ECB violations
346-350 West 88 Street, Manhattan • Block 01249 • Lot 0054
34 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Jan 15, 2026 | 39174136M | RESOLVE | CLASS - 1 | OBSERVED ON THE 8TH FLOOR UPRIGHT SPRINKLER HEADS NOT INSTALLED CORRECTLY. SPRINKLER HEADS THROUGHOUT THE BUILDING AR... | $2,530 | $2,530 | Apr 13, 2027 |
| Sep 26, 2024 | 39125883P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. BLACK GATE LEADING TO STREET DEFECTIVE. ALSO OBSERVED NO SELF ... | $0 | $0 | Dec 5, 2024 |
| Sep 26, 2024 | 39125882N | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $2,500 | $0 | May 15, 2025 |
| Sep 26, 2024 | 39125884R | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING. OBSERVED NON SELF CLOSING DOORS ON ROOF AND BASEMENT LEVEL. POTENTIAL FIRE HAZARD, REPAIR... | $0 | $0 | Dec 5, 2024 |
| Sep 17, 2024 | 39125077K | RESOLVE | CLASS - 1 | I OBSERVED A NEW ELECTRICAL PANEL, SUB-FEEDERS, AND CONDUIT FROM THE MDP FOR THE INSTALLATION OF BRANCH CIRCUIT WIRIN... | $4,800 | $0 | Nov 21, 2024 |
| Sep 17, 2024 | 39125078M | RESOLVE | CLASS - 1 | I OBSERVED THE INSTALLATION OF CONDUITS, SUBFEEDER, BRANCH CIRCUIT WIRING, ELECTRICAL PANEL, BREAKERS, JUNCTION BOXES... | $800 | $0 | Nov 21, 2024 |
| Sep 17, 2024 | 39125076Z | RESOLVE | CLASS - 2 | I OBSERVED IN THE EMPLOYEE BREAK AREA AND THE BOILER ROOM THE FAILURE TO INSTALL/ PROVIDE GFCI PROTECTION AS REQUIRED... | $1,200 | $0 | Nov 21, 2024 |
| Sep 6, 2024 | 35686258Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN EXTERIOR BUILDING FACADE AND APPURTENANCES. NOTED:OBSERVED THERE ARE SPALLING CONCRETE AT EXP 1(N... | $620 | $0 | Nov 14, 2024 |
| Aug 20, 2024 | 39122542N | RESOLVE | CLASS - 1 | OBSERVED IN THE GAS METER ROOM ADJACENT FROM THE ELECTRICAL METER ROOM LOCATED IN THE BASEMENT/CELLAR NO FIRE STOPPIN... | $625 | $0 | Oct 24, 2024 |
| Aug 20, 2024 | 39122543P | RESOLVE | CLASS - 2 | OBSERVED IN THE GAS METER ROOM LOCATED IN THE ROOM ADJACENT FROM THE ELECTRICAL ROOM NO VENTILATION NOTED. AS PER E 4... | $0 | $0 | Oct 24, 2024 |
| Jul 31, 2024 | 35683951Z | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN EXTERIOR BUILDING FACADE AND APPURTENANCES. NOTES:HAZARDOUS CONDITIONS OBSERVED (1)AT EXPOSURE #1... | $2,500 | $0 | May 8, 2025 |
| Mar 21, 2024 | 35682437L | RESOLVE | CLASS - 1 | UNLAWFUL ACTS.FAILURE TO COMPLY WITH COMMISSIONER'S ORDER.NOTE:AT THE TIME OF INSPECTION OBSERVED RESPONDENT FAILURE ... | $2,500 | $0 | Oct 2, 2024 |
| Dec 19, 2023 | 35674548Y | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN EXTERIOR BUILDING FACADE AND APPURTENANCES. NOTED AT TIME OF INSPECTION EAST ELEVATION EXPOSURE #... | $6,250 | $6,250 | Feb 22, 2024 |
| Jun 24, 2019 | 35365568M | RESOLVE | CLASS - 2 | REMOVAL OF SAFETY MEASURES/SIDEWALK SHED WITHOUT DEPARTMENTS APPROVAL NOTE AT TIME OF INSPECTION BUILDING FACADE WAS ... | $625 | $0 | Aug 22, 2019 |
| May 24, 2019 | 35365670Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN EXTERIOR BUILDING FACADE AND APPURTENANCE. ROOF LEVEL OBSERVE COPING STONE ON GAS ELEVATIONS SPAL... | $0 | $0 | Jul 25, 2019 |
| Aug 1, 2018 | 37012203Z | RESOLVE | CLASS - 2 | FAILURE TO FILE ACCEPTABLE AMENDED CYCLE 8A REPORT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRIBED IN INITIAL FA... | $1,250 | $0 | Apr 4, 2019 |
| Mar 12, 2014 | 35073959P | RESOLVE | CLASS - 1 | 28-301.FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.DEFECTS NOTED1HOLE IN CEILING WHERE GAS DRYER EXHAUST DUCT P... | $400 | $0 | May 8, 2014 |
| Mar 12, 2014 | 35073958N | RESOLVE | CLASS - 1 | 28-301.1 FAILURE TO MAINTAIN IN CODE COMPLIANT MANNER.EXHAUST DISCHARGE MUST BE NO CLOSER THAN 10'FROM BUILDING OPENI... | $400 | $0 | May 8, 2014 |
| May 24, 2013 | 38227475R | RESOLVE | CLASS - 2 | 05L10,52J01. 05- ZONE RESTRICTOR. 52- HOIST CABLES TOO LONG. | $0 | $0 | Jul 11, 2013 |
| Jul 26, 2008 | 34700508J | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG WALL OR APPURTENANCES.DEFECTS NOTED:RUBBLE/BRICK FENCE LOCATED AT REAR OF PREMISES EXPOSURE ... | $0 | $0 | Jan 7, 2010 |
| Apr 28, 2000 | 34206304Y | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN EXTERIOR BUILDING WALLS. NOTED AT NORTH ELEVATION 8 FLOOR SPALLING AND CRACKED STUCCO, AT EAST AN... | $350 | $0 | Jun 16, 2000 |
| Feb 22, 2000 | 34239403K | RESOLVE | Non-Hazardous | FAILURE TO PROVIDE "3"STAIR AND ELEVATOR I.D. SIGNS THROUGHOUT ALL FLS. IN BOTH WINGS.REMEDY:PROVIDE SIGNAGE AS PER L... | $0 | $0 | Apr 13, 2000 |
| Feb 22, 2000 | 34223575K | RESOLVE | Non-Hazardous | FAILURE TO FILE A REPORT OF COMPLIANCE WITH LOCAL LAW 16/84 CERTIFYING TO THE INSTALLATION OF REQUIRED FIRE PROTECTIO... | $0 | $0 | Apr 13, 2000 |
| Aug 9, 1999 | 34155368X | RESOLVE | Non-Hazardous | EORK WITHOUT A PERMIT WORK NOTED METAL STUDS AND SHEET ROCK PARTITION ERECTED IN 5 STORY NORTH WEST SECTION B RM 505 ... | $500 | $0 | Dec 16, 1999 |
| Aug 2, 1999 | 34155366M | RESOLVE | Non-Hazardous | WORK WITHOUT A PERMIT WORK NOTED 6 STY NORTH WEST SECTION RMS B03 CONVERTED TO BATHRM METAL STUD AN DSHEETROCK WALLS ... | $500 | $0 | Dec 16, 1999 |
| Sep 16, 1996 | 34145862M | RESOLVE | Non-Hazardous | FAILURE TO PROVIDE ACESS TO SRO ROOM ON ALL FLOORS AT TIME OF INSPECT-ION TO DETERMINE OMPLIANCE WITH APPROVED WHICH ... | $0 | $0 | Dec 5, 1996 |
| Apr 25, 1996 | 34129913N | RESOLVE | Non-Hazardous | WORK WITHOUT A PERMIT WORK NOTED BATHROOMS INSTALLED IN THE FOLLOWING 1STY ROOMS 120 118 116 117 119 123 REMEDY: OBTA... | $350 | $0 | Aug 8, 1996 |
| Feb 5, 1996 | 34129907R | RESOLVE | Non-Hazardous | WORK WITHOUT A PERMIT WORK NOTED COMPLETE BATHROOMS INSTALLED IN 7STY ROOM 715,6STY ROOM 615,5STY ROOM 519 ROOMS 619 ... | $350 | $0 | May 2, 1996 |
| Jan 26, 1996 | 34132775L | RESOLVE | Non-Hazardous | FAILURE TO PROVIDE APPROVED PLANS AT PREMISES AT TIME OF INSPECTION. LOCATION:ROOMS 319,615,619 AND 715.REMEDY:PROVID... | $0 | $0 | Mar 14, 1996 |
| Jan 26, 1996 | 34133301Y | RESOLVE | Non-Hazardous | WORK WITHOUT A PERMIT.EXPIRED PERMIT.WORK NOTED:INTERIOR REMOVATION FROM FIRST THRU-OUT 8FLR.PERMIT#100849352.ISSUED ... | $0 | $0 | Mar 14, 1996 |
| Jun 7, 1995 | 34124398P | RESOLVE | Non-Hazardous | FAILURE TO PROVIDE APPROVED PLANS AT PREMISES AT TIME OF INSPECTION NOTED CONSTRUCTION WORK ON THE 8TH,5TH,3RD&2ND FL... | $250 | $0 | Aug 10, 1995 |
| Dec 14, 1994 | 34115947Y | RESOLVE | Non-Hazardous | WORK DOES NOT CONFORM TO APPROVED PLANS: NON-CONFORMING WORK NOTED: UNDER ACT#2 100849352 INTERIOR RENOVATION OF #18 ... | $250 | $0 | Mar 23, 1995 |
| Oct 24, 1991 | 38018475X | RESOLVE | Non-Hazardous | 46L | $185 | $0 | Feb 13, 1992 |
| Jan 29, 1991 | 38006939R | RESOLVE | Non-Hazardous | 46L | $0 | $0 | May 30, 1991 |