ECB violations
56 West 47 Street, Manhattan • Block 01262 • Lot 0009
81 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Aug 11, 2026 | 39200134P | ACTIVE | CLASS - 1 | CLASS 1 CEASE USE: DOOR ZONE RESTRICTOR DEVICE FOUND INOPERATIVE AS PER CODE ASME A17.1/CSA B44 - SECTION 2.26.5. ELE... | $1,250 | $1,250 | Oct 15, 2026 |
| Aug 11, 2026 | 39200133N | ACTIVE | CLASS - 1 | CLASS 1 C/U: CAR OPERATING PANEL UNLOCKED AND CAN BE OPENED, EXPOSING LIVE INTERNAL COMPONENTS AND WIRING, CREATING A... | $1,250 | $1,250 | Oct 15, 2026 |
| Aug 3, 2026 | 39198917L | ACTIVE | CLASS - 2 | FAILURE TO SUBMIT CERTIFICATE OF CORRECTION OF VIOLATION #39121700P ISSUED ON 08-12-2024 FOR PERFORMED UNLICENSED ELE... | $1,250 | $1,250 | Oct 8, 2026 |
| Aug 3, 2026 | 39198913Y | ACTIVE | CLASS - 1 | FAILURE TO SUBMIT CERTIFICATE OF CORRECTION OF VIOLATION #39121612P ISSUED ON 08-12-2024 FOR FAILURE TO MAINTAIN BUIL... | $6,250 | $6,250 | Oct 8, 2026 |
| Aug 3, 2026 | 39198912M | ACTIVE | CLASS - 2 | FAILURE TO SUBMIT CERTIFICATE OF CORRECTION OF VIOLATION #39121695J ISSUED ON 08-12-2024 FOR ELECTRICAL CLOSET NOT DE... | $1,250 | $1,250 | Oct 8, 2026 |
| Aug 3, 2026 | 39198915H | ACTIVE | CLASS - 2 | FAILURE TO SUBMIT CERTIFICATE OF CORRECTION OF VIOLATION #39121697N ISSUED ON 08-12-2024 FOR UNAPPROVED/UNSAFE/UNSUIT... | $1,250 | $1,250 | Oct 8, 2026 |
| Aug 3, 2026 | 39198914X | ACTIVE | CLASS - 1 | AT TIME OF INSPECTION OBSERVED MANY HOLES PENETRATIONS WITH NO FIRE STOPPING CREATING CHIMNEY AFFECT AND AID FIRE AND... | $6,250 | $6,250 | Oct 8, 2026 |
| Aug 3, 2026 | 39198916J | ACTIVE | CLASS - 1 | AT TIME OF INSPECTION OBSERVED WATER METER JUMPER HANGING NOT CONNECTED TO MAINTAIN CONTINUITY OF GROUNDING SYSTEM AL... | $12,000 | $12,000 | Oct 8, 2026 |
| Aug 3, 2026 | 39198911K | ACTIVE | CLASS - 1 | FAILURE TO SUBMIT CERTIFICATE OF CORRECTION OF VIOLATION #39121610L ISSUED ON 08-12-2024 FOR WORK WITHOUT A PERMIT., ... | $2,500 | $2,500 | Oct 8, 2026 |
| Jul 28, 2026 | 39197976R | ACTIVE | CLASS - 2 | VF... HOIST MACHINE BRAKE MAINTENANCE TAG EXPIRED PROVIDE...8.6.4.6... MAINTENANCE LOG UPDATE MISSING PROVIDE.. 8.6.1... | $625 | $625 | Oct 1, 2026 |
| Jul 28, 2026 | 39197977Z | ACTIVE | CLASS - 1 | VF... CEASE USED...D L M INOPERATIVE..42-X-10.. DOOR POSITION MONITORING INOPERATIVE .THIS IS A CONTROLLER FEATURE WH... | $1,250 | $1,250 | Oct 1, 2026 |
| Jul 24, 2026 | 39557024X | ACTIVE | CLASS - 2 | NOTE: AT TIME OF INSPECTION, I OBSERVED SIDEWALK SHED ERECTED AT EXPOURES#1 WITH MISSING 20 FEET EXTENSION AT (57 WES... | $2,400 | $2,400 | Oct 1, 2026 |
| Jul 14, 2026 | 39196089X | ACTIVE | CLASS - 1 | CLASS 1 C/U: BRAKE SWITCH MONITOR INOPERATIVE - THE SWITCHES DISABLED AS PER ASME A17.1 2.26.12, WHICH REQUIRES OPERA... | $1,250 | $1,250 | Sep 17, 2026 |
| Apr 20, 2026 | 37036543L | ACTIVE | CLASS - 2 | FAILURE TO FILE ACCEPTABLE AMENDED CYCLE 8C REPORT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRIBED IN INITIAL FA... | $3,155 | $3,155 | Jul 23, 2026 |
| Oct 1, 2025 | 39161973R | ACTIVE | CLASS - 1 | CLASS 1 CEASE USE ITEMS: 1)DOOR ZONE RESTRICTOR INOPERATIVE. 2)DLM INOPERATIVE. THESE ARE THE SAFETY FEATURES WHAT EN... | $1,250 | $1,250 | Jan 15, 2026 |
| Jul 28, 2025 | 39155177P | ACTIVE | CLASS - 2 | PROVIDE THE OVERHEAD DOOR TO BE SELF LOCKING AND CLOSING. | $3,125 | $3,125 | Sep 29, 2026 |
| Jul 28, 2025 | 39155178R | ACTIVE | CLASS - 1 | CEASE USE ITEM: BRAKE SHOES HAVE EXCESSIVE GAP AND NEED TO BE CORRE CTED. REMEDY: TO RESTORE SERVICE, EMAIL THE D.O.B... | $6,250 | $6,250 | Oct 20, 2026 |
| Jul 28, 2025 | 39155235Y | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $12,500 | $12,500 | Sep 29, 2026 |
| Jul 28, 2025 | 39155179Z | ACTIVE | CLASS - 1 | CEASE USE ITEM: DOOR ZONE RESTRICTOR INOPERATIVE. THIS IS A SAFETY FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY: TO... | $6,250 | $6,250 | Sep 29, 2026 |
| Jul 28, 2025 | 39155085H | ACTIVE | CLASS - 2 | I FOUND A FEDERAL FST70 BOILER WITH OIL PUMP ON ALL THE TIME/AIR FAN PROOFING NOT PROPERLY/MISSING DAWGS AND NUTS ON ... | $6,250 | $6,250 | Sep 29, 2026 |
| Jul 28, 2025 | 39155222P | ACTIVE | CLASS - 2 | OBSERVED IN THE BASEMENT INCORRECT SPRINKLER HEADS INSTALLED AND ONE SPRINKLER HEAD DAMAGED. MULTIPLE HEADS THROUGHOU... | $6,250 | $6,250 | Sep 29, 2026 |
| Jul 28, 2025 | 39155234M | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED MISSING DOORS ON ELECTRICAL /MECHANICAL ROOM DOORS. D... | $6,250 | $6,250 | Oct 20, 2026 |
| Apr 8, 2025 | 37034612R | ACTIVE | CLASS - 2 | FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 9C REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WA... | $10,000 | $10,000 | Jul 3, 2025 |
| Dec 10, 2024 | 35689304J | RESOLVE | CLASS - 2 | FAILURE TO MAINTTAIN EXTERIOR BUILDING FACADE AND APPURTENANCES. OBSERVED AT EXPOSURE 1, SOUTH ELEVATION ON 46TH STRE... | $0 | $0 | Feb 13, 2025 |
| Aug 12, 2024 | 39121699R | ACTIVE | CLASS - 1 | I OBSERVED IN THE WATER METER ROOM, THE WATER METER JUMPER HANGING AND NOT CONNECTED AS REQUIRED TO MAINTAIN CONTINUI... | $4,800 | $4,800 | Dec 5, 2024 |
| Aug 12, 2024 | 39121695J | ACTIVE | CLASS - 1 | I OBSERVED THE ELECTRICAL CLOSETS ON FLOORS 3, 6, 9, &12 NOT DEDICATED TO ELECTRICAL DISTRIBUTION EQUIPMENT DUE TO TH... | $1,200 | $1,200 | May 23, 2025 |
| Aug 12, 2024 | 39121697N | ACTIVE | CLASS - 1 | I OBSERVED IN THE BASEMENT THE BOILER ROOM DISCONNECT MADE INACCESSIBLE DUE TO METAL SUPPORT BEAM FOR NEWLY ERECTED S... | $1,600 | $1,600 | May 23, 2025 |
| Aug 12, 2024 | 39121698P | ACTIVE | CLASS - 2 | I OBSERVED ON ALL FLOORS THE ELECTRICAL CLOSETS WITHOUT PROPER ILLUMINATION AS PER EC CODE 110.26 THE ILLUMINATION SH... | $800 | $800 | May 23, 2025 |
| Aug 12, 2024 | 39121704M | ACTIVE | CLASS - 2 | I OBSERVED IN STAIRWAY"D" THE INSTALLATION OF A CIRCUIT BREAKER PANEL WITH THE OVERCURRENT DEVICES INSTALL ABOVE 6' 7... | $800 | $800 | May 23, 2025 |
| Aug 12, 2024 | 39121612P | ACTIVE | CLASS - 1 | OBSERVED NO FRESH AIR VENTILATION IN THE GAS METER ROOM LOCATED IN THE BASEMENT/CELLAR. AS PER E4 OF THE FUEL GAS COD... | $1,250 | $1,250 | Aug 14, 2025 |
| Aug 12, 2024 | 39121701R | RESOLVE | CLASS - 1 | I OBSERVED ON ALL FLOORS IN BUILDINGS 1 AND 2 THE FAILURE TO INSTALL OR PROVIDE TAMPER-RESISTANT/PROOF OUTLETS IN THE... | $0 | $0 | Dec 5, 2024 |
| Aug 12, 2024 | 39121703K | RESOLVE | CLASS - 1 | I OBSERVED ON ALL FLOORS THE INSTALLATION OF JUNCTION BOXES, FLEXIBLE METAL RACEWAYS TO RELOCATE BRANCH CIRCUIT WIRIN... | $0 | $0 | Dec 5, 2024 |
| Aug 12, 2024 | 39121611N | ACTIVE | CLASS - 2 | OBSERVED PAINTED SPRINKLER HEADS THROUGHOUT BUILDING AS WELL AS SPRINKLER CAPS THAT ARE PAINTED AT LOBBY. AS PER 102.... | $625 | $625 | May 8, 2025 |
| Aug 12, 2024 | 39121610L | ACTIVE | CLASS - 1 | OBSERVED NEWLY INSTALLED PIPING TO GAS METERS LOCATED AT BASEMENT/CELLAR LEVEL. NP PERMITS ON FILE AT THE DOB FOR THI... | $2,500 | $0 | Aug 14, 2025 |
| Aug 12, 2024 | 39121696L | ACTIVE | CLASS - 2 | I OBSERVED IN THE BASEMENT BOILER ROOM AND IN THE ELEVATOR "E" MOTOR ROOM CONVENIENCE RECEPTACLES NOT OF THE GFCI TYP... | $2,400 | $2,400 | Dec 5, 2024 |
| Aug 12, 2024 | 39121700P | ACTIVE | CLASS - 1 | I OBSERVED THE INSTALLATION OF ELECTRIC PANELS, BRANCH CIRCUIT WIRING, CIRCUIT BREAKER PANELS, RACEWAYS, AND OVERCURR... | $4,800 | $4,800 | Dec 5, 2024 |
| Aug 9, 2024 | 39121424H | RESOLVE | CLASS - 1 | BRAKE SWITCHES BYPASSED. THIS IS A SAFETY FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY: TO RESTORE SERVICE, CALL TH... | $1,250 | $1,250 | Dec 5, 2024 |
| Aug 9, 2024 | 39121425J | ACTIVE | CLASS - 2 | SECURE ROPE INSIDE WINDING DRUM FROM MOVEMENT. CLEAN AND REPAIR OIL LEAK FROM HOIST MACHINE. PROVIDE AN UPDATED MAINT... | $625 | $625 | Dec 5, 2024 |
| Jun 28, 2024 | 39117973Z | ACTIVE | CLASS - 2 | OBSERVED ON THE GROUND FLOOR IN BOOTH 3 IN NEW YORK ONE JEWELRY REFINERY INC WATER DRIPPING FROM THE SECOND FLOOR INT... | $625 | $625 | Sep 11, 2025 |
| Jan 16, 2024 | 37026510X | ACTIVE | CLASS - 2 | FAILURE TO FILE ACCEPTABLE AMENDED CYCLE 8C REPORT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRIBED IN INITIAL FA... | $1,250 | $1,250 | Apr 25, 2024 |
| Jun 29, 2022 | 35651541J | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING FACADE AND APPURTENANCES. NOTE:OBSERVED AT EXPOSURE#1(SOUTH) MULTIPLE AREAS OF SPALLING ... | $1,250 | $0 | Nov 17, 2022 |
| Apr 26, 2022 | 35651129H | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN EXTERIOR BUILDING FACADE AND APPURTENANCES.NOTED:AT TIME OF INSPECTION WEST ELEVATION EXPOSURE#2 ... | $1,250 | $0 | Dec 8, 2022 |
| Oct 8, 2021 | 37022097N | ACTIVE | CLASS - 2 | FAILURE TO FILE ACCEPTABLE AMENDED CYCLE8C REPORT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRIBED IN INITIAL FAC... | $6,250 | $6,250 | Feb 24, 2022 |
| Sep 1, 2021 | 39046890H | RESOLVE | CLASS - 1 | FOUND EMERGENCY STOP SWITCH INSIDE CAR IS NOT WORKING. CEASE USED. REPAIR/REPLACE THE STOP SWITCH. RE-INSPECTION IS R... | $1,250 | $0 | Mar 10, 2022 |
| Apr 13, 2021 | 39039246L | RESOLVE | CLASS - 2 | GAS PIOLIT REGULATOR MISSING VENT LIMITER+SPRING COVER/OIL TANK SIGN MISSING/OIL PUMP BELT GUARD MISSING/BODY DRAINS ... | $312 | $0 | Aug 19, 2021 |
| Apr 13, 2021 | 39039247N | RESOLVE | CLASS - 2 | FLUE DOOR GASKETS DEFECT/FLUE TO CHIMNEY BASE HAS SOOT/CHIMNEY BASE DOOR DEFECT/SAFETY VALVE BODY DRAIN DISCHARGE PIP... | $312 | $0 | Aug 19, 2021 |
| Jul 10, 2019 | 35254578Y | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY AS NOTED: @TIME OF INSPECTION I OBSERVED ON EXP #4 EAST ELEVATION: SE... | $0 | $0 | Sep 24, 2020 |
| Jul 10, 2019 | 35254577M | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN EXTERIOR BUILDING WALLS AND APPURTENANCES: AS NOTED @TIME OF INSPECTION I OBSEVRED ON EXP #4 EAST... | $2,500 | $0 | Sep 24, 2020 |
| May 25, 2016 | 35159933Y | RESOLVE | CLASS - 1 | UNLAWFUL ACTS. FAILURE TO COMPLY W/ AN ORDER OF THE COMMISSIONER. IN 2/26/2015. A ELECTRICAL VIOLATION WAS ISSUED TO ... | $2,400 | $0 | Jul 14, 2016 |
| Feb 26, 2015 | 35123010L | RESOLVE | CLASS - 1 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT APPARATUS,MATERIALS,DEVICES,APPLIANCES OR WIRING IN USE. THE ENTIRE... | $1,600 | $0 | Apr 16, 2015 |