| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Oct 18, 2023 | 39097349J | RESOLVE | CLASS - 2 | COMBUSTION AIR FAN NEEDS PROOFING SWITCH/ REAR SPILL SWICTH HAS TO BE INSTALL PROPELY/FLUE PIPE OUTSIDE BOILER ROOM I... | $0 | $0 | Jan 25, 2024 |
| Oct 18, 2023 | 39112660P | RESOLVE | CLASS - 2 | COMBUSTION AIR FAN NEEDS PROOFING SWITCH/REAR SPILL SWITCH HAS TO BE INSTALL PROPELY/FLUE PIPE OUTSIDE BOILER ROOM IN... | $0 | -$625 | Aug 7, 2025 |
| Nov 8, 2021 | 39050759Y | ACTIVE | CLASS - 2 | BOILER OPERATING AT PRESSURE ABOVE PRESSURE RELIEF VALVE- PRESSURE RELIEF VALVE DISCHARGING IN BOILER ROOM. | $312 | $0 | Apr 14, 2022 |
| Nov 1, 2021 | 39050400H | ACTIVE | CLASS - 1 | FOUND BURNHAM BOILER WITH A MAWP OF 50PSI AND WITH A PRESSURE RELIEF VALVE WITH A SET PRESSURE RATING OF 60PSI. BOILE... | $1,250 | $1,250 | Apr 28, 2022 |
| Dec 24, 2008 | 34741088N | RESOLVE | CLASS - 1 | WORK W/O A PERMIT NOTED: A MASONRY WALL WITH CONDENSING UNITS ATTACHED TO IT WAS FOUND AT THE ROOF OF THIS PREMISES. ... | $0 | $0 | Feb 12, 2009 |
| Sep 11, 2008 | 34700968K | RESOLVE | CLASS - 1 | WORK W/O A PERMIT. FOUND A CONCRETE BLOCK WALL ATTCHED TO THE 8TH FL NW. EXTERIOR WALL OF BLDG 315 E 68 ST. THIS CONC... | $0 | $0 | Oct 30, 2008 |