ECB violations
2264 1 Avenue, Manhattan • Block 01710 • Lot 0003
6 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Jan 9, 2017 | 32086939L | ACTIVE | CLASS - 2 | AS PER CLASS 2 (B265) 28.303.7 FAILURE TO FILE A COMPLETE BOILER INSPECTION REPORT AS PER DOB RECORDS. SUBMIT A CURRE... | $2,500 | $0 | Feb 23, 2017 |
| Dec 7, 2007 | 32055174R | ACTIVE | Hazardous | 36,18B,48B,21B,38,50A. 50 A INSTALL STRUCTUAL SUPPORTS ON FLUE PIPE. | $400 | $0 | May 22, 2008 |
| Mar 13, 2006 | 32049079H | ACTIVE | Non-Hazardous | B4A/18A/24A/32A/48B/50/50A/50B/50C/BQ9/50D/36. 50- MISSING CONDENSATE TANK MUST BE REPLACED. 50A- MISSING BACK FLOW V... | $850 | $0 | Apr 27, 2006 |
| Mar 13, 2006 | 32049078X | ACTIVE | Non-Hazardous | 44C/50/50A. 50- FEED LINE TO BOILER IS PIPED DIRECTLY TO CAST IRON SECTION MUST BE PIPE TO RETURN LINE. 50A- REMOVE A... | $350 | $0 | Aug 9, 2007 |
| Apr 27, 2004 | 32044414N | RESOLVE | Non-Hazardous | 6A,32A,50. PEERLESS CD LP STEAM BOILER OIL FIRED.6A-SAFETY VALVE STUCKNO RESPONE TO MANUAL LIFT TEST.50-SAFETY VALVE ... | $0 | $0 | Jun 17, 2004 |
| Apr 27, 2004 | 32044412J | RESOLVE | Non-Hazardous | 48AB,50A,50B. FULTON VT BOILER,10HP,NB 92512,OIL FIRED 1995,50A-IMPROPER ARRANGEMENT OF BLOWDOWN VALVES (SWITCH AROUN... | $0 | $0 | Jun 17, 2004 |