ECB violations
Bilingual Head Start Site Ii, Manhattan • Block 01616 • Lot 0001
207 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Aug 13, 2026 | 39200454Y | ACTIVE | CLASS - 1 | CLASS1 ITEM: RTS FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER, SERVICE ELEVATOR EQUIPMENT AS PER CODE BC3001... | $1,250 | $1,250 | Oct 22, 2026 |
| May 14, 2026 | 39188690R | ACTIVE | CLASS - 1 | I OBSERVED IN APT #28A TWO ELECTRIC BASEBOARD HEATERS,CT METERS AND RECEPTACLES INSTALLED WITHOUT AN ELECTRICAL PERMI... | $800 | $0 | Jul 23, 2026 |
| Feb 10, 2026 | 39176760P | RESOLVE | CLASS - 2 | CLASS 2: EMR ACCESS DENIED TO PERFORM FULL INSPECTION. | $0 | $0 | Apr 16, 2026 |
| Nov 26, 2024 | 35689105R | RESOLVE | CLASS - 2 | REMOVAL OF PUBLIC PROTECTION FROM UNSAFE FACADE WITHOUT APPROVAL FROM THE DEPARTMENT. NOTE: AT THE TIME OF INSPECTION... | $0 | $0 | Jan 30, 2025 |
| Oct 1, 2024 | 37030928P | RESOLVE | CLASS - 1 | FAILURE TO SUBMIT THE REQUIRED PARKING STRUCTURE INITIAL OBSERVATION REPORT FOR AN EXISTING PARKING STRUCTURE OR A PE... | $0 | $0 | Jul 1, 2025 |
| Jul 30, 2024 | 35671490R | ACTIVE | CLASS - 2 | FAILURE TO CONDUCT OR FILE A FINAL INSPECTION OF PERMITTED WORK WITH DEPT.I OBSERVED THE INSTALLED WORK OF NET STANDP... | $1,250 | $0 | Oct 3, 2024 |
| Jun 3, 2024 | 39115815Y | RESOLVE | CLASS - 2 | WORK DOES NOT CONFORM TO APPROVED PLANS OR AMENDMENTS. APPROVED PLANS FOR JOB #M08032797 IDENTIFY WINDOW OPENING OF 3... | $0 | $0 | Sep 12, 2024 |
| Jan 30, 2024 | 39104768R | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTE: AT TIME OF INSPECTION OF LEVEL 1 DOWN RAMP IN GARAGE OBS... | $1,250 | $0 | Sep 13, 2024 |
| Oct 23, 2023 | 35656149H | RESOLVE | CLASS - 1 | WORK DOES NOT CONFORM TO APPROVED CONSTRUCTION DOCUMENTS AND/OR APPROVED AMENDMENTS: AFTER REVIEW OF CONSTRUCTION PLA... | $0 | $0 | Jun 20, 2024 |
| Oct 10, 2023 | 35676456X | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED PARKING GARAGE CELLAR AND 1ST FLOOR, EVIDENCE OF WATER P... | $1,250 | $0 | Apr 19, 2024 |
| Jul 27, 2023 | 35666999N | RESOLVE | CLASS - 1 | BC3303.10 FAILURE TO COMPLY WITH TENANT PROTECTION PLAN(TPP). NOTE: ATTIME OF INSPECTION, OBSERVED WORK BEING PERFORM... | $2,500 | $0 | Oct 5, 2023 |
| Apr 5, 2023 | 39514998Y | RESOLVE | CLASS - 2 | AT TIME OF INSPECTION OBSERVED ACTIVE JOBSITE CURRENTLY WORKING ON FACADE. UPON REQUESTING SST CARDS ONE WORKER CARD ... | $0 | $0 | Dec 28, 2023 |
| Apr 5, 2023 | 39514996K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN SUPPORTED SCAFFOLD IN CODE COMPLYING MANNER. AT TIME OF INSPECTION OBSERVED SUPPORTED SCAFFOLD ER... | $0 | $0 | Jun 15, 2023 |
| Jan 2, 2023 | 39511085X | RESOLVE | CLASS - 2 | AT THE TIME OF MY INSPECTION , I OBSERVED A PARAPET INFORMATON SIGN AT EXPOSURE 1 SHEDS'S PARAPET, NOT IN COMPLIANCE.... | $0 | $0 | Mar 9, 2023 |
| Jan 2, 2023 | 39511084Y | RESOLVE | CLASS - 2 | AT THE TIME OF MY INSPECTION, I OBSERVED ADVERTISING SIGNAGE ON SHEDS PARAPET AT EXPOSURE 1 THROUGHOUT . THE ADVERTIS... | $0 | $0 | Mar 9, 2023 |
| Oct 31, 2022 | 39508473K | RESOLVE | CLASS - 2 | OBSERVED ALL TIE-BACKS FOR SUSPENDED SCAFFOLDS HAD AT LEAST 1 SINGLE ANGLE TIE-BACK CONTRARY TO BC3314.10.9 AND APPRO... | $0 | $0 | Jan 12, 2023 |
| May 10, 2021 | 39040855P | RESOLVE | CLASS - 2 | CAT1 TAG IN ELEVATOR MACHINE ROOM EXPIRED. COMPLETE TSET & PROVIDE. BRAKE TAG IN ELEVATIOR MACHINE ROOM EXPIRED. COMP... | $655 | $0 | Jun 24, 2021 |
| Jan 28, 2021 | 39035575Y | RESOLVE | CLASS - 2 | HOIST ROPE SHORTENING. (COUNTERWEIGHTS JUST TOUCHING DOWN ON BUFFER) CAT 1 TAG MISSING. PERFORM AND FILE TEST. BRAKE ... | $1,562 | $0 | Mar 18, 2021 |
| Oct 23, 2020 | 39030918Y | RESOLVE | CLASS - 2 | MACHINE BRAKE TAG EXPIRED PROVIDE, DLM STICKER MISSING FROM CONTROLLER BOARD PROVIDE. | $655 | $0 | May 6, 2021 |
| Mar 3, 2020 | 39018809N | RESOLVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN CONTROLLER AS MANDATED IN 3.10.12 OF APPENDIX K3 OF THE 2014 NYC BC. REMEDY: INS... | $1,250 | $0 | Jun 29, 2020 |
| Mar 3, 2020 | 39018820Y | RESOLVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN CONTROLLER AS MANDATED IN 3.10.12 OF APPENDIX K3 OF THE 2014 NYC BC. REMEDY: INS... | $1,250 | $0 | Jul 15, 2021 |
| Mar 3, 2020 | 39018821X | RESOLVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN CONTROLLER AS MANDATED IN 3.10.12 OF APPENDIX K3 OF THE 2014 NYC BC. REMEDY: INS... | $3,125 | -$3,125 | Apr 23, 2021 |
| Mar 3, 2020 | 39018811M | RESOLVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN CONTROLLER AS MANDATED IN 3.10.12 OF APPENDIX K3 OF THE 2014 NYC BC. REMEDY: INS... | $3,125 | $0 | Apr 23, 2021 |
| Mar 3, 2020 | 39018810K | RESOLVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN CONTROLLER AS MANDATED IN 3.10.12 OF APPENDIX K3 OF THE 2014 NYC BC. REMEDY: INS... | $3,125 | $0 | Apr 23, 2021 |
| Jan 27, 2020 | 39016327L | RESOLVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 0F APPENDIX K3 OF 2014 NYCBC. REMEDY FILE... | $0 | $0 | Mar 13, 2020 |
| Nov 21, 2019 | 38272454K | RESOLVE | CLASS - 2 | 52B14, 14M07, 39O02: 52-B-14 SHORTEN HOISTWAY ROPES TO PROVIDE MINIMUM6" RUNBY, 14-M-07 PROVIDE IN CAR MIRROR, 39-O-0... | $1,562 | -$1,562 | Jul 13, 2020 |
| Aug 22, 2019 | 38271232K | RESOLVE | CLASS - 2 | 59-BB-15, 68-B-7, 13-X-10. 59-BRAKE MAINTENANCE TAG EXPIRED 68- LOG BOOK NOT UP TO DATE NB EMERGENCY LIGHTS INOPREATIVE | $0 | $0 | Oct 24, 2019 |
| Aug 22, 2019 | 38271231Z | RESOLVE | CLASS - 2 | 59-BB-15, 68-B-7 59 BRAKE MAINTENANCE TAG EXPIRED 68 LOG BOOK NOT UP TO DATE. | $0 | $0 | Oct 24, 2019 |
| Aug 22, 2019 | 38271230R | RESOLVE | CLASS - 2 | 59-BB-15, 68-B-7 59-BRAKE MAINTENANCE TAG EXPIRED 68 LOG BOOK NOT UP TO DATE. | $0 | $0 | Oct 24, 2019 |
| Aug 7, 2019 | 38270871M | RESOLVE | CLASS - 2 | 97X17 OUT OF SERVICE. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE. 3 ELEVATORS IN BUILDING WITH 35 FLOO... | $0 | $0 | Oct 10, 2019 |
| Jun 13, 2019 | 38269715M | RESOLVE | CLASS - 2 | 2.B.7,42.BB.8,59.BB.5,68.M.7,70.O.2=2-B-7 NEED TO PROVIDE A DEDICATED PHONE LINE FOR OUTSIDE 42-BB-8 REMOVE ALL OLD T... | $625 | $0 | Oct 17, 2019 |
| Jun 10, 2019 | 38269913N | RESOLVE | CLASS - 1 | 97.X.17,59.M.7=97.X.17 RESTORE TO SERVICE FOR PROPER INSPECTION BY DOE 59.M.7 MACHINE BRAKE TAG MISSING PROVIDE | $0 | $0 | Aug 8, 2019 |
| Apr 9, 2019 | 38269107Z | RESOLVE | CLASS - 2 | 68B7,59BB5;68-B-7 NO CURRENT MAINTENANCE LOG/MCP IN MOTOR ARM LAST ONEB FROM 2017,PROVIDE CURRENT LOG BOOKS/59-BB-5 E... | $0 | $0 | Jun 6, 2019 |
| Dec 14, 2018 | 38266830Y | RESOLVE | CLASS - 1 | 5A10,59BB7. 5A10 CEASE USE ITEM. DOOR LOWE RESTRICTOR HAS BEEN TAMPERED WITH DISABLED AND RENDERED INOPERATIVE. THIS ... | $1,250 | $0 | Feb 7, 2019 |
| Nov 9, 2018 | 38266383L | RESOLVE | CLASS - 2 | 2X10,68B7,100Y9,16H11. 2-PHONE INOPERATIVE; 68-LOGBOOK NOT UP TO DATE; 100-HYDRO-OIL ON MR FLOOR; 16-HOISTWAY RELEASE... | $625 | $0 | Feb 21, 2019 |
| Sep 28, 2018 | 35360215Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COKPLIANT MANNER AT TIME OF INSPECTION NOTED AT FRONT FACADE ARCADE. DELAMINATION OF... | $310 | $0 | Nov 29, 2018 |
| Sep 18, 2018 | 38265244R | RESOLVE | CLASS - 1 | RTS97X10; 56Y13;52Y02,60Q03,59M07. 97X10-RETURN TO SERVICE. THE ELEVA TOR ON THE PROPERTY IS OUT OF SERVICE CREATING ... | $1,250 | $0 | Jan 10, 2019 |
| Aug 15, 2018 | 38264766J | RESOLVE | CLASS - 1 | 05A10)CEASE USE ITEM, DOOR ZONE RESTRICTOR HAS BEEN TAMPERED WITH, DISABLED AND RENDERED INOPERATIVE. THIS IS A SAFET... | $1,250 | $0 | Oct 4, 2018 |
| Jun 8, 2018 | 37010157H | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION #38257893R ISSUED ON 09/19/17 AND TO FILE ... | $625 | $0 | Aug 30, 2018 |
| Jun 6, 2018 | 38263181J | RESOLVE | CLASS - 1 | 97X17 ENTIRE DEVICE INOPERATIVE RESTORE DEVICE TOP SERVICE AND CALL DOB FOR INSPECTION. | $312 | $0 | Nov 1, 2018 |
| May 8, 2018 | 38263280P | RESOLVE | CLASS - 2 | 97X10)RESTORE TO SERVICE FOR PROPER INSPECTION BY DOB. | $655 | $0 | Aug 30, 2018 |
| Apr 24, 2018 | 38262808J | RESOLVE | CLASS - 2 | 59BB7,57M7,71L10,99M7. 59BB7-MACHINE BRAKE TAG EXPIRED PROVIDE; 57M7-FIRE EXTINGUISHER MISSIG PROVIDE; 71L10-PIT LIGH... | $625 | $0 | Aug 16, 2018 |
| Apr 16, 2018 | 38262521M | RESOLVE | CLASS - 2 | 2M7,59M7,56Y13,39O2,99M7. 2M7-OUTSIDE COMM MISSING PROVIDE; 59M7-BRAKETAG MISSING PROVIDE; 56Y13-HOIST MACHINE OIL LE... | $1,562 | $0 | May 31, 2018 |
| Mar 15, 2018 | 38261836M | RESOLVE | CLASS - 1 | 5A10,3E10,16D6,34O2,42D6,40AA2,68B7,68BB7,70B7,99BB5. (5A)DOOR ZONE RESTRICTOR HAS BEEN TAMPERED WITH/DISABLED & REND... | $1,250 | $0 | Sep 13, 2018 |
| Mar 15, 2018 | 38261837Y | RESOLVE | CLASS - 2 | 17D6,60X10,61B10,68B7,70B7,99BB5. (17D)FLOORS 7,13,16. (60X)REPAIR LIGHTING LEADING TO MACHINE ROOM. (61B)UNABLE TO O... | $0 | $0 | May 3, 2018 |
| Dec 8, 2017 | 35264947J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN EXTERIOR BUILDING FACADE AND APPURTENANCES.*NORTH WEST ELEVATION EXPOSURE 8 CRACKED CONCRETE PARA... | $500 | $0 | Sep 13, 2018 |
| Dec 7, 2017 | 38260033Y | RESOLVE | CLASS - 2 | 10E10,40AA2,42D6,61B7,70O2. (10E)RUBBING/SCRAPING- REPAIR. (42D)SECURE WIRES ON TERMINAL/STRIP FOR MAIN PC BOARD. (61... | $500 | $0 | Jan 25, 2018 |
| Dec 7, 2017 | 38260034X | RESOLVE | CLASS - 1 | CEASE USE. 5A10,2X10,11I10,40AA2,68BB7,70O2. (5A)DOOR ZONE RESTRICTOR HAS BEEN TAMPERED W/ DISABLED & RENDERED INOPER... | $1,000 | $0 | Jan 25, 2018 |
| Sep 20, 2017 | 35259416Y | RESOLVE | CLASS - 1 | DESIGNATED FOREMAN/RIGGER.RIGGER OR DESIGNATED FOREMAN MUST BE ON SITEWHILE USE OF SUSPENDED SCAFFOLD.NOTE:AT TIME OF... | $1,600 | $0 | Nov 9, 2017 |
| Sep 20, 2017 | 35259418H | RESOLVE | CLASS - 1 | BC3310.4/SITE CONDITION.CONDITION OF ISTE HAS TO BE IN CONFORMANCE WITH SSP.NOTE:AT TIME OF INSPECTION I OBSERVED ACT... | $1,630 | $0 | Apr 12, 2018 |