ECB violations
1527 York Avenue, Manhattan • Block 01560 • Lot 0027
7 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Jun 16, 2009 | 32066502K | RESOLVE | CLASS - 2 | 48B,18B,50A,50B,50C,38. 50A- REPLACE DEFECTIVE FLUE PIPE. 50B- MAKE CHIMNEY BASE ACCESSIBLE FOR INSPECTION. 50C- CLEA... | $0 | $0 | Aug 6, 2009 |
| Jun 16, 2009 | 32066503M | ACTIVE | CLASS - 2 | 50A,50B,50C,50D,38,50E. 50A- BOILER FLU PIPE NOT PROPERLY SECURED & SUPPORTED. 50B- EXPOSED WOOD BEAMS ABOVE CHIMNEY ... | $500 | $0 | May 13, 2010 |
| Aug 20, 2007 | 32052353Z | ACTIVE | Hazardous | B4B,50A,B,C,D,E,18A,B.50A-BOILER CASING CORRODED.50B-FLUE PIPE DEFECTIVE(CONNECTION).50C-CHIMNEY CLEANOUT CORRODED.50... | $800 | $0 | Oct 17, 2007 |
| Dec 30, 2005 | 32049259P | RESOLVE | Non-Hazardous | 50A/50B/50C. FULTON V.T. BOILER, 10HP, NB 61344, GAS, 1991. 50A-LOOSE SECTION OF FLUE PIPE INSTALL SCREWS AND SECURE ... | $0 | $0 | Feb 16, 2006 |
| Dec 30, 2005 | 32049260M | RESOLVE | Non-Hazardous | 50A/50B. WEIL MCLAIN C.R. BOILER, LPS-50A-SCREW THREADS IN PLACE ON THE OUTLET END OF THE SAFETY VALVE DISCHARGE PIPE... | $0 | $0 | Feb 16, 2006 |
| May 4, 2004 | 32044705N | RESOLVE | Non-Hazardous | 32A/50A/48AB/50B FULTON V.T BOILER 10 HP NB61344 GAS FIRED 1991 50(A)SECONDARY LOW WATER CUT OFF MANUAL RESET SWITCH ... | $0 | $0 | Jun 24, 2004 |
| Dec 7, 1988 | 32001269X | RESOLVE | Hazardous | — | $150 | $0 | Jan 26, 1989 |