ECB violations

306 West 94 Street, Manhattan • Block 01252 • Lot 0060

89 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Jul 17, 2026 39196640Z RESOLVE CLASS - 1 VF... CEASE USED..D L M ... 42-X-10...DOOR POSITION MONITORING INOPERATIVE .THIS IS A CONTROLLER FEATURE WHICH ENSURE... $1,250 $1,250 Sep 24, 2026
Apr 14, 2026 39184886K ACTIVE CLASS - 1 ELECTRICAL CLOSET NOT DEDICATED TO ELECTRICAL DISTRIBUTION EQUIPMENT ONLY. OBSERVED IN THE MAIN ELECTRICAL RM THE INS... $1,230 $1,230 May 3, 2027
Apr 22, 2025 39145634M RESOLVE CLASS - 1 CEASE USE OF EASTMOND FST 125 BOILER- GENERATING 300 PPM CO AT FRONT ACCESS PANEL & EXTERNAL CHIMNEY PARTIALLY COLAPS... $2,500 $2,500 Feb 5, 2026
Jan 22, 2025 39136109J RESOLVE CLASS - 1 CEASE USE ITEM: DOOR LOCK MONITORING INOPERATIVE. . REMEDY: RESTORE TO SERVICE IMMEDIATELY AND CALL THE DOB ELEVATOR ... $1,250 $0 Sep 25, 2025
Jan 21, 2025 39136058Z RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: LACK OF EMERGENCY LIGHTING FOR EXITS, EXIT DISCHARGES AND PUBL... $2,500 $0 Oct 23, 2025
Jul 24, 2024 39119786M RESOLVE CLASS - 2 UNLAWFUL ACTS: FAILURE TO COMPLY WITH COMMISSIONER'S ORDER AS STATED IN ECB# 39107116P ISSUED ON 02/27/2024 AND FILE ... $1,250 $1,250 Sep 11, 2025
Feb 27, 2024 39107116P RESOLVE CLASS - 1 EMERGENCY EXIT STEEL STAIRCASE IS SEVERELY RUSTED WITH BROKEN TREADS. THE BROKEN STAIRCASE CAN NOT BE USED AS AN EXIT... $1,250 $0 Jun 6, 2024
Feb 27, 2024 39107115N RESOLVE CLASS - 2 HOLE PENTRATION-BOX CUTOUT, AND UNFINISHED WALLS IN THE SPRINKLER/ELECTRICAL MECHANICAL ROOM CELLAR LEVEL., PROVIDE/M... $625 $0 Jun 6, 2024
Dec 13, 2023 35667044P RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED AT EXPOSURE 1 FIRE ESCAPE DROP DOWN LADDER BLOCKED BY... $1,250 $0 Feb 22, 2024
Dec 13, 2023 35667046Z RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED IN THE BASEMENT/CELLAR 2 HOLE PENETRATION IN CEILING.... $1,250 $0 Feb 22, 2024
Sep 22, 2022 39070641R RESOLVE CLASS - 2 AT CELLAR LEVEL, EXPOSURE # 1 & #2, EXIT DOORS DO NOT CLOSE PROPERLY WHEN INSPECTED., REPAIR/REPLACE DOOR $0 $0 Nov 10, 2022
Sep 22, 2022 39070646X RESOLVE CLASS - 2 I OBSERVED IN THE BASEMENT MAINTENANCE STORAGE ROOM CONDUITS AND ARMORED CABLING NOT SUPPORTED AS REQUIRED., PROPERLY... $0 $0 Nov 10, 2022
Sep 22, 2022 39070639H RESOLVE CLASS - 2 AT 5TH FL, 6TH FL & 7TH FL, EXISTING EMERGENCY LIGHT DO NOT WORK WHEN TESTED., REPAIR/REPLACE LIGHTING $0 $0 Nov 10, 2022
Sep 22, 2022 39070640P RESOLVE CLASS - 2 AT CELLAR LEVEL, UTILITIES ROOM/ STORAGE ROOMS , SEVERAL OPENING DUE PIPES PENETRATION/ CEILING DAMAGE WITHOUT FIRE S... $0 $0 Nov 10, 2022
Sep 22, 2022 39070635K RESOLVE CLASS - 2 OBSERVED NO BALL DRIP ON THE SPRINKLER SERVICE, IN ITS PLACE THE RESPONDENT HAS A HOSE VALVE. AS PER 2014 BUILDING CO... $0 $0 Nov 10, 2022
Sep 22, 2022 39070645Y RESOLVE CLASS - 3 I OBSERVED ON ALL FLOORS THE BRANCH CIRCUITS IN THE HALLWAY ELECTRICAL PANELS NOT LABELED OR IDENTIFIED AS REQUIRED F... $0 $0 Nov 10, 2022
Sep 22, 2022 39070632P RESOLVE CLASS - 2 AS PER ONE FEDERAL FST-125 BOILER; AIR PROVING SWITCH DEFECTIVE-GAS PIPING AT BURNER UNDER GAS TRAIN NOT SUPPORTED-RE... $0 $0 Nov 10, 2022
Sep 22, 2022 39070644M RESOLVE CLASS - 1 I OBSERVED IN THE BASEMENT SECURITY OFFICE AND THE EMPLOYEE ROOM OPPOSITE THE LAUNDRY ROOM THE IMPROPER TERMINATION A... $4,000 $0 Nov 10, 2022
Jun 27, 2022 39064793P RESOLVE CLASS - 2 2/X/10 OUT SIDE COMM INOPERATIVE REPAIR,57/BB/7 FIRE EXTINGUISHER TAG EXPIRED PROVIDE,70/Z/2 WATER IN PIT SEAL CLEAN. $0 $0 Oct 6, 2022
May 24, 2022 39062723K RESOLVE CLASS - 2 EXISTING EMERGENCY LIGHTS WITH BACK-UP BATTERY AT 6TH FL WERE NOT OPERATIONAL WHEN TESTED., REPAIR/REPLACE LIGHTING $1,562 $0 Jul 14, 2022
May 24, 2022 39062724M RESOLVE CLASS - 2 AT BACKYARD AND EXIT CORRIDOR AROUND THE BUILDING, SEVERAL OPENINGS WITHOUT THE CORRECT PROTECTION TO AVOID ENTRY OF ... $1,562 $0 Jul 14, 2022
Dec 14, 2021 39052789Y RESOLVE CLASS - 1 FOUND DOOR LOCK MONITORING (DLM) IS NOT WORKING. CEASE USED. REPAIR AND ADJUST. RE-INSPECTION IS REQUIRED. BULB OF CA... $1,250 $0 Feb 3, 2022
Sep 3, 2021 39046999L RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: AT TIME OF INSPECTION OBSERVED THE STAIRS LEADING TO THE OUTER... $0 $0 Oct 21, 2021
Sep 3, 2021 39047000L RESOLVE CLASS - 2 WORK DOES NOT CONFORM TO APPROVED CONSTRUCTION DOCUMENTS AND/OR APPROVED AMENDMENTS: AT TIME OF INSPECTION OBSERVED A... $1,250 $0 Aug 4, 2022
Sep 3, 2021 39047001N RESOLVE CLASS - 2 ALTERED/CHANGED BUILDING OCCUPIED WITHOUT A VALID CERTIFICATE OF OCCUPANCY AS PER 28-118.3.1 - 28-118.3.2: AT TIME OF... $0 $0 Aug 4, 2022
Aug 3, 2021 39045420Z RESOLVE CLASS - 2 AT THE ROOF LEVEL, STAIR CASE, CRACKS IN BRICKS & MORTAR FALLING OUT ABOVE ROOF EXIT DOOR., MAINTAIN EXTERIOR BUILDIN... $625 $0 Jan 27, 2022
Aug 3, 2021 39045421K RESOLVE CLASS - 2 AT CELLAR LEVEL, GAS METER ROOM HAS NO FIRE STOPPING PROVIDED, HOLES WERE FILLED WITH FIREBLOCK FOAM WHICH IS FLAMMAB... $625 $0 Jan 27, 2022
May 27, 2021 39041866P RESOLVE CLASS - 1 FOUND DLM IS NOT WORKING. REPAIR. LABEL OF ONE FUSE IN CONTROLLER AT MACHINE ROOM UNREADABLE. REPLACE. CAT1 TAG IN MA... $1,250 $0 Jul 15, 2021
May 30, 2019 35434228M RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED ON 5/20/2019 AT ABOVE ADDRESS NO VENTILATION IN THE G... $312 $0 Oct 10, 2019
Mar 23, 2017 35253653K RESOLVE CLASS - 2 FAILURE TO MAINTAIN EXTERIOR BLDG WALLS & APPURTENANCES. AT TIME OF INSPECTION I OBSERVED ON EXP#1 NORTH ELEVATION SP... $250 $0 Aug 3, 2017
Nov 16, 2016 35203500Y RESOLVE CLASS - 1 OCCUPANCY CONTRARY TO THAT ALLOWED BY C OF O#31742 INDICATES PREMISES LEGALLY APPROVED MULTI DWELLING CLASS'A'. ILLEG... $2,400 $0 Apr 20, 2017
Nov 16, 2016 35203449H RESOLVE CLASS - 1 WORK W/O A PERMIT. NOTED: AT CELLAR LEVEL ERECTED FULL HEIGHT PARTITIONS CREATING ROOMS INSTALLED WATER & WASTE LINES... $0 $0 Apr 20, 2017
Nov 16, 2016 35203448X RESOLVE CLASS - 1 ALTERED/CHANGED BLDG OCCUPIED W/O A VALID C OF O AS PER 28-118.3.1;28-118.3.2. NOTED: ALT-1 #110214982 APPROVED 3-2-1... $1,000 $0 Apr 20, 2017
Nov 16, 2016 35203501X RESOLVE CLASS - 2 SEC. 12-10;73-36 CELLAR LEVEL CONVERTED/OCCUPIED PHYSICAL CULTURE ESTABLISHMENT(GYM/FITNESS CENTER)W/O BSA APPROVAL. ... $800 $0 Apr 20, 2017
Dec 22, 2014 36026842X RESOLVE CLASS - 2 FAILURE TO FILE AN ACCEPTABLE CYCLE 7 TECHNICAL REPORT IN COMPLIANCE WITH CODE PROVISIONS: PERIODIC INSPECTION OF EXT... $800 $0 Jun 25, 2015
Nov 8, 2013 35024117H RESOLVE CLASS - 2 FAILURE TO MAINTAIN EXTERIOR BLDGING NORTH ELEVATION EXPOSURE #1 OBSERVE BLOCKS OF WOOD IMPROPERLY INSTALL UNDER A/C ... $2,500 $0 Dec 26, 2013
Apr 2, 2013 35007055R RESOLVE CLASS - 1 SEC. 715 FAILURE TO COMPLY W/OPENING PROTECTIVES. NOTED EXIT DOORS WHICH SERVING FIRE SEPARATION BETWEEN CORRIDOR & E... $1,600 $0 Oct 10, 2013
Apr 2, 2013 35007056Z RESOLVE CLASS - 2 OCCUPANCY CONTRARY TO THAT ALLOWED BY BLDGS DEPT RECORDS. ILLEGAL OCCUPANCY NOTED CONVERTED CELLAR APPROX 50% IN TO O... $3,000 $0 Oct 10, 2013
Jul 5, 2012 34980316Y RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDINGS IN CODE COMPLIANT MANNER. FAILURE TO PROVIDE NUMBER OF REQUIRED MEANS OF EGRESS FOR EVE... $0 $0 Dec 20, 2012
Jul 5, 2012 34980317X RESOLVE CLASS - 1 715:FAILURE TO COMPLY WITH OPENING PROTECTIVES. NOTED:EXIT DOOR WHICH SERVING (FINE)SEPARATION BETWEEN CORRIDOR & STA... $1,600 $0 Dec 20, 2012
Jul 5, 2012 34980318H RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING WALLS ON APPURTENANCES. HAVING ACCUMULATION OF CONSTRUCTION ORGANIC DEBRIS FURNITURE ETC... $1,000 $0 Dec 20, 2012
Jul 5, 2012 34980314K RESOLVE CLASS - 2 OCCUPANCY CONTRARY TO THAT ALLOWED BY BUILDINGS DEPARTMENT RECORDS ILLEGAL OCCUPANCY NOTED;APT 201 ILLEGALLY CONVERTE... $0 $0 Aug 23, 2012
Jul 5, 2012 34980315M RESOLVE CLASS - 2 ILLEGAL USE IN RESIDENTIAL DISTRICT. ILLEGAL USE NOTED:APT#201 ILLEGALLY CONVERTED INTO TRANSIENT USE IN R8 GENERAL R... $0 $0 Aug 23, 2012
Aug 8, 2011 34915635K RESOLVE CLASS - 3 NOTED THE HOTEL HAS SRO TENANTS SINGLE ROOM OCCUPANCY REFERS THE HOTEL HAS SRO TENANTS SINGLE ROOM OCCUPANCY REFERS T... $0 $0 Jan 17, 2012
Jan 27, 2010 36011952P RESOLVE CLASS - 2 FAILURE TO FILE AN ARCHITECT ENGINEER REPORT CERTIFYING EXIT DIRECTIONAL SIGNS ARE CONNECTED TO EMERGENCY POWER SOURC... $800 $0 Apr 7, 2011
Nov 16, 2009 34754400L RESOLVE CLASS - 2 ILLEGAL USE IN A RESIDENTIAL DISTRICT NOTE:LOCATED IN & R8 ZONING DISTRICT EXIST AN ILLEGAL "PRIMARY TRANSIENT USE HO... $800 $0 Mar 10, 2011
Nov 16, 2009 34754397J RESOLVE CLASS - 1 SEC. BC1008.4.3. FAILURE TO MEET EXIT REQUIREMENTS FROM FLOORS 1-7 OF THIS "PRIMARY TRANSIENT HOTEL USE" ON NORTH & S... $0 $0 Jun 30, 2011
Nov 16, 2009 34754396H RESOLVE CLASS - 1 SEC. BC1016.2 FAILURE TO COMPLY W/MIN CORRIDOR WIDTH AT 7FL SOUTH SIDEEXIST A 28" CORRIDOR LEADING TO A DOUBLE HUNG W... $1,600 $0 Jun 30, 2011
Nov 16, 2009 34754398L RESOLVE CLASS - 1 SEC. BC1009.3.1. FAILURE TO COMPLY W/DIMENSIONAL UNIFORMITY OF VERTICAL EXIT STAIRS.NOTE:STAIRWAY "A" EXIT W/VARIOUS ... $800 $0 Jun 30, 2011
Nov 16, 2009 34754399N RESOLVE CLASS - 1 FAILURE TO COMPLY W/HANDRAIL GRASP ABILITY. NOTE:FROM 1 - 7TH FL THE HANDRAIL CLEARANCE DOES NOT CONFORM TO BC 1009.1... $1,600 $0 Mar 10, 2011