. FAILURE TO COMPLY W/PERMITTED PROJECTION IN COMMERCIAL DISTRICTS. LOCATED IN C1-9 DISTRICT DOUBLE FACED ILL... | $0 | $0 | Apr 7, 2011 |
| Feb 17, 2011 | 34838484X | RESOLVE | CLASS - 1 | SEC. 715. FAILURE TO COMPLY W/OPENING PROTECTIVES REQUIREMENT. NOTED: MISSING FPSC DOORS FROM 2 TO 5 FLRS BETWEEN COR... | $1,600 | $0 | Apr 7, 2011 |
| Feb 17, 2011 | 34838483Y | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/(MAXIMUM) FLR AREA REQUIREMENTS PER OCCUPANT (LOCATED). ROOMS 203,208,210,211,302,303,304 OCCUPIE... | $0 | $0 | Apr 7, 2011 |
| Feb 17, 2011 | 34838487L | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCES. NOTED: STOOP CRACKED DETERIORATED & HAS SEPARATION. REMEDY: REPAIR/R... | $1,000 | $0 | Apr 7, 2011 |
| Feb 17, 2011 | 34838491Y | RESOLVE | CLASS - 2 | ALTERED/CHANGED BLDG OCCUPIED W/O A VALID C/O AS PER 28-118.3.1-28-118.3.2. ALT 120451082. REMEDY: OBTAIN VALID C/O A... | $250 | $0 | Jul 7, 2011 |
| May 5, 2009 | 34775459Z | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. DEFECTS NOTED: LOOSE DECORATIVE STONE,LOOSE BRICKS,VERTICAL CR... | $1,000 | $0 | May 13, 2010 |
| Apr 6, 2009 | 38202325K | RESOLVE | CLASS - 2 | 54BB12.55BB12.56O2.60B7.77O2.32B1.02B7.40O2.37M7 02 INCREASE DECIBEL LEVEL OF ALARM SYSTEM 40 REMOVE STORED MATERIALS... | $500 | $0 | May 13, 2010 |
| Nov 27, 2007 | 32055169M | RESOLVE | Hazardous | 50A,BQ9.50A-BQ9 27-147,BOILER(BURNHAM)& GAS BURNER INSTALLED W/O AN APPROVAL & WORK PERMIT FROM NYC DEPT OF BLDG APPL... | $1,300 | $0 | May 8, 2008 |
| Sep 7, 2007 | 32052312M | RESOLVE | Hazardous | CEASE USE.1,50A,51,10A.OPERATING A SEALED BOILER,CEASE USE ORDER FOR GAS BURNHAM BOILER SPILLING CARBON MONOXIDE WAS ... | $800 | $0 | Oct 25, 2007 |
| Aug 22, 2007 | 32052146X | RESOLVE | Non-Hazardous | 18B,50A,B.50A-LEAK AT UNION OF BOILER FEED LINE.50B-LEAK ON WATER COLUMN UNION. | $0 | $0 | Oct 11, 2007 |
| Aug 22, 2007 | 32052147H | RESOLVE | Non-Hazardous | CEASE USE.50A,B,C,D,E,51.50A-SPILLAGE OF CARBON MONOXIDE FROM BOILER READING 850 PPM IN BOILER ROOM.50B-ADJUST GAS BU... | $0 | $0 | Oct 25, 2007 |
| Jan 24, 2006 | 32049265L | RESOLVE | Non-Hazardous | 50A/50B. FULTON V.T. BOILER, 10HP, NB 53941, OIL, 1988. (50A)DETERIORATED SEALS ON CONNECTION PASS OPENINGS AT UPPER ... | $2,500 | $0 | Mar 16, 2006 |
| Jan 24, 2006 | 32049266N | RESOLVE | Non-Hazardous | 6A. BURNHAM C.R. BOILER, LP STEAM, OIL FD, 2000. 6A-SAFETY VALVE LEAKING. INSTALL AN ASME-APPROVED SAFETY VALVE (2" X... | $180 | $0 | Apr 27, 2006 |
| May 24, 2004 | 32044829P | RESOLVE | Non-Hazardous | 18B/48B 1998 FULTON 53941 NBD# | $0 | $0 | Jul 8, 2004 |
| Mar 12, 2003 | 32041526Y | RESOLVE | Non-Hazardous | 44A/50A/50C/4B/50B/50D. 50A NO DRAFTSTAT INSTALLED ONTHE FLUE PIPE OF THE OIL-FIRED BOILER. 50B SAFETY VALVE DISCHARG... | $0 | $0 | May 1, 2003 |
| Feb 7, 2003 | 32041370R | RESOLVE | Non-Hazardous | B4B/3A/50. 3A OUTSIDE CHIMNEY POPE CRACKED AND ROTTED IN SEVERAL SECTIONS. NEEDS AT LEAST DOUBLE WALL CHIMNEY PIPE OF... | $400 | $0 | Mar 27, 2003 |
| Jul 1, 2002 | 32034238Y | RESOLVE | Non-Hazardous | 11A, 48C, 49. NO DISCHARGE PIPE ON SAFETY VALVE 11A MISSING SECONDARY SHUT OFF VALVE ON BLOWDOWN LINE 48C NO DRAIN LI... | $0 | $0 | Aug 15, 2002 |
| May 21, 2001 | 38116536J | RESOLVE | Non-Hazardous | 3M7,37G12,37U16,50Y11.3M7=CAPACITY PLATE 37G12=3 & 4 = INCORRECT CITY ID ON CONTROLLER. | $0 | $0 | Jul 5, 2001 |
| Aug 9, 2000 | 34257678Z | RESOLVE | Non-Hazardous | FAILURE TO PROVIDE A SYSTEM OF AUTOMATIC SPRINKLERS WHERE REQUIRED.REMEDY: PROVIDE AUTOMATIC SPRINKLERS LOCATION:CELL... | $0 | $0 | Sep 28, 2000 |
| May 22, 2000 | 38097980P | RESOLVE | Non-Hazardous | 46K12 47H12 03M12 50O02 33O02 33I12 15M12 74O02 46-REPLACE TOP OF CAR TO BRUM CABLES (47) CHANGE GOV.BABLE 03-INSTALL... | $0 | $0 | Jul 13, 2000 |
| May 19, 1999 | 34176838Y | RESOLVE | Non-Hazardous | FAILURE TO FILE A REPORT OF COMPLIANCE W/ LL 16/84-CERTIFYING TO THE INSTALLATION OF REQUIRED FIRE PROTECTION SYSTEMS... | $0 | $0 | Jul 8, 1999 |