ECB violations

56 West 47 Street, Manhattan • Block 01262 • Lot 0009

81 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Aug 11, 2026 39200134P ACTIVE CLASS - 1 CLASS 1 CEASE USE: DOOR ZONE RESTRICTOR DEVICE FOUND INOPERATIVE AS PER CODE ASME A17.1/CSA B44 - SECTION 2.26.5. ELE... $1,250 $1,250 Oct 15, 2026
Aug 11, 2026 39200133N ACTIVE CLASS - 1 CLASS 1 C/U: CAR OPERATING PANEL UNLOCKED AND CAN BE OPENED, EXPOSING LIVE INTERNAL COMPONENTS AND WIRING, CREATING A... $1,250 $1,250 Oct 15, 2026
Aug 3, 2026 39198917L ACTIVE CLASS - 2 FAILURE TO SUBMIT CERTIFICATE OF CORRECTION OF VIOLATION #39121700P ISSUED ON 08-12-2024 FOR PERFORMED UNLICENSED ELE... $1,250 $1,250 Oct 8, 2026
Aug 3, 2026 39198913Y ACTIVE CLASS - 1 FAILURE TO SUBMIT CERTIFICATE OF CORRECTION OF VIOLATION #39121612P ISSUED ON 08-12-2024 FOR FAILURE TO MAINTAIN BUIL... $6,250 $6,250 Oct 8, 2026
Aug 3, 2026 39198912M ACTIVE CLASS - 2 FAILURE TO SUBMIT CERTIFICATE OF CORRECTION OF VIOLATION #39121695J ISSUED ON 08-12-2024 FOR ELECTRICAL CLOSET NOT DE... $1,250 $1,250 Oct 8, 2026
Aug 3, 2026 39198915H ACTIVE CLASS - 2 FAILURE TO SUBMIT CERTIFICATE OF CORRECTION OF VIOLATION #39121697N ISSUED ON 08-12-2024 FOR UNAPPROVED/UNSAFE/UNSUIT... $1,250 $1,250 Oct 8, 2026
Aug 3, 2026 39198914X ACTIVE CLASS - 1 AT TIME OF INSPECTION OBSERVED MANY HOLES PENETRATIONS WITH NO FIRE STOPPING CREATING CHIMNEY AFFECT AND AID FIRE AND... $6,250 $6,250 Oct 8, 2026
Aug 3, 2026 39198916J ACTIVE CLASS - 1 AT TIME OF INSPECTION OBSERVED WATER METER JUMPER HANGING NOT CONNECTED TO MAINTAIN CONTINUITY OF GROUNDING SYSTEM AL... $12,000 $12,000 Oct 8, 2026
Aug 3, 2026 39198911K ACTIVE CLASS - 1 FAILURE TO SUBMIT CERTIFICATE OF CORRECTION OF VIOLATION #39121610L ISSUED ON 08-12-2024 FOR WORK WITHOUT A PERMIT., ... $2,500 $2,500 Oct 8, 2026
Jul 28, 2026 39197976R ACTIVE CLASS - 2 VF... HOIST MACHINE BRAKE MAINTENANCE TAG EXPIRED PROVIDE...8.6.4.6... MAINTENANCE LOG UPDATE MISSING PROVIDE.. 8.6.1... $625 $625 Oct 1, 2026
Jul 28, 2026 39197977Z ACTIVE CLASS - 1 VF... CEASE USED...D L M INOPERATIVE..42-X-10.. DOOR POSITION MONITORING INOPERATIVE .THIS IS A CONTROLLER FEATURE WH... $1,250 $1,250 Oct 1, 2026
Jul 24, 2026 39557024X ACTIVE CLASS - 2 NOTE: AT TIME OF INSPECTION, I OBSERVED SIDEWALK SHED ERECTED AT EXPOURES#1 WITH MISSING 20 FEET EXTENSION AT (57 WES... $2,400 $2,400 Oct 1, 2026
Jul 14, 2026 39196089X ACTIVE CLASS - 1 CLASS 1 C/U: BRAKE SWITCH MONITOR INOPERATIVE - THE SWITCHES DISABLED AS PER ASME A17.1 2.26.12, WHICH REQUIRES OPERA... $1,250 $1,250 Sep 17, 2026
Apr 20, 2026 37036543L ACTIVE CLASS - 2 FAILURE TO FILE ACCEPTABLE AMENDED CYCLE 8C REPORT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRIBED IN INITIAL FA... $3,155 $3,155 Jul 23, 2026
Oct 1, 2025 39161973R ACTIVE CLASS - 1 CLASS 1 CEASE USE ITEMS: 1)DOOR ZONE RESTRICTOR INOPERATIVE. 2)DLM INOPERATIVE. THESE ARE THE SAFETY FEATURES WHAT EN... $1,250 $1,250 Jan 15, 2026
Jul 28, 2025 39155177P ACTIVE CLASS - 2 PROVIDE THE OVERHEAD DOOR TO BE SELF LOCKING AND CLOSING. $3,125 $3,125 Sep 29, 2026
Jul 28, 2025 39155178R ACTIVE CLASS - 1 CEASE USE ITEM: BRAKE SHOES HAVE EXCESSIVE GAP AND NEED TO BE CORRE CTED. REMEDY: TO RESTORE SERVICE, EMAIL THE D.O.B... $6,250 $6,250 Oct 20, 2026
Jul 28, 2025 39155235Y ACTIVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... $12,500 $12,500 Sep 29, 2026
Jul 28, 2025 39155179Z ACTIVE CLASS - 1 CEASE USE ITEM: DOOR ZONE RESTRICTOR INOPERATIVE. THIS IS A SAFETY FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY: TO... $6,250 $6,250 Sep 29, 2026
Jul 28, 2025 39155085H ACTIVE CLASS - 2 I FOUND A FEDERAL FST70 BOILER WITH OIL PUMP ON ALL THE TIME/AIR FAN PROOFING NOT PROPERLY/MISSING DAWGS AND NUTS ON ... $6,250 $6,250 Sep 29, 2026
Jul 28, 2025 39155222P ACTIVE CLASS - 2 OBSERVED IN THE BASEMENT INCORRECT SPRINKLER HEADS INSTALLED AND ONE SPRINKLER HEAD DAMAGED. MULTIPLE HEADS THROUGHOU... $6,250 $6,250 Sep 29, 2026
Jul 28, 2025 39155234M ACTIVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED MISSING DOORS ON ELECTRICAL /MECHANICAL ROOM DOORS. D... $6,250 $6,250 Oct 20, 2026
Apr 8, 2025 37034612R ACTIVE CLASS - 2 FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 9C REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WA... $10,000 $10,000 Jul 3, 2025
Dec 10, 2024 35689304J RESOLVE CLASS - 2 FAILURE TO MAINTTAIN EXTERIOR BUILDING FACADE AND APPURTENANCES. OBSERVED AT EXPOSURE 1, SOUTH ELEVATION ON 46TH STRE... $0 $0 Feb 13, 2025
Aug 12, 2024 39121699R ACTIVE CLASS - 1 I OBSERVED IN THE WATER METER ROOM, THE WATER METER JUMPER HANGING AND NOT CONNECTED AS REQUIRED TO MAINTAIN CONTINUI... $4,800 $4,800 Dec 5, 2024
Aug 12, 2024 39121695J ACTIVE CLASS - 1 I OBSERVED THE ELECTRICAL CLOSETS ON FLOORS 3, 6, 9, &12 NOT DEDICATED TO ELECTRICAL DISTRIBUTION EQUIPMENT DUE TO TH... $1,200 $1,200 May 23, 2025
Aug 12, 2024 39121697N ACTIVE CLASS - 1 I OBSERVED IN THE BASEMENT THE BOILER ROOM DISCONNECT MADE INACCESSIBLE DUE TO METAL SUPPORT BEAM FOR NEWLY ERECTED S... $1,600 $1,600 May 23, 2025
Aug 12, 2024 39121698P ACTIVE CLASS - 2 I OBSERVED ON ALL FLOORS THE ELECTRICAL CLOSETS WITHOUT PROPER ILLUMINATION AS PER EC CODE 110.26 THE ILLUMINATION SH... $800 $800 May 23, 2025
Aug 12, 2024 39121704M ACTIVE CLASS - 2 I OBSERVED IN STAIRWAY"D" THE INSTALLATION OF A CIRCUIT BREAKER PANEL WITH THE OVERCURRENT DEVICES INSTALL ABOVE 6' 7... $800 $800 May 23, 2025
Aug 12, 2024 39121612P ACTIVE CLASS - 1 OBSERVED NO FRESH AIR VENTILATION IN THE GAS METER ROOM LOCATED IN THE BASEMENT/CELLAR. AS PER E4 OF THE FUEL GAS COD... $1,250 $1,250 Aug 14, 2025
Aug 12, 2024 39121701R RESOLVE CLASS - 1 I OBSERVED ON ALL FLOORS IN BUILDINGS 1 AND 2 THE FAILURE TO INSTALL OR PROVIDE TAMPER-RESISTANT/PROOF OUTLETS IN THE... $0 $0 Dec 5, 2024
Aug 12, 2024 39121703K RESOLVE CLASS - 1 I OBSERVED ON ALL FLOORS THE INSTALLATION OF JUNCTION BOXES, FLEXIBLE METAL RACEWAYS TO RELOCATE BRANCH CIRCUIT WIRIN... $0 $0 Dec 5, 2024
Aug 12, 2024 39121611N ACTIVE CLASS - 2 OBSERVED PAINTED SPRINKLER HEADS THROUGHOUT BUILDING AS WELL AS SPRINKLER CAPS THAT ARE PAINTED AT LOBBY. AS PER 102.... $625 $625 May 8, 2025
Aug 12, 2024 39121610L ACTIVE CLASS - 1 OBSERVED NEWLY INSTALLED PIPING TO GAS METERS LOCATED AT BASEMENT/CELLAR LEVEL. NP PERMITS ON FILE AT THE DOB FOR THI... $2,500 $0 Aug 14, 2025
Aug 12, 2024 39121696L ACTIVE CLASS - 2 I OBSERVED IN THE BASEMENT BOILER ROOM AND IN THE ELEVATOR "E" MOTOR ROOM CONVENIENCE RECEPTACLES NOT OF THE GFCI TYP... $2,400 $2,400 Dec 5, 2024
Aug 12, 2024 39121700P ACTIVE CLASS - 1 I OBSERVED THE INSTALLATION OF ELECTRIC PANELS, BRANCH CIRCUIT WIRING, CIRCUIT BREAKER PANELS, RACEWAYS, AND OVERCURR... $4,800 $4,800 Dec 5, 2024
Aug 9, 2024 39121424H RESOLVE CLASS - 1 BRAKE SWITCHES BYPASSED. THIS IS A SAFETY FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY: TO RESTORE SERVICE, CALL TH... $1,250 $1,250 Dec 5, 2024
Aug 9, 2024 39121425J ACTIVE CLASS - 2 SECURE ROPE INSIDE WINDING DRUM FROM MOVEMENT. CLEAN AND REPAIR OIL LEAK FROM HOIST MACHINE. PROVIDE AN UPDATED MAINT... $625 $625 Dec 5, 2024
Jun 28, 2024 39117973Z ACTIVE CLASS - 2 OBSERVED ON THE GROUND FLOOR IN BOOTH 3 IN NEW YORK ONE JEWELRY REFINERY INC WATER DRIPPING FROM THE SECOND FLOOR INT... $625 $625 Sep 11, 2025
Jan 16, 2024 37026510X ACTIVE CLASS - 2 FAILURE TO FILE ACCEPTABLE AMENDED CYCLE 8C REPORT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRIBED IN INITIAL FA... $1,250 $1,250 Apr 25, 2024
Jun 29, 2022 35651541J ACTIVE CLASS - 2 FAILURE TO MAINTAIN BUILDING FACADE AND APPURTENANCES. NOTE:OBSERVED AT EXPOSURE#1(SOUTH) MULTIPLE AREAS OF SPALLING ... $1,250 $0 Nov 17, 2022
Apr 26, 2022 35651129H ACTIVE CLASS - 2 FAILURE TO MAINTAIN EXTERIOR BUILDING FACADE AND APPURTENANCES.NOTED:AT TIME OF INSPECTION WEST ELEVATION EXPOSURE#2 ... $1,250 $0 Dec 8, 2022
Oct 8, 2021 37022097N ACTIVE CLASS - 2 FAILURE TO FILE ACCEPTABLE AMENDED CYCLE8C REPORT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRIBED IN INITIAL FAC... $6,250 $6,250 Feb 24, 2022
Sep 1, 2021 39046890H RESOLVE CLASS - 1 FOUND EMERGENCY STOP SWITCH INSIDE CAR IS NOT WORKING. CEASE USED. REPAIR/REPLACE THE STOP SWITCH. RE-INSPECTION IS R... $1,250 $0 Mar 10, 2022
Apr 13, 2021 39039246L RESOLVE CLASS - 2 GAS PIOLIT REGULATOR MISSING VENT LIMITER+SPRING COVER/OIL TANK SIGN MISSING/OIL PUMP BELT GUARD MISSING/BODY DRAINS ... $312 $0 Aug 19, 2021
Apr 13, 2021 39039247N RESOLVE CLASS - 2 FLUE DOOR GASKETS DEFECT/FLUE TO CHIMNEY BASE HAS SOOT/CHIMNEY BASE DOOR DEFECT/SAFETY VALVE BODY DRAIN DISCHARGE PIP... $312 $0 Aug 19, 2021
Jul 10, 2019 35254578Y RESOLVE CLASS - 1 FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY AS NOTED: @TIME OF INSPECTION I OBSERVED ON EXP #4 EAST ELEVATION: SE... $0 $0 Sep 24, 2020
Jul 10, 2019 35254577M RESOLVE CLASS - 1 FAILURE TO MAINTAIN EXTERIOR BUILDING WALLS AND APPURTENANCES: AS NOTED @TIME OF INSPECTION I OBSEVRED ON EXP #4 EAST... $2,500 $0 Sep 24, 2020
May 25, 2016 35159933Y RESOLVE CLASS - 1 UNLAWFUL ACTS. FAILURE TO COMPLY W/ AN ORDER OF THE COMMISSIONER. IN 2/26/2015. A ELECTRICAL VIOLATION WAS ISSUED TO ... $2,400 $0 Jul 14, 2016
Feb 26, 2015 35123010L RESOLVE CLASS - 1 UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT APPARATUS,MATERIALS,DEVICES,APPLIANCES OR WIRING IN USE. THE ENTIRE... $1,600 $0 Apr 16, 2015