Skip to content

ECB violations

183-185 East 100 Street, Manhattan • Block 01628 • Lot 0026

41 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Oct 8, 2025 39162948J ACTIVE CLASS - 2 FAILURE TO COMPLY WITH COMMISSIONERS ORDER TO FILE A CERTIFICATE OF CORRECTION FOR VIOLATION# 039100718K. $1,250 $0 Oct 20, 2025
Oct 8, 2025 39162927K ACTIVE CLASS - 2 FAILURE TO COMPLY WITH COMMISSIONERS ORDER TO FILE A CERTIFICATE OF CORRECTION FOR VIOLATION # 039100717Z. $1,250 $0 Oct 20, 2025
Oct 8, 2025 39162943K ACTIVE CLASS - 2 FAILURE TOCOMPLY WITH COMMISSIONERS ORDER TO FILE A CERTIFICATE OF CORRECTION FOR VIOLATION # 039100716R $1,250 $0 Oct 20, 2025
Nov 14, 2024 39130311X ACTIVE CLASS - 2 EXIT DOOR NOT SELF-CLOSING. OBSERVED DEFECTIVE DOOR NO DOOR KNOBS ON DOORS LOCATED AT BASEMENT LEVEL. INCASE OF EMERG... $625 $0 Nov 21, 2024
Nov 14, 2024 39130279P ACTIVE CLASS - 2 I OBSERVED IN THE 1ST FLOOR MAINTENANCE ROOM THE GFCI DEFECTIVE THEREFORE FAILING TO PROVIDE GFCI PROTECTION AS REQUI... $2,400 $0 Nov 21, 2024
Nov 14, 2024 39130264M ACTIVE CLASS - 2 I OBSERVED IN THE FIRST FLOOR MAINTENANCE ROOM A DEFECTIVE GFCI WHICH OFFERS NO PROTECTION WITHIN 6 FEET OF A SINK., ... $2,400 $0 Nov 21, 2024
Nov 14, 2024 39130310Y ACTIVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... $2,500 -$2,500 Nov 21, 2024
Dec 5, 2023 39100718K ACTIVE CLASS - 2 FOUND WEIL MCLAIN EG/PEG-75 299000 BTU BOILER NOT REGISTERED WITH DOB,PULL PERMIT BRING JOB UP TO CURRENT CODE AND CA... $625 $0 Jan 4, 2024
Dec 5, 2023 39100716R ACTIVE CLASS - 2 FOUND WEIL MCLAIN EG/PEG-75 299000 BTU BOILER NOT REGISTERED WITH DOB, PULL PERMIT BRING JOB UP TO CURRENT CODE AND C... $625 $0 Jan 4, 2024
Dec 5, 2023 39100717Z ACTIVE CLASS - 2 FOUND WEIL MCLAIN EG/PEG-75 299000 BTU BOILER NOT REGISTERED WITH DOB,PULL PERMIT, BRING JOB UP TO CURRET CODE AND CA... $625 $0 Jan 4, 2024
Jul 27, 2023 39091186R ACTIVE CLASS - 2 FAILURE TO COMPLY WITH COMMISSIONERS ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDING. FILE ... $1,250 $0 Jul 31, 2023
Jul 27, 2023 39091187Z ACTIVE CLASS - 2 FAILURE TO COMPLY WITH COMMISSIONERS ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDING. FILE ... $1,250 $0 Jul 31, 2023
Jul 27, 2023 39091185P ACTIVE CLASS - 2 FAILURE TO COMPLY WITH COMMISSIONERS ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDING. FILE ... $1,250 $0 Jul 31, 2023
Jan 3, 2023 39076815P ACTIVE CLASS - 2 AS PER ONE WEIL MCLAIN EG-75 HEATING BOILER. NO. 168340-01. BOILER NOT REGISTERED. REGISTER BOILER. APPLY FOR PROPER ... $625 $0 Jan 10, 2023
Jan 3, 2023 39076814N ACTIVE CLASS - 2 AS PER ONE WEIL MCLAIN EG-75 HOT WATER HEATING BOILER. BOILER NOT REGISTERED AS PER DOB RECORDS. REGISTER BOILER. APP... $625 $0 Jan 10, 2023
Jan 3, 2023 39076816R ACTIVE CLASS - 2 AS PER ONE WEIL MCLAIN EG-75, HOT WATER HEATING BOILER. MD 168340-02. BOILER NOT REGISTERED. REGISTER BOILER. APPLY F... $625 $0 Jan 10, 2023
Nov 5, 2021 35631757K ACTIVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.LACK OF EMERGENCY LIGHTING FOR EXITS EXIT DISCHARGES AND PUBIC ... $1,250 $0 Feb 17, 2022
Sep 15, 2021 39047500H ACTIVE CLASS - 2 PREVIOUS VIO#39017417J/EXPANSION TANK IS FULL/MOTORIZED FRESH AIR LOUVER MISSING WHISKER SWITCH INTERLOCKED WITH ALL ... $1,562 $0 Oct 15, 2021
Sep 15, 2021 39047501J ACTIVE CLASS - 2 PREVIOUS VIO#39017418L;CORRECT VIOLATION AND SUBMIT THE CERTIFICATE OF CORRECTION $1,562 $0 Oct 15, 2021
Sep 15, 2021 39047502L ACTIVE CLASS - 2 PREVIOUS VIO#39017419N;CORRECT VIOLATION AND SUBMIT THE CERTIFICATE OF CORRECTION $1,562 $0 Oct 15, 2021
Feb 12, 2020 39017419N ACTIVE CLASS - 2 FOUND 1 WEIL MCLAIN EG-75 299,000 BTU GAS FIRED HOT WATER BOILER NOT REGISTERED. REGISTER BOILER. $625 $0 Feb 21, 2020
Feb 12, 2020 39017417J ACTIVE CLASS - 2 FOUND 1 WEIL MCLAIN EG-75 299,000BTU GAS FIRED HOT WATER BOILER NOT REGISTERED. REGISTER BOILER $625 $0 Feb 21, 2020
Feb 12, 2020 39017418L ACTIVE CLASS - 2 FOUND 1 WEIL MCLAIN EG-75 299,000BTU GAS FIRED HOT WATER BOILER NOT REGISTERED. REGISTER BOILER. $625 $0 Feb 21, 2020
Sep 11, 2019 39009381R RESOLVE CLASS - 2 NOTED: OBSERVED AT EXPOSURE #1 SOUTH ELEVATION, BULGING CEMENT AND AN APPROXIMATELY 1" HORIZONTAL CRACK THROUGHOUT TH... $0 $0 Sep 20, 2019
Mar 22, 2019 35383815J RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. NOTED:OBSERVED AT EXP1 FRONT (SOUTH ELEVATION)-1"CRACK ALONG T... $0 $0 May 30, 2019
Sep 28, 2018 35361392J RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. NOTED:AT ROOF AT CHIMNEY, BRICKS ARE LOOSE, CRACKED AND SPALLI... $0 $0 Nov 29, 2018
Sep 14, 2018 35347397H ACTIVE CLASS - 1 EC250.53 WATER METER JUMPER IS MISSING. OBSERVED THE FOLLOWING VIOLATING CONDITION IN THE CELLAR. WATER METER JUMPER ... $0 $0 Dec 6, 2018
Jun 27, 2018 32097149K ACTIVE CLASS - 2 50A-C. AS PER CLASS 2(B254) 28-301.1, FAILURE TO MAINTAIN. (50A)NO PROVING SWITCH ON MOTORIZED FRESH AIR DAMPERS. (50... $0 $0 Oct 11, 2018
Apr 6, 2018 35328720P ACTIVE CLASS - 2 FAILURE TO SECURE/SUPPORT RACEWAYS/CABLE ASSEMBLIES/BOXES/CABINETS/ FITTINGS. OBSERVED IN BASEMENT BOILER ROOM ON AUX... $0 $0 Jun 28, 2018
Apr 6, 2018 35329489X ACTIVE CLASS - 1 MISC VIOLATION. RESIDENTIAL GAS FLEX USED ON COMMERCIAL EQUIPMENT. OB SERVED IN LAUNDRY ROOM RESIDENTAL GAS FLEX HOSE... $0 $0 Jun 21, 2018
Apr 6, 2018 35329490N ACTIVE CLASS - 1 WORK W/O A PERMIT. OBSERVED IN BOILER ROOM TWO HOT WATER STORAGE TANKSINSTALLED. DOB RECORDS DO NOT SHOW ANY RECORDS ... $0 $0 Jun 21, 2018
Apr 6, 2018 35329491P ACTIVE CLASS - 1 FAILURE TO HAVE NEW OR ALTERED PLUMBING SYSTEM TESTED. OBSERVED IN BOILER ROOM IS CELALR TWO HOT WATER STORAGE TANKS ... $0 $0 Jun 21, 2018
Apr 6, 2018 35325722P RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.NO FIRE STOPPING PER712.3; 27-345. NOTED: OBSERVED AT CELLAR, WITHI... $0 $0 Jun 7, 2018
Apr 6, 2018 35325721N RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG WALL(S) OR APPURTENANCES. NOTED: OBSERVED AT FRONT OF BUILDING. RETAINING WALL HAVE HORIZONT... $0 $0 Jun 7, 2018
Aug 23, 2017 35289824K ACTIVE CLASS - 2 UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT,APPARATUS DEVICES,APPLICANCE WIRING IN USE.OBSERVED IN BOILER ROOM ... $0 $0 Dec 21, 2017
Aug 23, 2017 35289823Z RESOLVE CLASS - 2 FAILURE TO ADEQUATELY GROUND ELECTRICAL SYSTEMS OBSERVED WATER METER W/OUT REQUIRED JUMPER INSTALLED ACROSS METER.REM... $0 $0 Dec 21, 2017
Mar 27, 2017 35235664R RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NO FIRE STOPPING PER BC 712.3;27-345: MISSING FIRE STOP AT CELLAR ... $0 $0 May 4, 2017
Mar 27, 2017 35235742N RESOLVE CLASS - 1 SEC. 404.1 GAS PIPING NOT LABELED. OBSERVED ON 3-27-17 GAS PIPING IN BASEMENT NOT LABELED. REMEDY: COMPLY W/SUMMONS. $0 $0 Apr 27, 2017
Mar 27, 2017 35235741L ACTIVE CLASS - 1 SEC. 408.2 DRIPS FUTURE CONNECTIONS EXIST DOWN STREAM OF APPLICANCE. OBSERVED ON 3-27-17 AT THE ABOVE ADDRESS FUTURE ... $0 $0 Apr 27, 2017
Sep 16, 2016 35207839L RESOLVE CLASS - 2 FAILURE TO MAINTAIN IN CODE-COMPLIANT MANNER. DEFECT NOTED: RETAINING WALL AT FRONT OF PREMISES HAS APPROX 2"WIDE HOR... $0 $0 Nov 17, 2016
Sep 16, 2016 35208029Y ACTIVE CLASS - 1 MISC VIOL. 402.5 OBSERVED ON 9/16/16 @9:45AM INSTALLED DRESSER COUPLING IN HOUSE SIDE OF GAS METER,NLABLEED GAS PIPIN... $0 $0 Nov 17, 2016