Skip to content

ECB violations

2526-2530 Broadway, Manhattan • Block 01242 • Lot 0039

42 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Aug 3, 2026 39198789X ACTIVE CLASS - 1 CLASS 1: CLASS 1: DROP CEILING PANEL LEADING TO THE EMERGENCY ESCAPE HATCH AND THE ESCAPE HATCH ARE UNSECURED, PROVID... $1,250 $1,250 Oct 8, 2026
Aug 3, 2026 39198788Y ACTIVE CLASS - 2 CLASS 2: TOP OF CAR LIGHT IS DAMAGED, AS PER ASME A17.1-2013, SEC. 2.7.9.2. REMEDY: REPAIR OR REPLACE THE LIGHT. COUN... $625 $625 Oct 8, 2026
Aug 3, 2026 39198811N ACTIVE CLASS - 1 ELECTRICAL CLOSET NOT DEDICATED TO ELECTRICAL DISTRIBUTION EQUIPMENT ONLY. OBSERVED ON THE 4TH FL ELECTRICAL CLOSET N... $1,200 $1,200 Oct 8, 2026
Aug 3, 2026 39198808M ACTIVE CLASS - 1 AT THE TIME OF INSPECTION OBSERVED LACK OF COVERAGE AND OBSTRUCTED SPRINKLER HEADS LOCATED THROUGH OUT THE BUILDING C... $2,500 $2,500 Oct 8, 2026
Aug 3, 2026 39198810L ACTIVE CLASS - 2 UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT, APPARATUS, MATERIALS, DEVICES, APPLIANCES OR WIRING IN USE. OBSERV... $250 $250 Oct 8, 2026
Aug 3, 2026 39198809Y ACTIVE CLASS - 1 ELECTRICAL WORK WITHOUT A PERMIT. OBSERVED ON THE ROOF NEW A/C CONDENSERS INSTALLED NEW OUTDOOR PANELS AND PIPPING AL... $2,500 $2,500 Oct 8, 2026
Aug 3, 2026 39198807K ACTIVE CLASS - 1 ATOI OBSERVED IN THE MAIN BOILER ROOM 2 OUT OF THE 5 GAS BOILERS REMOVED CHECKED BIS/DOBNOW NO PERMIT ON FILE FOR REM... $2,500 $2,500 Oct 8, 2026
Jul 29, 2025 39155303R ACTIVE CLASS - 2 OBSERVED IN THE LAUNDRY CHUTE ROOM ON FLOORS 4,3,2 INSTALLED NEW SPRINKLER SYSTEM 99 PERCENT OF THE WORK COMPLETED NO... $1,250 $0 Nov 6, 2025
Jul 29, 2025 39155285M RESOLVE CLASS - 2 FOUND LAARS GAS FIRED BOILERS MODEL # PH0400, WITH EXPOSED WIRING, BOILER ROOM DOOR NOT SELF CLOSING, OPENINGS ON CEI... $625 $0 Nov 6, 2025
Jul 29, 2025 39155300L RESOLVE CLASS - 2 EXIT DOOR NOT SELF-CLOSING. OBSERVED FIRE PUMP ROOM AT ROOF LEVEL AND GAS METER ROOM AT BASEMENT LEVEL. DOORS DO NOT ... $0 $0 Oct 2, 2025
Jul 29, 2025 39155267Z ACTIVE CLASS - 1 CEASE USE SLANT FIN GAS FIRED BOILERS (4) MODEL #GXH-300, DUE TO HAZARDOUS CONDITION OF SAFETY RELIEF VALVES DEFECTIV... $2,500 $0 Oct 2, 2025
Jul 29, 2025 39155298L RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... $2,500 $0 Oct 2, 2025
Jul 29, 2025 39155299N RESOLVE CLASS - 1 UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT, APPARATUS, MATERIALS, DEVICES, APPLIANCES OR WIRING IN USE. OBSERV... $1,600 $0 Oct 2, 2025
Jul 29, 2025 39155301N RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8 (2014 C... $2,500 $0 Oct 2, 2025
Jul 29, 2025 39155302P RESOLVE CLASS - 2 OBSERVED NO ACTIVE SPRINKLER SYSTEM FOR FLOORS 2 THROUGH 9 THE ROOF TANK VALVE IS CLOSED THAT SUPPLY WATER TO THE FIR... $0 $0 Oct 2, 2025
Jul 28, 2025 39155117N RESOLVE CLASS - 2 CLASS 2 ITEM: PROVIDE AN UPDATED CATERGORY 5 TEST TAG. $0 $0 Nov 6, 2025
Aug 9, 2024 39121460P RESOLVE CLASS - 2 HOLE PENETRATIONS ON WALLS AND CEILINGS WITH PIPES AND WIRES RUNNING THROUGH THEM LOCATED IN THE MECHANICAL ROOMS THR... $0 $0 Oct 17, 2024
Aug 9, 2024 39121546X RESOLVE CLASS - 1 OBSERVED IN THE SECOND GAS METER ROOM LOCATED IN THE BASEMENT/CELLAR NO FRESH AIR VENTILATION NOTED. AS PER E 4 OF TH... $312 $0 Mar 13, 2025
Aug 9, 2024 39121547H RESOLVE CLASS - 2 OBSERVED IN THE MAIN GAS METER ROOM EXCESSIVE COMBUSTIBLE STORAGE (SUCH AS A WORK TABLE CHAIRS, ELECTRIC FAN). AS PER... $0 $0 Oct 17, 2024
Feb 5, 2020 35470491H RESOLVE CLASS - 1 BC33091-FAILURE TO PROTECT ADJOINING STRUCTURES(GENERAL)NOTED:AT TIME OF MY INSPECTIONOF AN ALTERATOIN TYPE-1 9 STORI... $2,500 $0 Nov 19, 2020
Feb 5, 2020 35470492J RESOLVE CLASS - 1 WORK DOES NOT CONFORM TO APPROVED CONSTRUCTION DOCUMENTS AND OR AMENDMENTS.NOTED:AT TIME OF MY INSPECITON OF AN ALTER... $2,500 $0 Nov 19, 2020
Feb 5, 2020 35470493L RESOLVE CLASS - 1 FAILURE TO MAINTAIN/DISPLAY ON-SITE DOCUMENTS REQUIRED BY CHAPTER 33.NOTED:AT TIME OF MY INSPECTION OF AN ALTERATION ... $1,250 $0 Nov 19, 2020
Feb 5, 2020 35470494N RESOLVE CLASS - 1 CONSTRUCTION SUPERINTENDENT FAILED TO PERFORM DUTIES PER CODE.NOTED:ATTIME OF MY INSPECTION OF AN ALTERATION TYPE 1,9... $10,000 $0 Nov 19, 2020
Feb 5, 2020 35470495P RESOLVE CLASS - 2 BC330113-CONTRACTORS SHED NOT FIRE RETARDANT TREATED.NOTED:AT TIME OF INSPECTION OF ALTERATION TYPE-1 8 STORY ELEVATO... $0 $0 Nov 19, 2020
Feb 21, 2019 35369479Z RESOLVE CLASS - 2 28-104.8.4 FAILURE TO DISPLAY TENANT PROTECTION PLAN. AT THE TIME OF INSPECTION OF A 9 STORY BUILDING UNDER CONSTRUCT... $620 $0 Apr 18, 2019
Feb 21, 2019 35369480X RESOLVE CLASS - 1 FAILURE TO SAFEGUARD. AT THE TIME OF MY INSPECTION OF A 9 STY BLDG,I OBSERVED MULTIPLE PIECES OF REBAR STICKING OUT F... $0 $0 Apr 18, 2019
Jul 28, 2017 38256813N RESOLVE CLASS - 1 CU05A10,72X10,29D06,40AA02,52D06,98M07. 05A10-CEASE USE ITEM. DOOR ZONE RESTRICTOR HAS BEEN TAMPERED WITH/DISABLED AN... $1,000 $0 Sep 14, 2017
Jan 27, 2017 38253050K RESOLVE CLASS - 2 41M10. MACHINE ROOM DOOR NEEDS LOCK. $0 $0 Mar 16, 2017
Aug 23, 2012 34979635N RESOLVE CLASS - 2 OCCUPANCY CONTRARY TO THAT ALLOWED BY THE CERTIFICATE OF OCCUPANCY. ILLEGAL OCCUPANCY NOTED:BLDG OCCUPIED AS TRANSIEN... $0 $0 Feb 11, 2013
Aug 23, 2012 34980599N RESOLVE CLASS - 1 1021.3:FAILURE TO COMPLY WITH OPENING PROTECTIVE IN HORIZONTAL EXITS. NOTED:WIDE OPEN SECURED IN OPEN POSITION FIRE E... $1,600 $0 Oct 11, 2012
Jan 30, 2012 38220469Z RESOLVE CLASS - 1 72X10,16Q03,16J01,18M07,17H11,17D06,17M07,60X10,56Y13,59Y02,42G11,45O02,42M07,77M07,70M07. *CEASE USE ITEMS. 72X- INO... $1,000 $0 Mar 15, 2012
Jun 15, 2011 38216405H RESOLVE CLASS - 2 97J01. 97-DEVICE STALLS IN LEVELING ON 4TH FLOOR. $0 $0 Aug 4, 2011
Feb 5, 2010 34821458L RESOLVE CLASS - 2 SEC. 28-404.1. SUPERVISION OR USE OF RIGGING EQUIPMENT W/O A RIGGER'S LICENSE. PLATFORM OFF C-HOOKS AT REAR OF BLDG (... $800 $0 Jun 10, 2010
Jul 13, 2005 32048114J RESOLVE Non-Hazardous 36/50. 50-PIPE THE RELIEF VALVE DISCHARGE DOWN TO A SAFE POINT. $0 $0 Apr 6, 2006
Jul 13, 2005 32048115L RESOLVE Non-Hazardous 36/50. 50 PIPE THE RELEIF VALVE DISCHARGE DOWN TO A SAFE POINT. $0 $0 Apr 6, 2006
Jul 13, 2005 32048113H RESOLVE Non-Hazardous 36/50. 50-PIPE SAFETY VALVE DISCHARGE DOWN TO A SAFE POINT. $0 $0 Apr 6, 2006
Jul 13, 2005 32048112X RESOLVE Non-Hazardous 50A. 50A) PIPE SAFETY VALVE DOWN TO A SAFE POINT. $180 $0 Feb 9, 2006
Apr 19, 2004 38145871J RESOLVE Non-Hazardous 56D06/39O02/55Y13/44O02/34D06/16B11/38O02/38L10/03M07/28B01 (56-D-06) PROPERLY SECURE MOTOR WIRE TO MOTOR (PROTECT) (... $0 $0 Jun 3, 2004
Jun 24, 2002 38124035L RESOLVE Non-Hazardous 73U07/03H10/05F11/09I10/30O02/20B10/03D07/28E11// 73- USE CORRECT NYC ID SEE ABOVE ON TAGS 03-RENEW OR REPLACE CAB SA... $180 $0 Dec 5, 2002
Apr 2, 2002 38122608K RESOLVE Non-Hazardous 46D6, 35D6, 40M14, 36W6, 22D6, 2L11, 3D6. 46 GUARD 35 SMOKE HOLE GRATE 3 FIRE SERVICE PLATE. $180 $0 May 23, 2002
Jul 12, 2000 38099072Z RESOLVE Non-Hazardous 44D6,36T7,50F11,5E1,9B7,74B7,29I11,50B16,54B16,44B16.44D-BOLT STAND TOFL AND BOLT GENERATOR TO STAND.50F-MACHINE YEAR... $0 $0 Aug 31, 2000
Jun 14, 1991 38013463X RESOLVE Non-Hazardous 73#,50Y,73O,22D,11Q,09M,17Q,73#PERFORM 5YEAR TEST,PROPERLY TAG DEVICE,AND FILE ELV3 FORM $150 $0 Sep 26, 1991