ECB violations
189 East 100 Street, Manhattan • Block 01628 • Lot 0029
36 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Oct 8, 2025 | 39162991P | ACTIVE | CLASS - 2 | WEIL MCLAIN BOILER MODEL- EG65. CEILING INSULATION IS HANGING ON TOP OF BOILER. REPLACE INSULATION. | $1,250 | $0 | Oct 20, 2025 |
| Oct 8, 2025 | 39163091Y | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $2,500 | $0 | Oct 20, 2025 |
| Nov 14, 2024 | 39130304H | ACTIVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING. OBSERVED NON SELF CLOSING DOORS AT BASEMENT LEVEL AND ROOF LEVEL. POTENTIAL FIRE OR SMOKE... | $625 | $0 | Nov 21, 2024 |
| Nov 14, 2024 | 39130303X | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $2,500 | $0 | Nov 21, 2024 |
| Nov 14, 2024 | 39130284J | ACTIVE | CLASS - 2 | I OBSERVED IN THE FIRST FLOOR MAINTENANCE ROOM NO GFCI PROTECTION WITHIN 6 FEET OF A SINK., INSTALL GFC1 PROTECTION; ... | $2,400 | $0 | Nov 21, 2024 |
| Dec 21, 2023 | 39102044M | ACTIVE | CLASS - 1 | UNLAW ACTS: FAILURE TO COMPLY WITH COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION# 39076993H ISSUED ON 01/04/2023... | $2,500 | $0 | Jan 2, 2024 |
| Apr 5, 2023 | 39083145K | ACTIVE | CLASS - 2 | I OBSERVED IN THE MAINTENANCE CLOSET THE RECEPTACLE WITHIN 6 FEET OF THE SINK NOT OF THE GFCI TYPE., INSTALL GFC1 PRO... | $2,400 | $0 | Apr 27, 2023 |
| Jan 4, 2023 | 39076950H | ACTIVE | CLASS - 2 | OBSERVED EXCESSIVE COMBUSTIBLE STORAGE IN THE BOILER LOCATED IN THE BASEMENT, NO STORAGE SHALL BE STORED IN THE BOILE... | $625 | $0 | Jan 10, 2023 |
| Jan 4, 2023 | 39076951J | ACTIVE | CLASS - 2 | OBSERVED GAS PIPING IN BASEMENT HAS AREAS OF RUST AND CORROSION., REPAIR AND/OR REPLACE | $625 | $0 | Jan 10, 2023 |
| Jan 4, 2023 | 39076992X | ACTIVE | CLASS - 2 | OBSERVED: AT ROOF LEVEL, STAIRCASE EXTERIOR WALLS CRACKED NEAR EXIT DOOR, MAINTAIN EXTERIOR BUILDING WALL | $1,250 | $0 | Jan 10, 2023 |
| Jan 4, 2023 | 39076993H | ACTIVE | CLASS - 1 | OBSERVED: AT CELLAR LEVEL, EXIT PASSAGEWAY FROM BOILER ROOM TO THE FRONT IS BEING OBSTRUCTED BY FLAMMABLE MATERIALS, ... | $1,250 | $0 | Jan 10, 2023 |
| Jan 4, 2023 | 39076994J | ACTIVE | CLASS - 2 | OBSERVED: AT CELLAR LEVEL, FRONT EXIT DOOR AND FIRST FLOOR MAIN ENTRANCE DOOR DO NOT CLOSE PROPERLY WHEN INSPECTED., ... | $625 | $0 | Jan 10, 2023 |
| Jan 4, 2023 | 39076995L | ACTIVE | CLASS - 2 | OBSERVED: AT CELLAR LEVEL, BOILER ROOM, CEILING DOES NOT MEET TECHNICAL SPECIFICATIONS AND FIRE DEPARTMENT REQUIREMEN... | $625 | $0 | Jan 10, 2023 |
| Nov 5, 2021 | 35631755R | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.LACK OF EMERGENCY LIGHTING FOR EXITS,EXIT DISCHARGES AND PUBLIC... | $1,250 | $0 | Feb 17, 2022 |
| Sep 15, 2021 | 39047515K | ACTIVE | CLASS - 2 | INSULATION ON THE BOILER ROOM CEILING IS LOOSE AND FALLING/FRESH AIR LOUVER IS 1/2 CLOGGED;CORRECT VIOLATION AND SUBM... | $625 | $0 | Oct 15, 2021 |
| Sep 11, 2019 | 39009386X | RESOLVE | CLASS - 2 | NOTED: OBSERVED AT EXPOSURE #1 SOUTH ELEVATION, BULGING CEMENT AND AN APPROXIMATELY 1" HORIZONTAL CRACK THROUGHOUT TH... | $0 | $0 | Sep 20, 2019 |
| Mar 22, 2019 | 35383817N | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES NOTED: OBSERVED HORIZONTAL CRACKS AND BULGIN CEMET ALONG THE LE... | $0 | $0 | May 30, 2019 |
| Sep 28, 2018 | 35361393L | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. NOTED:AT BULKHEAD EXTERIOR, ABOVE BULKHEAD EXIT DOOR, BRICKS A... | $0 | $0 | Nov 29, 2018 |
| Sep 14, 2018 | 35347398J | ACTIVE | CLASS - 1 | EC250.53 WATER METER JUMPER IS MISSING. OBSERVED THE FOLLOWING VIOLATING CONDITION IN THE CELLAR. WATER METER JUMPER ... | $0 | $0 | Dec 6, 2018 |
| Jun 27, 2018 | 32097250P | ACTIVE | CLASS - 2 | 50A-F. AS PER CLASS 2(B254)28-301.1. FAILURE TO MAINTAIN. (50A)SAFETY VALVE FOR HEATING BOILER LEAKING.(50B)HOT WATER... | $0 | $0 | Oct 11, 2018 |
| Apr 20, 2018 | 32096413X | ACTIVE | CLASS - 2 | 5 - FOUND HYDROTHERM BOILER MODEL MR500BP 500,000 BTUS WITH DEFECTS TOBACKFLOW. CORRECT ANY OTHER VIOLATIONS AND SUBM... | $0 | $0 | Jul 5, 2018 |
| Mar 23, 2018 | 35325702H | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER:(INTERIOR)NOTED:OBSERVED AT ROOF AND STAIR BULKHEAD-SPALLING AN... | $0 | $0 | May 31, 2018 |
| Mar 23, 2018 | 35325700Y | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NO FIRE STOPPINGPER BC712.3;27-345.NOTED:OBSERVED AT CELLAR WIT... | $0 | $0 | May 31, 2018 |
| Mar 23, 2018 | 35325701X | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:OBSERVED AT REAR OF BUILDING FIRE ESCAPE DROP LADDER HAS ... | $0 | $0 | May 31, 2018 |
| Mar 23, 2018 | 35322499H | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING WALL(S)OR APPURTENANCES.NOTED:OBSERVED ATFRONT OF BUILDING THE RETAINING WALL HAS CRAKCS... | $0 | $0 | May 31, 2018 |
| Aug 22, 2017 | 35290004N | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: OBSERVED AT ROOF BULKHEAD, CEILING AROUND SKYLIGHT HAS ... | $0 | $0 | Dec 21, 2017 |
| Aug 22, 2017 | 35290003L | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. NOTED: OBSERVED AT FRONT OF BUILDING, RETAINING WALL HAS A CRA... | $0 | $0 | Dec 21, 2017 |
| Aug 22, 2017 | 35290278K | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED IN BSMT ANUNSERVICEABLE ELECTRICALLY POWERED GARBAGE COMP... | $2,500 | $0 | Oct 19, 2017 |
| Aug 22, 2017 | 35289646R | ACTIVE | CLASS - 1 | FGC 411.1 RESIDENTAIL GAS FLEX USED ON COMMERCIAL EQUIPMENT.OBSERVED ON 08/22/2017 @ABOVE ADDRESS RESIDENTAIL GAS FLE... | $0 | $0 | Dec 21, 2017 |
| Mar 27, 2017 | 35235745Z | ACTIVE | CLASS - 2 | FAIL TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 3-27-17 JIM CAPS INSTALLED IN BOILER AREA. REMEDY: REMOVE... | $0 | $0 | Apr 27, 2017 |
| Mar 27, 2017 | 35235746K | ACTIVE | CLASS - 1 | SEC. 401.1 GAS PIPING NOT LABELED OBSERVED ON 3-27-17 IN BASEMENT/CELLAR GAS PIPING NOT LABELED. REMEDY: COMPLY W/SUM... | $0 | $0 | Apr 27, 2017 |
| Mar 27, 2017 | 35235739M | ACTIVE | CLASS - 1 | SEC. 408.2 DRIPS FUTURE CONNECTION EXIST DOWN STREM OF APPLICANCE. OBSERVED ON 3-27-17 IN BASEMENT/CELLAR FUTURE GAS ... | $0 | $0 | Apr 27, 2017 |
| Sep 16, 2016 | 35207841K | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN IN CODE COMPLIANT MANNER. DEFECTS NOTED:RETAINING WALL AT FRONT OF PREMISES HAS APPRX 2"WIDE HORI... | $0 | $0 | Nov 17, 2016 |
| Sep 16, 2016 | 35207830P | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.DEFECT NOTE:APPROXIMAELY 9SF AREA CEILING MISSING AT 1ST FLR LOBBY.... | $0 | $0 | Nov 17, 2016 |
| Sep 16, 2016 | 35207829H | ACTIVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING THE FOLLOWING DOORS NOT SELF-CLOSING.EXIT DOOR TO ROOF LEVEL, ELECTIRC/GAS METER ROOM DOOR... | $0 | $0 | Nov 17, 2016 |
| Sep 16, 2016 | 35208031N | ACTIVE | CLASS - 2 | FAILURE TO HAVE NEW OR ALTERED PLY SYSTEM TESTED. OBSERVED ON 9/16/16 AT 10:15AM IN BST NEW HOT WATER STORAGE TANK AN... | $0 | $0 | Nov 17, 2016 |