ECB violations
4-6 East 64 Street, Manhattan • Block 01378 • Lot 0066
65 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Aug 27, 2021 | 39046653Y | RESOLVE | CLASS - 2 | FOUND CROWN BOILER S/N 512640 ACTIVE WITH DEFECTS. COMBUSTION AIR INTAKE FAN DEFECTIVE. SAIL SWITCH INTERLOCK WITH BO... | $1,562 | -$1,562 | Oct 14, 2021 |
| Jul 7, 2021 | 35583319R | RESOLVE | CLASS - 2 | 3314.4 SUPPORTED PIPE SCF NOT INSTALLED,MAINTAINED AS PER CODE.ATOI OF5STYALT1 ACTIVE JOBSITE,OBSERVED SUPPORTED PIPE... | $0 | $0 | Sep 23, 2021 |
| Jul 6, 2021 | 39043971X | RESOLVE | CLASS - 2 | CONDENSATE TANK LEAKING;CORRECT VIOLATION AND SUBMIT THE CERTIFICATE OF CORRECTION | $625 | $0 | Jan 6, 2022 |
| Dec 4, 2020 | 39033002H | RESOLVE | CLASS - 2 | SPILL SWITCH DISCONNECTED., MAINTAIN BOILER; CORRECT VIOLAING CONDITION AND SUBMIT A CERTIFICATE OF CORRECTION | $1,562 | $0 | Jan 21, 2021 |
| Dec 4, 2020 | 39032999Y | RESOLVE | CLASS - 1 | 240 PPM CO READING AT CROWN BSI379 BOILER DIVERTER. BOILER CEASE USE; CORRECT HAZARDOUS CONDITION IMMEDIATELY. DON'T ... | $3,125 | -$3,125 | Jan 21, 2021 |
| Dec 4, 2020 | 39033001X | RESOLVE | CLASS - 1 | 60 PPM DIVERTER OF LOCHINVAR CWN135PM HOT WATER HEATER. ISSUED CEASE USE. CORRECT IMMEDIATELY, MAINTAIN BOILER; DON'T... | $3,125 | $0 | Jan 21, 2021 |
| Dec 4, 2020 | 39033000Y | RESOLVE | CLASS - 2 | CONTROLS NOT WIRED, CHIMNEY CLEAN OUT INCORRECT. CORRECT VIOLATING CONDITION & SUBMIT A CERTIFICATE OF CORRECTION. | $1,562 | -$1,562 | Jan 21, 2021 |
| Feb 16, 2020 | 39017671P | RESOLVE | CLASS - 2 | NOTED SWS AT FRONT UNDER PERMIT #M00163172-01SH LACKED MUDSILLS IN VARIOUS LOCATIONS AND WITH VARIOUS POSTS OUT OF PL... | $2,400 | $0 | Apr 22, 2021 |
| Sep 12, 2019 | 39009412K | RESOLVE | CLASS - 1 | AS PER ONE LOCHINVAR HOT WATER MAKER MOD.# CWN135PM SER# E13H00250237 ; WORK W/O A PERMIT., OBTAIN PERMIT; APPLY FOR ... | $6,250 | $0 | Oct 31, 2019 |
| Sep 12, 2019 | 39009411Z | RESOLVE | CLASS - 1 | FLUE PIPE DISCONNECTED. BOILER SEALED ; CORRECT ALL VIOLATIONS, CALL FOR AN INSPECTION. | $3,125 | $0 | Oct 31, 2019 |
| Sep 9, 2019 | 35445267Z | RESOLVE | CLASS - 2 | FAILURE TO INSTITUTE & MAINTAIN SAFETY EQUIPMENT MEASURES. NOTE: @THE TIME OF INSPECTION OF AN ACTIVE JOB SITE, I OBS... | $5,000 | $0 | Dec 5, 2019 |
| Feb 21, 2019 | 35332356J | RESOLVE | CLASS - 1 | FAILURE TO SAFEGUARD ALL PERSONS AND PROPERTY AFFECTED BY CONSTRUCTIONOPERATION.5 STORY EXISTING BUILDING-ALT 1 & ACT... | $5,000 | $0 | Apr 18, 2019 |
| Feb 21, 2019 | 35332357L | RESOLVE | CLASS - 1 | FAILURE TO INSTITUTE MAINTAIN SAFETY EQUIPMENT MEASURES OR TEMPORARY CONSTRUCTION NO GUARDRAILS 5 STORY EXISTING BUIL... | $0 | $0 | Apr 18, 2019 |
| Mar 21, 2017 | 38253744P | RESOLVE | CLASS - 2 | 70M7,71L10. 70M7-PIT LADDER MISSING PROVIDE; 71L10-PIT LIGHT DEFECTIVE REPAIR. | $250 | $0 | May 11, 2017 |
| Mar 18, 2014 | 32073184J | RESOLVE | CLASS - 2 | 50 FRESH AIR FAN NOT INTERLOCKED WITH BOILER. | $0 | $0 | May 8, 2014 |
| Nov 12, 2013 | 35065554R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN. NOTED: AT REAR YARD OF PREMISES INSTALLATION OF EXHAUST FAN FROM BOILER ROOM. DIRECTLY UNDER GRO... | $0 | $0 | Mar 20, 2014 |
| Nov 28, 2012 | 32072779Y | RESOLVE | CLASS - 2 | B254,4A. | $500 | $0 | Feb 28, 2013 |
| Nov 28, 2012 | 32072777K | RESOLVE | CLASS - 2 | B254,16,50,50A,B,C,D,E. 50- GAS REGULATOR NOT VENTED OUTSIDE. 50A- WATER COLUMN CORRODED. 50B- MIXING VALVE MISSING C... | $500 | $0 | Feb 28, 2013 |
| Nov 28, 2012 | 32072778M | RESOLVE | CLASS - 2 | B254,50,50A. 50- GAS PIPE BLOCKING FRONT JACKET AND BLOCKING SERVICE. 50A- GAS PIPE NOT SUPPORTED. | $500 | $0 | Feb 28, 2013 |
| Oct 6, 2012 | 34995101Z | RESOLVE | CLASS - 2 | SIDEWALK SHED DOES NOT MEET BLDG CODE SPECIFICATIONS SIDEWALK SHED ERECTED IN PLACE UNDER PERMIT#121369465, EXPIRING ... | $2,400 | $0 | Jan 10, 2013 |
| Oct 6, 2012 | 34995100R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCES.REAR 4-STORY BRICK EXTENSION EXTERIOR BRICK FACADE SEPARATING APPROX.... | $1,250 | $0 | May 9, 2013 |
| Mar 31, 2012 | 34950535R | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN NOTICE OF VIOLATION #34925481X ISSUED ON 12/11/11 FOR WORK W/O A PE... | $2,400 | $0 | May 17, 2012 |
| Mar 23, 2012 | 34971436Y | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMMISSIONER'S ORDER TO FILE A C OF C W/THE DEPT OF BUILDINGS FOR NOTICE OF VIOLATION #349160... | $2,000 | $0 | May 10, 2012 |
| Feb 28, 2012 | 34963837P | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/ THE COMM ORDER CONTAINED IN NOV#34925481X ISSUED ON 12/11/11 FOR WORK W/O A PERMIT A ROOF AREA R... | $0 | $0 | Apr 26, 2012 |
| Feb 28, 2012 | 34971252J | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMMISSIONER'S ORDER TO FILE A C OF C W/THE DEPT OF BUILDINGS FOR NOTICE OF VIOLATION #349254... | $800 | $0 | Apr 26, 2012 |
| Feb 27, 2012 | 34937985H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. DEFECT NOTED:WATER PENTRATING & LEAKING THRU EXTERIOR WALLS DA... | $500 | $0 | Dec 13, 2012 |
| Jan 20, 2012 | 34932819J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG. NOTED: HANGING, PEELING CEILING PLASTER & WATER DAMAGE TO CEILING & WALLS. LIGHT FIXTURE UN... | $0 | $0 | Apr 12, 2012 |
| Jan 14, 2012 | 34932741Z | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF CLOSING. NOTED:AT APT 1F EXIT/ENTRY DOOR IS RACKED TO FRAME & DOES NOT CLOSE & DOOR CHECKS/CLOSER ... | $500 | $0 | Apr 12, 2012 |
| Jan 14, 2012 | 34962933K | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/THE COMMISSIONER'S ORDER CONTAINED IN NOTICE OF VIOLATION #34740996Y ISSUED ON 11/4/11. THE RESPO... | $0 | $0 | Apr 12, 2012 |
| Jan 13, 2012 | 34937954P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN A CODE COMPLAINT MANNER. NOTED THE FOLLOWING CONDITIONS: WALK IN APT LOCATED AT 8 EAS... | $500 | $0 | Apr 12, 2012 |
| Jan 13, 2012 | 34937956Z | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER TO FILE A C OF C W/THE DEPT OF BUILDINGS. TO CERTIFY THAT YOU HAVE CORRECTED THE... | $800 | $0 | Apr 12, 2012 |
| Jan 13, 2012 | 34937955R | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER TO FILE A C OF C W/THE DEPT OF BUILDINGS. TO CERTIFY THAT YOU HAVE CORRECTED THE... | $800 | $0 | Apr 12, 2012 |
| Jan 13, 2012 | 34937742N | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERT OF CORRECTION WITH THE DOB. DEFECT NOTED:AT TIME OF IN... | $800 | $0 | Apr 12, 2012 |
| Jan 13, 2012 | 34937741L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER. DEFECTS NOTEDAT TIME OF INSPECTION WATER DAMAGE IS EVIDENT T... | $500 | $0 | Apr 12, 2012 |
| Dec 30, 2011 | 34940328P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG WALL(S) OR APPURTENANCES. NOTED: FACADE ON WEST SIDE, WATER HAS PENETRATED AND CAUSED INTERI... | $0 | $0 | Apr 12, 2012 |
| Dec 11, 2011 | 34925482H | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG WALLS. NOTED: @ REAR OF PREMISES FROM ROOF DOWN - @ SE SIDE WHERE EXTENSION MEETS MAIN BLDG ... | $1,000 | $0 | Apr 26, 2012 |
| Dec 11, 2011 | 34925481X | RESOLVE | CLASS - 1 | WORK W/O A PERMIT. @ ROOF A DECK HAS BEEN ERECTED COVERING MORE THAN 90% OF ROOFING W/O A RAILING W/O A PERMIT @ TIME... | $1,600 | -$250 | Apr 26, 2012 |
| Nov 23, 2011 | 34917038L | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER:DEFECT NOTED @ APT 4C CRACKS EVIDENT IN BATHROOM CEILING,THRO... | $250 | $0 | Apr 12, 2012 |
| Nov 4, 2011 | 34740996Y | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN A CODE COMPLIANT MANNER @ REAR CHIMNEY STAINLESS STEEL STACK PIPE FURNACE IS CROOKED W/ G... | $0 | $0 | Mar 8, 2012 |
| Nov 2, 2011 | 34916098Z | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN EXTERIOR BLDG WALLS OR APPURTENANCES.DEFECTS NOTED:@ TIME OF INSPEC 3 IS A VERTICAL CRACK IN THE ... | $0 | $0 | Mar 8, 2012 |
| Nov 2, 2011 | 34916099K | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY DEFECTS NOTED:@ TIME OF INSPEC THERE ARE POTTED PLANTS BY STAIRWELL L... | $1,200 | -$1,200 | Mar 8, 2012 |
| Oct 26, 2011 | 34915999L | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN EXTERIOR BLDG WALL(S)OR APPURTENANCES.DEFECTS NOTED:@ TIME OF INSPEC.METAL CHIMNEY AT REAR OF BLD... | $500 | -$500 | Mar 8, 2012 |
| Mar 30, 2011 | 34879897P | RESOLVE | CLASS - 2 | ALTERED/CHANGED BLDG OCCUPIED W/O A VALID C/O. NOTED: EXISTING C/O #96501 DOES NOT INDICATE A LAUNDRY ROOM IN CELLAR:... | $500 | $0 | Sep 8, 2011 |
| Mar 30, 2011 | 34879898R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN A CODE-COMPLIANT MANNER. NOTED: BOILER ROOM CEILING HAS A NON-FIRE RATED MATERIAL ATTACHE... | $500 | $0 | Sep 8, 2011 |
| Mar 30, 2011 | 34879894J | RESOLVE | CLASS - 1 | WORK W/O A PERMIT IN CELLAR. NOTED: ROOM W/TOILET ROOM, CLOSET AND DOOR TO REAR YARD. THIS CELLAR CONDITIONS WHICH IS... | $1,600 | $0 | Sep 8, 2011 |
| Mar 30, 2011 | 34879895L | RESOLVE | CLASS - 1 | WORK W/O A PERMIT. NOTED: WOOD ROOF DECK W/WOOD LATTICE AND SLAT DIVISIONS: ROOF DECK MISSING FRONT RAILING. ROOF DEC... | $1,600 | $0 | Sep 8, 2011 |
| Mar 30, 2011 | 34879896N | RESOLVE | CLASS - 1 | WORK W/O A PERMIT. NOTED: LAUNDRY ROOM IN CELLAR W/ONE COMMERCIAL GAS CLOTHES DRYER AND 1 WASHING MACHINE. THERE'S NO... | $1,600 | $0 | Sep 8, 2011 |
| Mar 30, 2011 | 34879893H | RESOLVE | CLASS - 1 | WORK W/O A PERMIT. NOTED: METAL CHIMNEY LOCATED AT THE REAR OF BLDG DOES NOT HAVE A PERMIT ON FILE FOR ITS INSTALLATI... | $1,600 | $0 | Sep 8, 2011 |
| Mar 30, 2011 | 34879899Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN A CODE-COMPLIANT MANNER. NOTED: LAUNDRY ROOM GAS COMMERCIAL CLOTHES DRYER HAS FLEXIBLE GA... | $0 | $0 | Mar 8, 2012 |
| Jan 12, 2010 | 32067483Z | RESOLVE | CLASS - 2 | B254 32A.50.50A.50 MISSING FIRE SAMPER FOR FEED INTO BOILER RM 50A BOILER AND GAS BURNER HAVE LOUD RUMBLING NOISE ON ... | $500 | $0 | Feb 10, 2011 |