ECB violations
1-19 Tudor City Place, Manhattan • Block 01333 • Lot 0023
69 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Mar 18, 2024 | 39109021L | RESOLVE | CLASS - 2 | OBSERVED IN WHY BISCUITS & BATH ANIMAL FACILITY ON THE GROUND FLOOR NO SPRINKLER SYSTEM IN PLACE WHICH CONTRARY TO CO... | $0 | $0 | Sep 9, 2024 |
| Nov 14, 2022 | 39509064Y | RESOLVE | CLASS - 2 | AT THE TIME OF INSPECTION I OBSERVED 8 FT SLEEVE TO BE USED ON THE OUTRIGGER BEAMS NOT COMPLIED WITH MANUFACTURER SPE... | $0 | $0 | Dec 29, 2022 |
| Nov 25, 2019 | 35463203Z | RESOLVE | CLASS - 1 | FAILURE TO MAINATIN DISPLAY ON SITE DOCUMENTS REQUIRED BY CHAPTER 33 AT TIM EOF INSPECTION OF A 26 TSORY BUILDING UND... | $0 | $0 | Dec 9, 2021 |
| Nov 25, 2019 | 35463206Y | RESOLVE | CLASS - 1 | 3314.1=FAILURE TO MIANTAIN SUSPENDED SCAFFOLD IN CODE COMPLIANT AT TIME OF INSPECTION OF A 26 STORY BUILDING UNDER FA... | $0 | $0 | Dec 9, 2021 |
| Nov 25, 2019 | 35463208H | RESOLVE | CLASS - 1 | WORK DOES NOT CONFORM TO P/E/ APPROVED DESIGN DRAWINGS AT TIME OF INSPECTION OF A 26 STORY BUILDINGUNDER FACADE RENOV... | $0 | $0 | Dec 9, 2021 |
| Nov 25, 2019 | 35463207X | RESOLVE | CLASS - 1 | WORK DOES NOT CONFORM TO P.E. APPROVED DEISGN ARMINGS AT TIME OF INSPECTION OF A 26 STORY BUILDING UNDER FACADE RESTO... | $0 | $0 | Dec 9, 2021 |
| Nov 25, 2019 | 35463202R | RESOLVE | CLASS - 1 | WORK DOES NOT COFNORM TO APPROVED CONSTRUCTION DOCUMENST AND OR APPROVED AMENDMENTS AT TIME OF INSEPCTION FO A 26 STO... | $2,500 | $0 | Dec 9, 2021 |
| Nov 25, 2019 | 35463204K | RESOLVE | CLASS - 1 | WORK DOES NOT CON FORM TO APPROVED CONSTRUCTION DOCUMENTS AND OR APPROVED AMENDMENTS AT TIME FO INSPECTION OF A 26 ST... | $2,500 | $0 | Dec 9, 2021 |
| Nov 25, 2019 | 35463205M | RESOLVE | CLASS - 1 | 3314.1=FAILURE TO MAINTAIN SUPPROTED SCAFFOLD IN CODE COMPLIANT AT TIM EOF INSPECTION FO A 26 STORY BUIDLING UNDER FA... | $2,500 | $0 | Dec 9, 2021 |
| Nov 25, 2019 | 35463209J | RESOLVE | CLASS - 1 | WORK DOES NOT CONFORM TO APPOVED CONSTRUCTION DOCUMENTS AND OR APPROVED AMENDMENTS AT TIME FO INSPECTION FO A 26 STOR... | $625 | $0 | Dec 9, 2021 |
| Nov 25, 2019 | 35463210R | RESOLVE | CLASS - 1 | 3301.2=FAILURE TO NSTISTUTE.MAINTAIN SFATEY MEASURES AT TIME OF INSPECTION OF A 26 STORY BUILDING UNDER FACADE RESTOR... | $625 | $0 | Dec 9, 2021 |
| Aug 19, 2019 | 35448224M | RESOLVE | CLASS - 1 | 3301.2:CONTROL ACCESS ZONE NOTE ATIME OF INSPECTION ON A 26 STROY BUILDING ACOVE JOB SITE I OBSERVED OPEN AREA UNPROT... | $0 | $0 | Sep 24, 2020 |
| Aug 19, 2019 | 35452600Z | RESOLVE | CLASS - 1 | 3314.1:SUPPORTED SCAFFOLD DOES NOT MEET BUILDING CODE SPECIFICATIONS TSOP WORK NOTE AT TIME OF INSPECTION ON A 26 STO... | $0 | $0 | Sep 24, 2020 |
| Aug 19, 2019 | 35452602M | RESOLVE | CLASS - 2 | FAILURE TO POST OR DISTRIBUTE NOTICE OF TENANT PROETCTION PLAN NOTE AT TIME OF INSPECTION I OBSERVED NO TENENAT PROET... | $0 | $0 | Sep 24, 2020 |
| Aug 19, 2019 | 35452603Y | RESOLVE | CLASS - 2 | FAILURE TO POST OR DISTRIBUTE SAFE CONSTRUCTION BILL OF RIGHT NOTE:FAILURE TO POST SAFE CONSTRUCTION BILL OF RIGHTS J... | $0 | $0 | Sep 24, 2020 |
| Aug 19, 2019 | 35452604X | RESOLVE | CLASS - 2 | FAILURE TO NOTIFY THE DEPARTMENT PRIOR TO COMMENCEMENT OF WORK THAT REQUIRED TEST PROTECTION PLAN NOTE THE OWNER SHAL... | $0 | $0 | Sep 24, 2020 |
| Aug 19, 2019 | 35448221R | RESOLVE | CLASS - 1 | WORK DOES NOT CONFORM TO APPROVED COMSTRUCTION DOCUMENTS OR APPROVED AMENDMENTS NOTE AT TIME OF MY INSPECTION OF 26 S... | $0 | $0 | Sep 24, 2020 |
| Aug 19, 2019 | 35448222Z | RESOLVE | CLASS - 1 | 3306.9.12.1:HOLES ON THE FLOOR (LONGER THAN 2") NOTE AT TIME OF INSPECTION OF A 26 STROY BUILDING ACTIEV JOB SITE I O... | $0 | $0 | Sep 24, 2020 |
| Aug 19, 2019 | 35452601K | RESOLVE | CLASS - 2 | NO STORAGE ON SHED NOTE AT TIME OF INSPECTION I OBSERVED SITE WALK SHED IN PLACE AT EXPO 1 MAIN ENTRANCE OF THE BUILD... | $2,400 | $0 | Sep 24, 2020 |
| Aug 19, 2019 | 35448223K | RESOLVE | CLASS - 1 | HOUSEKEEPING NOTE AT TIME OF INSPECTION AT A 26 STROY BUILDING ON AN ACTIEV JOB SITE I OBSERVED INADEQUATE HOUSEKEEPI... | $625 | $0 | Sep 24, 2020 |
| Aug 19, 2019 | 35438643H | RESOLVE | CLASS - 2 | PEDESTRIAN PROTECTION DOES NOT MEET CODE SPEFICATION 3307.6.5.3.NOTE AT TIME OF INSPECTION OBSERVED AHEAZY DUTY SIDEW... | $0 | $0 | Sep 24, 2020 |
| Aug 19, 2019 | 35448220P | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN AND INSTITUTE SAFETY MEASURES AND TEMPORARY CONSTRUCTION NOTE AT TIME OF MY INSPECTION AT A 26 TO... | $0 | $0 | Sep 24, 2020 |
| Jul 5, 2016 | 35202226X | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN NOV'S 35159070H;35159446R & 35159447Z ISSUED ON 3-16-16 & TO FILE A... | $800 | $0 | Jan 26, 2017 |
| Mar 16, 2016 | 35159070H | RESOLVE | CLASS - 1 | UNLAWFUL ACTS. FAILURE TO COMPLY W/AN ORDER OF THE COMMISSIONER. ON 10/30/15. A ELECTRICAL VIOLATION WAS ISSUE TO THE... | $800 | $0 | Jan 26, 2017 |
| Oct 30, 2015 | 35159446R | RESOLVE | CLASS - 1 | ELECTRICAL WORK DOES JOT CONFORM TO APPROVED SUBMITTED DOCUMENT/AMENDMENT. CELLAR BOILER ROOM CO. GENERATION SYSTEMS:... | $0 | $0 | Jan 26, 2017 |
| Oct 30, 2015 | 35159447Z | RESOLVE | CLASS - 1 | SEC. 250.30 SEPARATELY DERIVED SYSTEMS. SEPARATELY DERIVED SYSTEMS AS COVERED IN 250.20(A) OR (B) SHALL BE GROUNDED A... | $0 | $0 | Jan 26, 2017 |
| Oct 30, 2015 | 35159445P | RESOLVE | CLASS - 1 | ELECTRICAL WORK W/O A PERMIT. CELLAR BOILER ROOM CO. GENERATION SYSTEMS: 3-75KW GENERATORS,3 FEEDERS 400MCM,3-400AMP ... | $1,600 | $0 | Jan 26, 2017 |
| Feb 6, 2013 | 34989659R | RESOLVE | CLASS - 2 | 28-105-12.2SUPPORTED SCAFF CONTRARY TO PLANS.NOTED:AT TIME OF INSPECT ION SUPPORTED SCAFFOLD WAS CONTRARY TO APPROVED... | $0 | $0 | Mar 28, 2013 |
| Feb 6, 2013 | 34989658P | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE SITE SAFETY MANAGER.NOTED: AT TIME OF INSPECTION THERE WAS NO SITE SAFETY MANAGER AS REQUIRED.THE ... | $1,200 | $0 | May 23, 2013 |
| Jul 7, 2011 | 34922302H | RESOLVE | CLASS - 1 | BC3310.6)FAILURE TO PROVIDE DESIGNATED SITE SAFETY MANGER.EXAMINATION OF SITE SAFETY LOGS SHOW THAT VARIOUS SITE SAFE... | $0 | $0 | Sep 22, 2011 |
| Mar 21, 2011 | 34906854X | RESOLVE | CLASS - 2 | SEC. BC3310.6. FAILURE TO PROVIDE DESIGNATED SITE - SAFETY MANAGER. ATTIME OF INSPECTION OBSERVED SITE SAFETY MANAGER... | $800 | $0 | Aug 11, 2011 |
| Mar 21, 2011 | 34906853Y | RESOLVE | CLASS - 1 | PARTIAL SWO - ISSUED PURSUANT TO 28-207.2 AND POSTED AT PREMISES. WORKDOES NOT CONFORM TO APPROVED CONSTRUCTION DOCUM... | $500 | $0 | Aug 11, 2011 |
| Mar 21, 2011 | 34906855H | RESOLVE | CLASS - 2 | SEC. BC3310.6. FAILURE TO PROVIDE DESIGNATED SITE SAFETY MANAGER AT TIME OF INSPECTION OBSERVED (SITE) SAFETY MANAGER... | $0 | $0 | Aug 11, 2011 |
| Jul 21, 2009 | 34787712L | RESOLVE | CLASS - 1 | UNLAWFULLY CONTINUED WORK WHILE ON NOTICE OF A STOP WORK ORDER. (SUSPENDED SCAFFOLD RELOCATED TO EXPOSURE #4 FROM EXP... | $2,400 | $0 | Jan 21, 2010 |
| Jul 8, 2009 | 34788396N | RESOLVE | CLASS - 2 | FAILED TO NOTIFY DEPT/OBTAIN PERMIT PRIOR TO USE/INST OF C-HOOKS IN CONNECTION W/SUSPENDED SCAFFOLD. EXPIRED C-HOOK N... | $800 | $0 | Oct 28, 2010 |
| Jul 8, 2009 | 34788395L | RESOLVE | CLASS - 1 | LICENSED RIGGER FAILED TO ENSURE SCAFFOLD WORKER MET MINIMUM REQUIREMENTS. (WORKER ON TWO PT SUSPENDED SCAFFOLD W/NO ... | $1,600 | $0 | Oct 28, 2010 |
| Jul 8, 2009 | 34788394J | RESOLVE | CLASS - 1 | INADEQUATE SAFETY MEASURES. OPERATION OF HOISTING EQUIPMENT IN UNSAFE MANNER. (RAILS MISSING ON SUSPENDED SCAFFOLD PL... | $0 | $0 | Oct 28, 2010 |
| Jul 8, 2009 | 34754665R | RESOLVE | CLASS - 2 | WORKING W/O A PLUMBING PERMIT IN APT 614: UPON INSPECTION AT ABOVE LOCATION SUBJECT WAS PERFORMING UNLICENSED PLUMBIN... | $0 | $0 | May 22, 2014 |
| Sep 25, 2008 | 34702103K | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. NOTED: @ APT 1738 ON THE 17TH FL A WINDOW PANE FULL ONTO 1 AVE... | $1,000 | $0 | Nov 13, 2008 |
| Apr 8, 2008 | 34633239N | RESOLVE | Non-Hazardous | SEC. 27-1020. FAILURE TO POST DOT PERMIT FOR STREET/SIDEWALK CLOSING (PERMIT EXPIRED). AT TIME OF INSPECTION THERE IS... | $800 | $0 | May 29, 2008 |
| Apr 8, 2008 | 34633237J | RESOLVE | Non-Hazardous | WORK W/O A PERMIT. UPON INSPECTION A SIDEWALK SHED IS ERECTED ON 1ST AVE APPROX 50 IN LENGTH W/O A PERMIT. A PERMIT I... | $0 | $0 | May 29, 2008 |
| Apr 8, 2008 | 34633238L | RESOLVE | Non-Hazardous | SEC. 27-146. APPROVED PLANS NOT AVAILABLE FOR INSPECTION. AT TIME OF INSPECTION NO APPROVED PLAN FOR PIPE SCAFFOLD AP... | $800 | $0 | May 29, 2008 |
| Sep 10, 2007 | 34582183X | RESOLVE | Hazardous | FAILURE TO POST DOT PERMIT FOR STREET CLOSING.AS NOTED:UPON INSPECTION1 LANE CLOSED ON 1ST AVE FRONT OF ABOVE ADDRESS... | $0 | $0 | Nov 8, 2007 |
| Apr 16, 2007 | 38165910L | RESOLVE | Non-Hazardous | 01L10,02L10.01-ALARM BELL DOES NOT RING WHEN RUN/STOP SWITCH PULLED.02-ALARM BELL-DEFECTIVE. | $0 | $0 | Jun 14, 2007 |
| Apr 16, 2007 | 38165911N | RESOLVE | Non-Hazardous | 44B10.44-GOVERNOR NOISE | $0 | $0 | Jun 14, 2007 |
| Mar 27, 2007 | 34540752L | RESOLVE | Non-Hazardous | WORK CONTRARY TO APPROVED DOB PLANS & APPLICATION. OBSERVED HOISTING EQUIPMENT ON BLDG THAT WAS NOT ON PLANS. | $500 | $0 | Nov 1, 2007 |
| Oct 16, 2006 | 34538990Y | RESOLVE | Non-Hazardous | FAILURE TO POST SIGN ON SHED AS REQUIRED BY LOCAL LAW 33/91.AS NOTED:SIDEWALK ERECTED ON E. 40TH ST.W/NO PERMIT HOLDE... | $200 | $0 | Jul 12, 2007 |
| Apr 28, 2006 | 34514629R | RESOLVE | Hazardous | FAILURE TO HAVE SITE SAFETY MANAGER PRESENT AS REQUIRED. NOTED:AT TIME OF INSPECTION MEN WERE WORKING AT EAST ELEVATI... | $2,000 | $0 | Jun 20, 2007 |
| Feb 8, 2006 | 34509409Z | RESOLVE | Non-Hazardous | NO DESIGN DRAWING AT TIME OF INSP. ALT 2 #101902292. AT INSP. OUT RIGGING TWO POINT SUSPENSION SCAFFOLD GRADED ON EAS... | $500 | $0 | Jun 7, 2007 |
| Feb 7, 2006 | 34509173L | RESOLVE | Hazardous | NO SITE SAFETY PLAN. UPON INSPECTION AT THE ABOVE PROPERTY 26 STORIES OCCUPIED BLDG UNDER ALTERATION REMOVING BRICKS ... | $250 | $0 | Mar 30, 2006 |