ECB violations
East 52 Street, Manhattan • Block 01364 • Lot 0034
81 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Apr 21, 2026 | 39185327Z | RESOLVE | CLASS - 1 | 5/A/10 CAR CEASE USE, CLASS 1, CAR DOOR RESTRICTOR DEFECTIVE REPAIR. | $1,250 | $0 | Jun 25, 2026 |
| Apr 20, 2026 | 37036763N | ACTIVE | CLASS - 2 | FAILURE TO FILE ACCEPTABLE AMENDED CYCLE 9A REPORT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRIBED IN INITIAL FA... | $1,250 | $1,250 | Aug 13, 2026 |
| Jul 1, 2025 | 37036059J | RESOLVE | CLASS - 2 | FAILURE TO FILE REQUIRED ANNUAL BOILER INSPECTION REPORTS FOR LOW-PRESSURE BOILER 10000161755Y0002 IN ACCORDANCE WITH... | $0 | $0 | Oct 16, 2025 |
| Jul 1, 2025 | 37036058H | RESOLVE | CLASS - 2 | FAILURE TO FILE REQUIRED ANNUAL BOILER INSPECTION REPORTS FOR LOW-PRESSURE BOILER 10000161755Y0001 IN ACCORDANCE WITH... | $0 | $0 | Oct 16, 2025 |
| May 10, 2023 | 39085988H | ACTIVE | CLASS - 2 | OBSERVED PARKING GARAGE LEVELS 2ND 1ST,CELLAR AND SUBCELLAR IN DISREPAIR. SUBCELLAR LEVEL HORIZONTAL CRACK IN FOUNDAT... | $625 | $0 | Aug 17, 2023 |
| Dec 2, 2022 | 37023948R | ACTIVE | CLASS - 2 | FAILURE TO SUBMIT ACCEPTABLE REQUIRED CYCLE 9A REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALL ... | $6,250 | $0 | Feb 23, 2023 |
| Mar 16, 2022 | 35644307X | RESOLVE | CLASS - 2 | MISC.VIOLATION OF CONDITION ON AS OF RIGHT PRIVATELY OWNED SPACE.AS PER ZR 37-751 AND ZR E 27-42 A PLAQUE OR OTHER PE... | $5,000 | $0 | Jun 30, 2022 |
| Oct 1, 2020 | 39029632K | RESOLVE | CLASS - 1 | CAR CEASE USE CLASS 1 ,CAR DOOR RESTRICTOR IS NOT WORKING MISSING PARTS REPAIR, OR REPLACE. BRAKE TAG EXPIRED PROVIDE. | $1,250 | $0 | Nov 19, 2020 |
| Oct 15, 2019 | 35457610P | RESOLVE | CLASS - 1 | BC90728-FAILURE TO PROVIDE FIRE ALARM SYSTEM FOR TRANSIENT USE FOR APARTMENT 16C.REMEDY:DISCONTINUE ILLEGAL USE. | $0 | $0 | Feb 11, 2021 |
| Oct 15, 2019 | 35457609H | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.LACK OF AUTOMATIC SPRINKLER SYSTEM,WHERE IS REQUIRED AS PER 903... | $0 | $0 | Feb 11, 2021 |
| Oct 15, 2019 | 35457608X | RESOLVE | CLASS - 2 | PERMANENT DWELLING USE/CONVERTED FOR OTHER THAN PERMANENT-RESIDENTIAL PURPOSED.DEPARTMENT OF BUILDINGS RECORDS INDICA... | $0 | $0 | Feb 11, 2021 |
| Jun 10, 2019 | 35434312P | ACTIVE | CLASS - 2 | ZR 37-77 VIOLATION OF CONDITION ON AS OF RIGHT PRIVATELY OWNED PUBLIC SPACE.NOTED:AS PER ZONING RESOLUTION CHAPTER 7,... | $5,000 | $0 | Sep 26, 2019 |
| Feb 9, 2018 | 35311247H | ACTIVE | CLASS - 2 | ZR 37-726 MISC. VIO OF CONDITION ON AS OF RIGHT PRIVATELY OWNED PUBLICSPACE.NOTED:@TIME OF INSP PLAZA SPACE LOCATED O... | $4,000 | $0 | Jun 27, 2018 |
| Dec 21, 2016 | 35210161Y | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN EXTERIOR BLDG ROOF-AT EMR.VERTICLE CRACK APPROX 10'THRU BRICK AND MORTAR-RAISED AND NOT SECURED F... | $500 | $0 | Feb 9, 2017 |
| Aug 11, 2016 | 37001056Y | RESOLVE | CLASS - 2 | FAILURE TO SUBMIT ACCEPTABLE 7TH ROUND REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALLS & APPUR... | $4,000 | $0 | Feb 9, 2017 |
| Apr 26, 2016 | 35174281N | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN EXTERIOR BLDG SOUTH ELEV EXP#1. GARAGE ENTRANCE STUCCO CRACKED/BROKEN OFF. GARDEN VERTICLE CRACKS... | $250 | $0 | Aug 11, 2016 |
| Sep 21, 2015 | 37000116M | RESOLVE | CLASS - 2 | 28.317.3 FAILURE TO REGISTER COOLING TOWER.REM:COMPLY W/CODE. | $0 | $0 | Oct 30, 2015 |
| Sep 15, 2015 | 36027932Y | RESOLVE | CLASS - 2 | FAIL TO FILE AN ACCEPTABLE TECH REPORT IN COMPLIANCE W/CODE PROVISIONS:NOV #36018986P PERIODIC INSPECTION OF EXTERIOR... | $4,000 | -$4,000 | Feb 25, 2016 |
| Sep 3, 2015 | 35133552P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN EXTERIOR BLDG.NORTH ELEVATION EXP1 SPALLING & DETERIORATING MASONRY BELOW 3RD FL WINDOW,ORNAMENTA... | $250 | $0 | Oct 22, 2015 |
| Apr 24, 2015 | 35131760K | RESOLVE | CLASS - 1 | 3314.4.1.5 NOTIFICATION OF ADJUSTIBLE SUSPENDED SCAFFOLD.NOTED OBSERVED SUSPENDED SCAFFOLD IN CONNECTION W/ C-HOOK ER... | $8,000 | $0 | Jun 11, 2015 |
| Jan 5, 2015 | 35121915R | RESOLVE | CLASS - 1 | WORK DOES NOT CONFORM TO APPROVED CONST DOCS-SITE SAFETY PLAN NOTED:CONTRARY TO SITE SAFETY PLAN SECTION CLOSE OUT IN... | $1,000 | $0 | Feb 19, 2015 |
| Jan 5, 2015 | 35121916Z | RESOLVE | CLASS - 2 | DESIGN REQUIRED BY THE CHAPTER 33 NOTED:SIDEWALK SHED ERECTED @EXP#1 &3 NO DESIGN DRAWING AVAILABLE FOR REVIEW UPON R... | $400 | $0 | Feb 19, 2015 |
| Jan 5, 2015 | 35121913N | RESOLVE | CLASS - 2 | EXPIRED PERMIT.ACTIVE FACADE JOB.RIGGS @EXP#1 & 3 CD-5 (TRI3-1231)EXPIRED ON 01/01/15.PSWO ISSUED PURSUANT TO 28-207.... | $800 | $0 | Feb 19, 2015 |
| Jan 5, 2015 | 35121914P | RESOLVE | CLASS - 1 | WORK DOES NOT CONFORM TO APPROVED CONST DOCS-SITE SAFETY PLAN NOTED:CONTRARY TO SITE SAFETY MESH NETTING HAS NOT BEEN... | $1,000 | $0 | Feb 19, 2015 |
| Aug 23, 2014 | 32074588K | RESOLVE | CLASS - 1 | B154/ 50A/ 32A/ 50B/ (50A) BOILER BURNER EXCESSIVE SMOKE 50B PIPE RELIEF VALUE AT A SAFE LOCATION. (50C) REMOVE WASTE... | $1,030 | $0 | Oct 9, 2014 |
| Aug 12, 2014 | 35107197K | RESOLVE | CLASS - 3 | WORK W/O PERMIT. ILLEGAL WORK NOTED @ APT. 35B W/ THE ERECTION OF FULLHEIGHT PARTITIONS, WORK APPEARS TO NOT BE OF OR... | $200 | $0 | Oct 2, 2014 |
| Apr 21, 2014 | 36018986P | RESOLVE | CLASS - 2 | FAILUER TO FILE AN ACCEPTABLE CYCLE 7 TECHNICAL REPORT IN COMPLIANCE WITH CODE PROVISIONS: PERIODIC INSPECTION OF EXT... | $800 | $0 | Oct 30, 2014 |
| Mar 11, 2014 | 35086871N | RESOLVE | CLASS - 2 | FAILED TO NOTIFY DEPT PRIOR TO USE OFF C-HOOKS/OUT RIGGER BEAMS IN CONNECTION WITH SUSPENDED SCAFFOLD.NOTE:@ TIME OF ... | $400 | $0 | May 1, 2014 |
| Mar 11, 2014 | 35086872P | RESOLVE | CLASS - 1 | NO RECORD OF DAILY INSP.OF SUSPENDED SCAFFOLD PERFORMED BY AUTORIZED PERSON AT SITE.NOTE:AT TIME OF INSP FACADE WORK ... | $2,400 | $0 | May 1, 2014 |
| Jan 27, 2014 | 35024269R | ACTIVE | CLASS - 2 | FAIL TO MAINTAIN EXTERIOR BLDG.NOTE:EXPOSURE #3 SPALLED CONCRETE,EXPOSED REBAR,CRACKING;EXPOSURE #4 DISPLACED BRICKS/... | $500 | $0 | Mar 13, 2014 |
| Dec 14, 2013 | 35084353Y | ACTIVE | CLASS - 2 | SEC. 27-385 FAILURE TO MAINTAIN ILLUMINATED EXIT SIGNS,PER 27-385. NOTED: AT GARAGE,NO ILLUMINATION FOR EMERGENCY EXI... | $800 | $0 | Jan 30, 2014 |
| Dec 14, 2013 | 35084355H | RESOLVE | CLASS - 2 | WORK W/O PERMIT. NOTED: AT GARAGE INSTALLED 2 STRUCTURAL STEEL I BEAM GIRDERS W/FLAGES BOLTED TO FOUNDATION WALLS & C... | $800 | $0 | Apr 17, 2014 |
| Dec 14, 2013 | 35084354X | RESOLVE | CLASS - 2 | WWORK W/O PERMIT. NOTED: AT GARAGE,INSTALLED 6 CAR LIFTS,NO PERMIT OR APPL HAS BEEN ISSUED FOR THIS WORK. REMEDY: OBT... | $800 | $0 | Apr 17, 2014 |
| Dec 14, 2013 | 35084351K | ACTIVE | CLASS - 2 | EXIT DOORS NOT SELF CLOSING. NOTED: AT GARAGE,FIRE PROOF SELF CLOSING DOORS ARE NOT SELF CLOSING ADJACENT TO AREA "A5... | $500 | $0 | Apr 17, 2014 |
| Dec 14, 2013 | 35084352M | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3;27-345. NOTED: AT GARAGE,MISSING FIR... | $500 | $0 | Apr 17, 2014 |
| Oct 19, 2013 | 32073824Z | ACTIVE | CLASS - 2 | B254,50A. 50A-EXCESSIVE SMOKE COMING FROM CHIMNEY ON MOBILE STEAM BOILER ON 53RD STREET. CONNECTED TO 429 E 52ND STR ... | $500 | $0 | Dec 5, 2013 |
| Feb 20, 2013 | 35001681R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG WALLS-NOTED I-SPALLINGS AND REBARS AT PARAPETS AT EXPOSURE 1 & EXPOSURE 3 B/AT UNDERSIDE OF ... | $500 | $0 | Apr 11, 2013 |
| Sep 7, 2012 | 32072550X | RESOLVE | CLASS - 1 | 154,51,50A,50B,(50A)EXCESSIVE STEAM ENTERING MOBILEBOILERCONDENSATION,TANK HAZARDOUS CONDITION (50B)DO NOT OPERATE BO... | $1,000 | $0 | Dec 13, 2012 |
| Sep 6, 2012 | 32072421J | RESOLVE | CLASS - 1 | 154,50A,32A,50A,50B.(50A)EXCESSIVE STEAM ESCAPING FROM MOBILE BOILER CONDENSATION TAK/DISCHARGE PIPE (50B)BOILER BURN... | $1,000 | $0 | Dec 13, 2012 |
| Apr 16, 2012 | 32071876L | RESOLVE | CLASS - 2 | 50A,B. 50A- SATURATED RAGS OF # 2 FUEL OIL ON FLR ABSORBING OIL LEAK POSSIBLY FROM FUEL BURNER (FIRE HAZARD). 50B- FU... | $250 | $0 | May 31, 2012 |
| Apr 16, 2012 | 34925952N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING WALLS. PARAPETS SPALLINGS & REBARS WERE FOUND AT EXTERIOR & INTERIOR OF PARAPETS AT EXPO... | $500 | $0 | Jul 19, 2012 |
| Sep 13, 2011 | 38218276J | RESOLVE | CLASS - 2 | 61G11,17D06,52M07,70O02. 61G- UNREADABLE. 17D-WHERE NEEDED. 52M- ANTI-SPINS. | $0 | $0 | Nov 3, 2011 |
| Sep 13, 2011 | 38218149R | RESOLVE | CLASS - 2 | 61B01,05X10,52M07,70O02,79E01,17D06. 61B- HOIST MACHINE NOT IN LINE OFSIGHT W/MAIN LINE - ADJUST PER NEC CODE. 05X- Z... | $0 | $0 | Nov 3, 2011 |
| Sep 13, 2011 | 38218275H | RESOLVE | CLASS - 2 | 52M07,70O02,17D06. 52M- ANTI-SPINS. 17D-WHERE NEEDED. | $0 | $0 | Nov 3, 2011 |
| Aug 4, 2011 | 34923698H | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY. NOTED: ALL EXIT PASSAGEWAYS FROM SUB CELLAR TO 1 FL ARE OBSTRUCTED B... | $1,200 | $0 | Oct 27, 2011 |
| Aug 4, 2011 | 34923697X | RESOLVE | CLASS - 1 | SEC. 715 FAILURE TO COMPLY W/OPENING PROTECTIVE'S REQUIREMENTS. NOTED ALL FPSC DOORS FROM SUB CELLAR TO 1 FLOOR ARE S... | $0 | $0 | Oct 27, 2011 |
| Jul 27, 2011 | 32069617Y | RESOLVE | CLASS - 1 | 51 50A-STEAM HOSES LEAKING FROM MOBILE BOILER STATIONED OUTSIDE OF BLDG PROVIDING TEMP HEAT AND HOT WATER HOSES ARE R... | $1,000 | $0 | Sep 15, 2011 |
| Jan 12, 2009 | 34758346H | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER: LACK OF EMERGENCY POWER OR STORAGE BATTERY CONNECTION TO EXIT SIGN... | $4,800 | $0 | May 7, 2009 |
| Aug 4, 2008 | 38190026P | RESOLVE | CLASS - 1 | 01X10.10H11.02X10.60Q03.70O02.C.U IN CAR STOP SW INOPERATIVE 01X10 10H11 WORN CAR DOOR GIBS REPLACE 02X10 ALARM BELL ... | $1,000 | $0 | Sep 25, 2008 |
| Apr 7, 2008 | 38183177R | RESOLVE | Non-Hazardous | 86BB5. 86BB5 PERFORM & FILE 2 YEAR TEST. | $180 | $0 | May 29, 2008 |