ECB violations
183-185 East 100 Street, Manhattan • Block 01628 • Lot 0026
41 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Oct 8, 2025 | 39162948J | ACTIVE | CLASS - 2 | FAILURE TO COMPLY WITH COMMISSIONERS ORDER TO FILE A CERTIFICATE OF CORRECTION FOR VIOLATION# 039100718K. | $1,250 | $0 | Oct 20, 2025 |
| Oct 8, 2025 | 39162927K | ACTIVE | CLASS - 2 | FAILURE TO COMPLY WITH COMMISSIONERS ORDER TO FILE A CERTIFICATE OF CORRECTION FOR VIOLATION # 039100717Z. | $1,250 | $0 | Oct 20, 2025 |
| Oct 8, 2025 | 39162943K | ACTIVE | CLASS - 2 | FAILURE TOCOMPLY WITH COMMISSIONERS ORDER TO FILE A CERTIFICATE OF CORRECTION FOR VIOLATION # 039100716R | $1,250 | $0 | Oct 20, 2025 |
| Nov 14, 2024 | 39130311X | ACTIVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING. OBSERVED DEFECTIVE DOOR NO DOOR KNOBS ON DOORS LOCATED AT BASEMENT LEVEL. INCASE OF EMERG... | $625 | $0 | Nov 21, 2024 |
| Nov 14, 2024 | 39130279P | ACTIVE | CLASS - 2 | I OBSERVED IN THE 1ST FLOOR MAINTENANCE ROOM THE GFCI DEFECTIVE THEREFORE FAILING TO PROVIDE GFCI PROTECTION AS REQUI... | $2,400 | $0 | Nov 21, 2024 |
| Nov 14, 2024 | 39130264M | ACTIVE | CLASS - 2 | I OBSERVED IN THE FIRST FLOOR MAINTENANCE ROOM A DEFECTIVE GFCI WHICH OFFERS NO PROTECTION WITHIN 6 FEET OF A SINK., ... | $2,400 | $0 | Nov 21, 2024 |
| Nov 14, 2024 | 39130310Y | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $2,500 | -$2,500 | Nov 21, 2024 |
| Dec 5, 2023 | 39100718K | ACTIVE | CLASS - 2 | FOUND WEIL MCLAIN EG/PEG-75 299000 BTU BOILER NOT REGISTERED WITH DOB,PULL PERMIT BRING JOB UP TO CURRENT CODE AND CA... | $625 | $0 | Jan 4, 2024 |
| Dec 5, 2023 | 39100716R | ACTIVE | CLASS - 2 | FOUND WEIL MCLAIN EG/PEG-75 299000 BTU BOILER NOT REGISTERED WITH DOB, PULL PERMIT BRING JOB UP TO CURRENT CODE AND C... | $625 | $0 | Jan 4, 2024 |
| Dec 5, 2023 | 39100717Z | ACTIVE | CLASS - 2 | FOUND WEIL MCLAIN EG/PEG-75 299000 BTU BOILER NOT REGISTERED WITH DOB,PULL PERMIT, BRING JOB UP TO CURRET CODE AND CA... | $625 | $0 | Jan 4, 2024 |
| Jul 27, 2023 | 39091186R | ACTIVE | CLASS - 2 | FAILURE TO COMPLY WITH COMMISSIONERS ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDING. FILE ... | $1,250 | $0 | Jul 31, 2023 |
| Jul 27, 2023 | 39091187Z | ACTIVE | CLASS - 2 | FAILURE TO COMPLY WITH COMMISSIONERS ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDING. FILE ... | $1,250 | $0 | Jul 31, 2023 |
| Jul 27, 2023 | 39091185P | ACTIVE | CLASS - 2 | FAILURE TO COMPLY WITH COMMISSIONERS ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDING. FILE ... | $1,250 | $0 | Jul 31, 2023 |
| Jan 3, 2023 | 39076815P | ACTIVE | CLASS - 2 | AS PER ONE WEIL MCLAIN EG-75 HEATING BOILER. NO. 168340-01. BOILER NOT REGISTERED. REGISTER BOILER. APPLY FOR PROPER ... | $625 | $0 | Jan 10, 2023 |
| Jan 3, 2023 | 39076814N | ACTIVE | CLASS - 2 | AS PER ONE WEIL MCLAIN EG-75 HOT WATER HEATING BOILER. BOILER NOT REGISTERED AS PER DOB RECORDS. REGISTER BOILER. APP... | $625 | $0 | Jan 10, 2023 |
| Jan 3, 2023 | 39076816R | ACTIVE | CLASS - 2 | AS PER ONE WEIL MCLAIN EG-75, HOT WATER HEATING BOILER. MD 168340-02. BOILER NOT REGISTERED. REGISTER BOILER. APPLY F... | $625 | $0 | Jan 10, 2023 |
| Nov 5, 2021 | 35631757K | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.LACK OF EMERGENCY LIGHTING FOR EXITS EXIT DISCHARGES AND PUBIC ... | $1,250 | $0 | Feb 17, 2022 |
| Sep 15, 2021 | 39047500H | ACTIVE | CLASS - 2 | PREVIOUS VIO#39017417J/EXPANSION TANK IS FULL/MOTORIZED FRESH AIR LOUVER MISSING WHISKER SWITCH INTERLOCKED WITH ALL ... | $1,562 | $0 | Oct 15, 2021 |
| Sep 15, 2021 | 39047501J | ACTIVE | CLASS - 2 | PREVIOUS VIO#39017418L;CORRECT VIOLATION AND SUBMIT THE CERTIFICATE OF CORRECTION | $1,562 | $0 | Oct 15, 2021 |
| Sep 15, 2021 | 39047502L | ACTIVE | CLASS - 2 | PREVIOUS VIO#39017419N;CORRECT VIOLATION AND SUBMIT THE CERTIFICATE OF CORRECTION | $1,562 | $0 | Oct 15, 2021 |
| Feb 12, 2020 | 39017419N | ACTIVE | CLASS - 2 | FOUND 1 WEIL MCLAIN EG-75 299,000 BTU GAS FIRED HOT WATER BOILER NOT REGISTERED. REGISTER BOILER. | $625 | $0 | Feb 21, 2020 |
| Feb 12, 2020 | 39017417J | ACTIVE | CLASS - 2 | FOUND 1 WEIL MCLAIN EG-75 299,000BTU GAS FIRED HOT WATER BOILER NOT REGISTERED. REGISTER BOILER | $625 | $0 | Feb 21, 2020 |
| Feb 12, 2020 | 39017418L | ACTIVE | CLASS - 2 | FOUND 1 WEIL MCLAIN EG-75 299,000BTU GAS FIRED HOT WATER BOILER NOT REGISTERED. REGISTER BOILER. | $625 | $0 | Feb 21, 2020 |
| Sep 11, 2019 | 39009381R | RESOLVE | CLASS - 2 | NOTED: OBSERVED AT EXPOSURE #1 SOUTH ELEVATION, BULGING CEMENT AND AN APPROXIMATELY 1" HORIZONTAL CRACK THROUGHOUT TH... | $0 | $0 | Sep 20, 2019 |
| Mar 22, 2019 | 35383815J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. NOTED:OBSERVED AT EXP1 FRONT (SOUTH ELEVATION)-1"CRACK ALONG T... | $0 | $0 | May 30, 2019 |
| Sep 28, 2018 | 35361392J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. NOTED:AT ROOF AT CHIMNEY, BRICKS ARE LOOSE, CRACKED AND SPALLI... | $0 | $0 | Nov 29, 2018 |
| Sep 14, 2018 | 35347397H | ACTIVE | CLASS - 1 | EC250.53 WATER METER JUMPER IS MISSING. OBSERVED THE FOLLOWING VIOLATING CONDITION IN THE CELLAR. WATER METER JUMPER ... | $0 | $0 | Dec 6, 2018 |
| Jun 27, 2018 | 32097149K | ACTIVE | CLASS - 2 | 50A-C. AS PER CLASS 2(B254) 28-301.1, FAILURE TO MAINTAIN. (50A)NO PROVING SWITCH ON MOTORIZED FRESH AIR DAMPERS. (50... | $0 | $0 | Oct 11, 2018 |
| Apr 6, 2018 | 35328720P | ACTIVE | CLASS - 2 | FAILURE TO SECURE/SUPPORT RACEWAYS/CABLE ASSEMBLIES/BOXES/CABINETS/ FITTINGS. OBSERVED IN BASEMENT BOILER ROOM ON AUX... | $0 | $0 | Jun 28, 2018 |
| Apr 6, 2018 | 35329489X | ACTIVE | CLASS - 1 | MISC VIOLATION. RESIDENTIAL GAS FLEX USED ON COMMERCIAL EQUIPMENT. OB SERVED IN LAUNDRY ROOM RESIDENTAL GAS FLEX HOSE... | $0 | $0 | Jun 21, 2018 |
| Apr 6, 2018 | 35329490N | ACTIVE | CLASS - 1 | WORK W/O A PERMIT. OBSERVED IN BOILER ROOM TWO HOT WATER STORAGE TANKSINSTALLED. DOB RECORDS DO NOT SHOW ANY RECORDS ... | $0 | $0 | Jun 21, 2018 |
| Apr 6, 2018 | 35329491P | ACTIVE | CLASS - 1 | FAILURE TO HAVE NEW OR ALTERED PLUMBING SYSTEM TESTED. OBSERVED IN BOILER ROOM IS CELALR TWO HOT WATER STORAGE TANKS ... | $0 | $0 | Jun 21, 2018 |
| Apr 6, 2018 | 35325722P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.NO FIRE STOPPING PER712.3; 27-345. NOTED: OBSERVED AT CELLAR, WITHI... | $0 | $0 | Jun 7, 2018 |
| Apr 6, 2018 | 35325721N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG WALL(S) OR APPURTENANCES. NOTED: OBSERVED AT FRONT OF BUILDING. RETAINING WALL HAVE HORIZONT... | $0 | $0 | Jun 7, 2018 |
| Aug 23, 2017 | 35289824K | ACTIVE | CLASS - 2 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT,APPARATUS DEVICES,APPLICANCE WIRING IN USE.OBSERVED IN BOILER ROOM ... | $0 | $0 | Dec 21, 2017 |
| Aug 23, 2017 | 35289823Z | RESOLVE | CLASS - 2 | FAILURE TO ADEQUATELY GROUND ELECTRICAL SYSTEMS OBSERVED WATER METER W/OUT REQUIRED JUMPER INSTALLED ACROSS METER.REM... | $0 | $0 | Dec 21, 2017 |
| Mar 27, 2017 | 35235664R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NO FIRE STOPPING PER BC 712.3;27-345: MISSING FIRE STOP AT CELLAR ... | $0 | $0 | May 4, 2017 |
| Mar 27, 2017 | 35235742N | RESOLVE | CLASS - 1 | SEC. 404.1 GAS PIPING NOT LABELED. OBSERVED ON 3-27-17 GAS PIPING IN BASEMENT NOT LABELED. REMEDY: COMPLY W/SUMMONS. | $0 | $0 | Apr 27, 2017 |
| Mar 27, 2017 | 35235741L | ACTIVE | CLASS - 1 | SEC. 408.2 DRIPS FUTURE CONNECTIONS EXIST DOWN STREAM OF APPLICANCE. OBSERVED ON 3-27-17 AT THE ABOVE ADDRESS FUTURE ... | $0 | $0 | Apr 27, 2017 |
| Sep 16, 2016 | 35207839L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN IN CODE-COMPLIANT MANNER. DEFECT NOTED: RETAINING WALL AT FRONT OF PREMISES HAS APPROX 2"WIDE HOR... | $0 | $0 | Nov 17, 2016 |
| Sep 16, 2016 | 35208029Y | ACTIVE | CLASS - 1 | MISC VIOL. 402.5 OBSERVED ON 9/16/16 @9:45AM INSTALLED DRESSER COUPLING IN HOUSE SIDE OF GAS METER,NLABLEED GAS PIPIN... | $0 | $0 | Nov 17, 2016 |