ECB violations
34 East 81 Street, Manhattan • Block 01492 • Lot 0048
7 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Feb 10, 2014 | 35038674H | RESOLVE | CLASS - 1 | FAILURE TO PROPERLY BOND ELECTRICAL SYSTEMS. BSMT SERVICE SWITCH 200 AMP GENERAL ELECTRIC: NEUTRAL BAR NOT BONDED TO ... | $15,000 | $0 | Apr 3, 2014 |
| Feb 10, 2014 | 35038672Y | RESOLVE | CLASS - 1 | ELECTRICAL WORK W/O A PERMIT. THE ENTIRE HALLWAY IS BRANCH CIRCUIT WIRING,LIGHTING FIXTURES. TEMPORARY WIRING. RMDY: ... | $800 | $0 | Jun 19, 2014 |
| Feb 10, 2014 | 35038700M | RESOLVE | CLASS - 2 | FAILURE TO INSTALL GROUND-FAULT CIRCUIT INTERRUPTER (GFCI) PROTECTION AS REQUIRED. THE ENTIRE HALLWAY'S TEMPORARY WIR... | $0 | $0 | Jun 5, 2014 |
| Feb 10, 2014 | 35038673X | RESOLVE | CLASS - 1 | FAILURE TO GROUND ELECTRICAL SYSTEMS. BSMT SERVICE EQUIPMENT GROUND:NOWATER MAIN GROUND PROVIDED. RMDY: PROVIDE GROUN... | $24,000 | $0 | Apr 3, 2014 |
| Apr 11, 2005 | 34465273R | ACTIVE | Hazardous | FAILURE TO MAINTAIN EXTERIOR.DEFECTS NOTED:AT WESTERN WALL APROX 10' TO 15' BELOW PARAPET FROM CENTER TO SOUTH SIDE O... | $800 | $0 | May 26, 2005 |
| Dec 8, 2003 | 34417179Y | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN BUILDING NOTED : WATER SEEPING THROUGH CELLAR FOUNDATION WALL FROM 34 E 81 ST CAUSING MINOR WATER... | $180 | $0 | Jan 22, 2004 |
| Sep 1, 1999 | 34223076X | RESOLVE | Hazardous | FAOLURE TO MAINTAIN EXTERIOR BUILDING WALL. IN THAT LOOSE BRICKS BECAME DISLOCATED FROM 4 FLOOR WEST WALL AND FELL ON... | $800 | $0 | Nov 5, 1999 |